PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 4, pages 57 to 66

Pages 57 to 66 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual

The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 20-COMM-C

Page 57

Configuring the I/O

4-21

Table 4.C Drives with 32-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Logic Command/ Status

Ref/Fdbk (32-bit)

Datalinks (32-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

D

✔ ✔

• PowerFlex 753 drives • PowerFlex 755 drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

Input

Output

6

TIP: For instructions on configuring the I/O for the adapter using Parameter 13 - [DPI I/O Cfg] and its Master-Slave hierarchy using Parameters 25 - [M-S Input] and 26 - [M-S Output], see Setting the I/O Configuration on page 3-3. When using Datalinks, up to 8 drive [Data In xx] parameters (300…307) and/or up to 8 [Data Out xx] parameters (310…317) must be assigned to point to the appropriate drive parameters for your application. 7. After setting the information in the drive’s New Module screen, click OK. The Module Properties screen appears. 8. Click the Connection tab.

9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0 milliseconds or greater. This value determines the maximum interval that a controller should use to move data to and from the adapter. To conserve bandwidth, use higher values for communicating with low priority devices. For this example, leave the ‘Inhibit Module’ and ‘Major Fault…’ boxes unchecked. 10. Click OK.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 58

4-22

Configuring the I/O

The new node (‘My_PowerFlex_70_EC_Drive’ in this example) now appears under the bridge (‘My_ControlNet_Bridge’ in this example) in the I/O Configuration folder. If you double-click the Controller Tags, you will see that module-defined data types and tags have been automatically created (Figure 4.4). After you save and download the configuration, these tags allow you to access the Input and Output data of the drive via the controller’s ladder logic. For this example, all Datalinks (A, B, C, and D) are enabled. The Input Size is set to 12 words and the Output Size is set to 10 words. Also, the following adapter I/O parameters are set to the following values. Adapter Parameter No.

Setting

13 - [DPI I/O Cfg] xxxx xxxx xxx1 1111

25 - [M-S Input] xxxx xxxx xxx1 1111

26 - [M-S Output] xxxx xxxx xxx1 1111

11. Reset the adapter (see Resetting the Adapter on page 3-7) or power cycle the drive. For the drive speed reference and Datalink parameter values and the adapter setup parameter values, see Drive and Adapter Parameter Settings on page 5-24. Figure 4.4

Controller Tags

Save the I/O Configuration to the Controller After adding the bridge and drive/adapter to the I/O configuration, you must download the configuration to the controller. You should also save the configuration as a file on your computer. TIP: When using RSLogix 5000 software, version 16.00 or later, you can add the I/O configuration of a Generic Profile while the controller is online and in the Run mode. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 59

Configuring the I/O

4-23

1. In the RSLogix 5000 window, select Communications > Download. The Download dialog box appears.

TIP: If a message box reports that RSLogix 5000 software is unable to go online, select Communications > Who Active to find your controller in the Who Active screen. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add or configure the ControlNet driver with RSLinx software. See Using RSLinx Classic Software on page 4-1 and RSLinx online help for details. 2. Click Download to download the configuration to the controller. When the download is successfully completed, RSLogix 5000 software goes into the Online mode and the I/O Not Responding box in the upper-left of the screen should be flashing green. 3. Select File > Save. If this is the first time you saved the project, the Save As dialog box appears. a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer. To be sure that the present project configuration values are saved, RSLogix 5000 software prompts you to upload them. Click Yes to upload and save the values. 4. Configure any Datalinks in the drive (for example, Datalink parameters 300…317 in PowerFlex 70/700 drives) that were enabled in the controller and adapter during I/O configuration (Table 4.A, Table 4.B or Table 4.C). Each Datalink being used must be assigned to a specific parameter in the drive or connected peripheral. If this is not done, the controller will receive or send placeholder data instead of actual drive or peripheral parameter values. 5. Place the controller in Remote Run or Run Mode.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 60

4-24

Configuring the I/O

6. Use the procedure in the subsection Use RSNetworx for ControlNet Software to Save the I/O to the Bridge on page 4-13 to: – Change the I/O Not Responding box in the upper-left of the RSLogix 5000 window from flashing green to steady green. – Remove the yellow warning symbols in the treeview under the I/O Configuration folder and drive profile.

PLC-5 Controller Example

After the adapter is configured, the connected drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple ControlNet network (see Figure 4.5). In our example, we will configure a PLC-5/40C controller to communicate with a drive using Logic Command/Status, Reference/Feedback, and Datalinks over the network. Figure 4.5

Example PLC-5 Controller ControlNet Network

PLC-5/40C Controller

Computer with ControlNet Connection

PowerFlex 70 Drive with 20-COMM-C Adapter

Channel A (optional redundancy)

Channel B

ControlNet Network

TIP: Information for PowerFlex 750-Series drives has been added to this manual where it is applicable.

Configuring Parameters for Network I/O Because the I/O for the drive is defined in the next subsection Use RSNetWorx for ControlNet Software to Configure the I/O and Save It to the Controller on page 4-25, there is no need to configure any I/O inside the RSLogix 5 project, version 7.00 or later, until using the I/O as described in Chapter 5. However, to get the adapter to operate with the I/O created in Chapter 5, you need to configure the adapter to accept the I/O and the drive to point to the appropriate Datalinks. 1. Set adapter Parameters 13 - [DPI I/O Cfg], 25 - [M-S Input], and 26 [M-S Output] to values that meet your application requirements.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 61

Configuring the I/O

4-25

For this example, the adapter I/O parameters are set to these values. Adapter Parameter No.

Setting

13 - [DPI I/O Cfg] xxxx xxxx xxx1 1111

25 - [M-S Input] xxxx xxxx xxx1 1111

26 - [M-S Output] xxxx xxxx xxx1 1111

2. Reset the adapter (see Resetting the Adapter on page 3-7) or power cycle the drive. For the drive speed reference and Datalink parameter values and the adapter setup parameter values, see Drive and Adapter Parameter Settings on page 5-24.

Use RSNetWorx for ControlNet Software to Configure the I/O and Save It to the Controller To establish an I/O configuration that can be used between the controller and drive over a ControlNet network, you must first create an I/O image for the PLC-5/40C controller’s built-in scanner. 1. Start RSNetWorx for ControlNet software. 2. In the RSNetWorx for ControlNet window, select File > New to display the New File screen. 3. Select ‘ControlNet Configuration’ as the network configuration type. 4. Click OK. 5. Select Network > Online to display the Browse for Network screen.

6. Expand the communication path from your computer to the PLC-5/40C controller.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 62

4-26

Configuring the I/O

The following screen shows our example navigating to devices that are on a ControlNet network. Depending on the communication link you are using, the navigation path may be different.

7. After selecting a valid path to the ControlNet network (for this example, ControlNet, ControlNet), click OK. As the selected ControlNet path is browsed, RSNetWorx for ControlNet software creates a graph view window that shows a graphical representation of the devices on the network.

If the icon for the drive (for this example, PowerFlex 70 EC) on the network appears as Unrecognized Device, you must download the EDS file for that PowerFlex drive from the Rockwell Automation website. a. Go to the website http://www.rockwellautomation.com/resources/ eds.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 63

Configuring the I/O

4-27 b. On the website search screen in the Network entry field, enter the type of network (for this example, ControlNet), which enables the use of the other search fields. c. In the Keyword entry field, enter the type of PowerFlex drive (for this example, PowerFlex 70EC), noting that this field is space sensitive. d. Click Search. Due to the large number of EDS files, this search may take seconds or up to several minutes. e. On the search results screen in the Details & Download Column, click the ‘Download’ hyperlink for the EDS file. f.

Click Save on the File Download screen to save the EDS file to an appropriate location on your computer.

g. Launch the EDS Hardware Installation Tool by clicking the Microsoft Windows Start button and selecting Programs > Rockwell Software > RSLinx Tools > EDS Hardware Installation Tool. Follow the screen prompts to add the EDS file for use with your project. h. Reboot the computer and repeat steps 1 through 7 at the beginning of this subsection. The Unrecognized Device icon in the RSNetWorx for ControlNet graph view window in step 7 should have been replaced by a drive icon (for this example, the icon for a PowerFlex 70 EC drive). 8. Select Network > Enable Edits or check the Edits Enabled box in the RSNetWorx for ControlNet project window. If the PLC-5/40C controller has a different I/O configuration than the configuration now being saved, the Online/Offline mismatch dialog box will appear.

a. When both Options choices are available, click ‘Use offline data (download)’. When this choice is dimmed (grayed out), you must select ‘Use online data (upload)’. b. Click OK. TIP: If a message box reports that the download cannot be completed because the controller is not in Program mode, click Change Mode to place the controller in Remote Run mode and continue the download. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 64

4-28

Configuring the I/O

9. In the RSNetWorx for ControlNet graph view window, right-click the PLC-5/40C icon and choose Scanlist Configuration to display the Scanlist Configuration screen.

10. Right-click the PowerFlex 70 EC drive row in the screen and choose Insert Connection… to display the Connection Properties screen.

a. In this screen, leave the Connection Name box at the default value shown. b. For the Requested Packet Interval box, choose a value that is suitable for your application, but is at least 5 ms. c. For the Input Size and Output Size boxes, use the pull-down menu to choose the number of words that are required for your I/O. The size will depend on the I/O that you enabled in the adapter using Parameter 13 - [DPI I/O Cfg]. For this example, an Input Size of ‘10’ and an Output Size of ‘10’ are selected. Depending on the size of the drive’s Reference/Feedback and the number of Datalinks used in your I/O configuration, Table 4.D, Table 4.E, or Table 4.F defines the number of 16-bit words that you need to enter for the Input Size and Output Size boxes.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 65

Configuring the I/O

4-29

Table 4.D Drives with 16-bit Reference/Feedback and 16-bit Datalinks These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (16-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

D

✔ ✔

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

2

…0 0001

…0 0001

…0 0001

4

4

…0 0011

…0 0011

…0 0011

6

6

…0 0111

…0 0111

…0 0111

8

8

…0 1111

…0 1111

…0 1111

10

10

…1 1111

…1 1111

…1 1111

Input

Output

2

Table 4.E Drives with 16-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (32-bit)

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

A

B

C

D

✔

• PowerFlex Digital DC drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

Input

Output

2

2

…0 0001

…0 0001

…0 0001

6

6

…0 0011

…0 0011

…0 0011

10

10

…0 0111

…0 0111

…0 0111

14

14

…0 1111

…0 1111

…0 1111

18

18

…1 1111

…1 1111

…1 1111

Table 4.F Drives with 32-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Logic Command/ Status

Ref/Fdbk (32-bit)

Datalinks (32-bit)

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

A

B

C

D

✔

• PowerFlex 753 drives • PowerFlex 755 drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

Input

Output

4

4

…0 0001

…0 0001

…0 0001

8

8

…0 0011

…0 0011

…0 0011

12

12

…0 0111

…0 0111

…0 0111

16

16

…0 1111

…0 1111

…0 1111

20

20

…1 1111

…1 1111

…1 1111

TIP: If necessary, the N9:0, N10:0, and N11:0 address defaults can be changed to meet processor address requirements or eliminate address conflicts. 11. Click OK.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 66

4-30

Configuring the I/O

An address row (in blue text) will be added below the PowerFlex 70 EC drive row. 12. Select File > Save to save the I/O configuration file to the PLC-5/40C controller. The Save Configuration dialog box appears.

TIP: If both Save Type choices are available, we recommend to click ‘Optimize and re-write schedule for all connections’. 13. Click OK to download the I/O configuration to the controller. A warning will appear about communication and I/O disruption on the network. 14. Click Yes. If this is the first time that you saved the project, the Save As dialog box appears. a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer.

SLC 500 Controller Example After the adapter is configured, the connected drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple ControlNet network (see Figure 4.6). In our example, we will configure a SLC 500 controller to communicate with a drive using Logic Command/Status, Reference/Feedback, and Datalinks over the network. Figure 4.6

Example SLC 500 Controller ControlNet Network

SLC 5/05 Controller with 1747-SCNR

Computer with ControlNet Connection

PowerFlex 70 Drive with 20-COMM-C Adapter

Channel A (optional redundancy)

Channel B

ControlNet Network

TIP: Information for PowerFlex 750-Series drives has been added to this manual where it is applicable. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P