Manual · Allen-Bradley
PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual
Manual270 pagesPDF 6.7 MB
User manual for the Allen-Bradley PowerFlex 20-COMM-C (coax) and 20-COMM-Q (fiber) ControlNet adapters for PowerFlex 7-Class drives.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation user manual for the PowerFlex 20-COMM-C (coax) and 20-COMM-Q (fiber) ControlNet adapters, used with PowerFlex 7-Class drives and other products that support a DPI adapter. It explains installing the adapter, setting node address switches, configuring it with a HIM or software, setting up I/O with ControlLogix, PLC-5 and SLC 500 controllers, using datalinks and explicit messaging, troubleshooting with the status indicators, and lists specifications, parameters and ControlNet objects.
Its parts
- Getting Started
- Installing the Adapter
- Configuring the Adapter
- Configuring the I/O
- Using the I/O
- Using Explicit Messaging
- Troubleshooting
- Using the Adapter in a DPI External Comms Kit (20-XCOMM-DC-BASE)
- Specifications
- Adapter Parameters
- ControlNet Objects
- Logic Command/Status Words
From the manual
Key facts from this manual
Each line names its page in the PDF.
This user manual covers the PowerFlex ControlNet adapters 20-COMM-C (coax) and 20-COMM-Q (fiber). These adapters fit in a PowerFlex 7-Class drive and connect it to a ControlNet network. The manual shows how to install the adapter, set its node address, read its status indicators and events, and lists its specifications.
- Device
- ControlNet network adapter that installs in a PowerFlex 7-Class drive p. 13
- Network
- ControlNet, 5 Mbps (fixed) p. 205
- Network connectors
- 20-COMM-C: BNC coax for Channel A and redundant Channel B; 20-COMM-Q: V-pin fiber p. 13
- Power
- 275 mA at 5 V DC, supplied by the drive or DPI External Comms Kit p. 205
- Compatible products
- PowerFlex 70, 700, 700H, 700S, 700L, 750-Series and Digital DC drives; SMC Flex and SMC-50 controllers; DPI External Comms Kit p. 15
- Drive link
- DPI at 125 kbps or 500 kbps, through an Internal Interface cable p. 13, 205
- I/O
- Logic Command/Reference and up to four pairs of Datalinks; explicit messaging p. 14
- Connections
- 20 CIP messaging connections; 1 exclusive-owner, up to 3 redundant-owner, or 1 listen-only I/O connection; 5 ms minimum RPI p. 205
- Node address
- Rotary switches 01…99 (default 02); 00 uses Parameter 03 - [CN Addr Cfg] p. 20
- Included cables
- One 2.54 cm (1 in.) and one 15.24 cm (6 in.) Internal Interface cable p. 15
- PowerFlex 750 use
- Needs adapter firmware 3.001 or later and a 20-750-20COMM or 20-750-20COMM-F1 Communication Carrier Card p. 15
- Firmware
- 20-COMM-C Series A FRN 2.xxx, Series B FRN 3.xxx; Series B firmware 2.xxx or later also fits the 20-XCOMM-DC-BASE kit p. 1, 13
- Configuration tools
- PowerFlex HIM, Connected Components Workbench 1.02+, DriveExplorer 2.01+, DriveExecutive 3.01+, RSNetWorx for ControlNet 6.00+ p. 14, 16
- Size and weight
- 16 mm x 103 mm x 80 mm; 85 g (3 oz.) p. 205
What this manual walks you through
- Quick start: installing and configuring the adapter p. 18
- Checking the equipment shipped and the equipment you supply p. 15, 16
- Setting the node address switches p. 20
- Connecting the adapter to the drive p. 21
- Reading the PORT, MOD, NET A and NET B status indicators p. 193, 194, 195
- Viewing adapter diagnostic items with the HIM p. 196, 197
- Viewing and clearing the event queue, with event codes p. 198, 199
- Adapter specifications p. 205, 206
Good to know
- Remove power from the drive and verify it has discharged before installing or removing the adapter. p. 21
- By default, Parameters 10 [Comm Flt Action] and 11 [Idle Flt Action] fault the drive when communication is lost or the controller is idle. p. 17
- Set the node address before power is applied; a new address takes effect only after a power cycle or reset. p. 20
- Tighten all screws to ground the adapter; the recommended torque is 0.9 N•m (8.0 lb•in). p. 21
- For PowerFlex 750-Series drives the manual recommends the 20-750-CNETC option module instead. p. 13
Questions this manual answers
What does a flashing red PORT light mean on a 20-COMM-C?
The adapter is not receiving a ping message from the drive. Check that the cables are secure and undamaged, then cycle power. p. 194
What does a steady red MOD light mean on a 20-COMM-C?
The adapter failed its hardware test. Cycle power, and replace the adapter if that does not help. p. 194
What does it mean when both NET lights are steady red?
A link interface failed. Check the media for broken cables, loose connectors and missing terminators, then cycle power or reset the adapter. p. 195
How do I set the ControlNet node address on a 20-COMM-C?
Turn the two rotary switches to 01 to 99 before power-up; setting 00 makes the adapter use Parameter 03 instead. p. 20
Can a 20-COMM-C be used in a PowerFlex 750 drive?
Yes, with firmware 3.001 or later and a 20-750-20COMM or 20-750-20COMM-F1 carrier card, with some limits on logic and speed scaling. p. 15
Contents
Chapters and sections
Each line opens the PDF at its page.
- PowerFlex 20-COMM-C/-Q ControlNet Adapters User Manual1
- Summary of Changes3
- Preface9
- Chapter 113
- Chapter 219
- Chapter 329
- Chapter 437
- Chapter 575
- Chapter 6129
- Chapter 7193
- Chapter 8201
- Appendix A205
- Appendix B207
- Appendix C211
- Appendix D247
- Glossary255
- Index263
- Back Cover / Publication 20COMM-UM003F-EN-P March 2013270
The whole text · 33 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Table of Contents5-8
- Preface9-12
- Chapter 113-18
- Chapter 219-28
- Chapter 329-36
- Chapter 4, pages 37 to 4637-46
- Chapter 4, pages 47 to 5647-56
- Chapter 4, pages 57 to 6657-66
- Chapter 4, pages 67 to 7467-74
- Chapter 5, pages 75 to 8375-83
- Chapter 5, pages 84 to 9284-92
- Chapter 5, pages 93 to 10193-101
- Chapter 5, pages 102 to 110102-110
- Chapter 5, pages 111 to 119111-119
- Chapter 5, pages 120 to 128120-128
- Chapter 6, pages 129 to 138129-138
- Chapter 6, pages 139 to 148139-148
- Chapter 6, pages 149 to 158149-158
- Chapter 6, pages 159 to 168159-168
- Chapter 6, pages 169 to 178169-178
- Chapter 6, pages 179 to 188179-188
- Chapter 6, pages 189 to 192189-192
- Chapter 7193-200
- Chapter 8201-204
- Pages 205 to 210205-210
- Appendix C, pages 211 to 219211-219
- Appendix C, pages 220 to 228220-228
- Appendix C, pages 229 to 237229-237
- Appendix C, pages 238 to 246238-246
- Appendix D247-254
- Glossary255-262
- Pages 263 to 270263-270
The file