PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 4, pages 47 to 56

Pages 47 to 56 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual

The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 20-COMM-C

Page 47

Configuring the I/O

4-11

Save the I/O Configuration to the Controller After adding the bridge and drive/adapter to the I/O configuration, you must download the configuration to the controller. You should also save the configuration to a file on your computer. 1. In the RSLogix 5000 window, select Communications > Download. The Download dialog box appears.

TIP: If a message box reports that RSLogix 5000 software is unable to go online, select Communications > Who Active to find your controller in the Who Active screen. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add or configure the ControlNet driver with RSLinx software. See Using RSLinx Classic Software on page 4-1 and RSLinx online help for details. 2. Click Download to download the configuration to the controller. When the download is successfully completed, RSLogix 5000 software goes into the Online mode and the I/O Not Responding box in the upper-left of the window should be flashing green. Also, a yellow warning symbol should be displayed on the I/O Configuration folder in the treeview and on the drive profile because the connections have not yet been scheduled using RSNetWorx for ControlNet software. If the controller was in Run Mode before clicking Download, RSLogix 5000 software prompts you to change the controller mode back to Remote Run. In this case, choose the appropriate mode for your application. If the controller was in Program Mode before clicking Download, this prompt will not appear. 3. Select File > Save. If this is the first time you saved the project, the Save As dialog box appears. a. Navigate to a folder b. Type a file name. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 48

4-12

Configuring the I/O c. Click Save to save the configuration to a file on your computer. To be sure that the present project configuration values are saved, RSLogix 5000 software prompts you to upload them. Click Yes to upload and save the values. Correlate the Drive with the Controller You must now correlate the drive settings to the RSLogix 5000 project I/O settings so that they match. This requires loading the project I/O settings into the drive. 1. In the treeview under I/O Configuration, right-click the drive profile (for this example, My_PowerFlex_70_EC_Drive) and choose Properties. 2. Click the Drive tab.

3. Click Connect to Drive to begin the correlation process. The Connect To Drive screen appears. 4. Browse the communication path to the drive and select the drive. 5. Click OK. After the drive configuration data has been verified, a pop-up dialog box appears, which synchronizes ports from the online drive to the project to be sure that correct Datalinks are assigned. 6. Click OK. If the Differences Found screen appears - which is typical, click Download. This will download the project settings from the controller to the drive and its connected adapter. If Upload is clicked, the drive and adapter settings are uploaded to the controller.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 49

Configuring the I/O

4-13

TIP: On subsequent connections to the drive (after initial download), click Upload. 7. When the Reset Comm Module screen appears, click Yes to reset the communication adapter so that the new I/O settings take effect.

After resetting the communication module, which may take up to a minute to complete, a Comm Module Reset Error popup message may appear. If it does, click OK to close this message and complete the adapter reset. Then click OK to close the Drive Correlation screen. 8. Use the procedure in the next subsection Use RSNetworx for ControlNet Software to Save the I/O to the Bridge to do the following: – Change the I/O Not Responding box in the upper-left of the RSLogix 5000 window from flashing green to steady green. – Remove the yellow warning symbols in the treeview under the I/O Configuration folder and drive profile. Use RSNetworx for ControlNet Software to Save the I/O to the Bridge After configuring the I/O in the controller and drive, you must now download and save these configurations to the bridge. This will also resolve the I/O Not Responding box and the yellow warning symbols in the RSLogix 5000 project. 1. Start RSNetWorx for ControlNet software. 2. In the RSNetWorx for ControlNet window, select File > New to display the New File screen. 3. Select ‘ControlNet Configuration’ as the network configuration type. 4. Click OK.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 50

4-14

Configuring the I/O

5. Select Network > Online to display the Browse for Network screen.

6. Expand the communication path from your computer to the ControlNet bridge. The following screen shows our example navigating to devices that are on a ControlNet network. Depending on the communication link you are using, the navigation path may be different.

7. After selecting a valid path to the ControlNet network (for this example, A, ControlNet), click OK. As the selected ControlNet path is browsed, RSNetWorx for ControlNet software creates a graph view window that shows a graphical representation of the devices on the network.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 51

Configuring the I/O

4-15

If the icon for the drive (for this example, PowerFlex 70 EC) on the network appears as Unrecognized Device, you must download the EDS file for that PowerFlex drive from the Rockwell Automation website. a. Go to the website http://www.rockwellautomation.com/resources/eds. b. On the website search screen in the Network entry field, enter the type of network (for this example, ControlNet), which enables the use of the other search fields. c. In the Keyword entry field, enter the type of PowerFlex drive (for this example, PowerFlex 70EC), noting that this field is space sensitive. d. Click Search. Due to the large number of EDS files, this search may take seconds or up to several minutes. e. On the search results screen in the Details & Download Column, click the ‘Download’ hyperlink for the EDS file. f.

Click Save on the File Download screen to save the EDS file to an appropriate location on your computer.

g. Launch the EDS Hardware Installation Tool by clicking the Microsoft Windows Start button and selecting Programs > Rockwell Software > RSLinx Tools > EDS Hardware Installation Tool. Follow the screen prompts to add the EDS file for use with your project. h. Reboot the computer and repeat steps 1 through 7 at the beginning of this subsection. The Unrecognized Device icon in the RSNetWorx for ControlNet graph view window in step 7 should have been replaced by a drive icon (for this example, the icon for a PowerFlex 70 EC drive). 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 52

4-16

Configuring the I/O

8. Select Network > Enable Edits or check the Edits Enabled box in the RSNetWorx for ControlNet project window. If the bridge has a different I/O configuration than the configuration now being saved, the Online/Offline mismatch dialog box will appear.

a. When both Options choices are available, click ‘Use offline data (download)’. When this choice is dimmed (grayed out), you must click ‘Use online data (upload)’. b. Click OK. TIP: If a message box reports that the download cannot be completed because the controller is not in Program mode, click Change Mode to place the controller in Remote Program mode and continue the download. 9. Select File > Save to save the I/O configuration file to the computer. If this is the first time you saved the project, the Save As dialog box appears. a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer. The Save Configuration dialog box appears.

TIP: When both Save Type choices are available, we recommend you click ‘Optimize and re-write schedule for all connections’. d. Click OK to download the I/O configuration to the bridge.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 53

Configuring the I/O

4-17

Using the RSLogix 5000 Classic Profile, Versions 13.00…15.00 When compared to using the RSLogix 5000 Generic Profile (all versions), the RSLogix 5000 Classic Profile provides these advantages: • Profiles for specific drives (Figure 4.3) that provide descriptive controller tags for basic control I/O words (Logic Command/Status and Reference/ Feedback). The controller tags for Datalinks, however, have non-descriptive UserDefinedData[n] names. • Improved I/O configuration - no I/O assembly configuration required. Basic control I/O is defined, but Datalinks still need to be configured/ mapped. • The Setup tab includes a DriveExecutive icon link to conveniently launch DriveExecutive software (when installed on computer) to match the adapter I/O configuration with the controller, and to assign the Datalink parameters in the drive. This reduces I/O mismatches. TIP: Because the RSLogix 5000 Classic Profile has been significantly improved upon by RSLogix 5000 Drive Add-on Profiles, version 16.00 or later, we recommend using RSLogix 5000 Drive Add-on Profiles to take advantage of their benefits (more intuitive, time saving, and less likely to make I/O configuration errors). Figure 4.3

Classic Profile Screens for Drives

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 54

4-18

Configuring the I/O

When Datalinks are used, you must enable the desired Datalinks and assign names to their non-descriptive controller tags. When a Datalink is enabled, you must set the following adapter I/O parameters: • Parameter 13 - [DPI I/O Cfg] turns on the enabled Datalink bit so the 20-COMM-C or 20-COMM-Q adapter will communicate that Datalink’s information with the drive. • Parameter 25 - [M-S Input] turns on the enabled Datalink bit so the 20-COMM-C or 20-COMM-Q adapter will input that Datalink’s information from the controller. • Parameter 26 - [M-S Output] turns on the enabled Datalink bit so the 20-COMM-C or 20-COMM-Q adapter will output that Datalink’s information to the controller. When using Datalinks, up to 8 drive [Data In xx] parameters (300…307) and/or up to 8 [Data Out xx] parameters (310…317) must be assigned to point to the appropriate drive parameters for your application. Important: To change the I/O Not Responding box in the upper-left of the RSLogix 5000 window from flashing green to steady green, and to remove the yellow warning symbols displayed in the treeview under the I/O Configuration folder and drive profile, follow the procedure in Use RSNetworx for ControlNet Software to Save the I/O to the Bridge on page 4-13.

Using the RSLogix 5000 Generic Profile, All Versions We recommend that you use the basic RSLogix 5000 Generic Profile for only the following reasons: • A specific drive profile in other versions of RSLogix 5000 software is unavailable. • Users are already familiar with a drive Generic Profile and do not want to convert an existing project to a Classic Profile, versions 13.00…15.00, or to a drive Add-on Profile (RSLogix 5000 software, version 16.00 or later.) • A project must maintain specific revision level control. • The controller cannot be taken offline. RSLogix 5000 software, version 16.00 or later, enables the drive Generic Profile to be added while the controller is online and in the Run mode.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 55

Configuring the I/O

4-19

Add the Drive/Adapter to the I/O Configuration To transmit data between the bridge and the drive, you must add the drive as a child device to the parent bridge. 1. In the treeview, right-click the bridge and select New Module… to display the Select Module screen.

In our example, we right-click on the 1756-CNBR/D bridge. 2. Expand the Communications group to display all of the available communication modules. 3. Select ‘CONTROLNET-MODULE’ from the list to configure the drive and its connected 20-COMM-C or 20-COMM-Q adapter. 4. Click OK. The drive’s New Module screen appears.

5. Edit the following information about the drive and adapter. Box

Setting

Name

A name to identify the drive and adapter.

Description

Optional – description of the drive/adapter.

Comm Format

Data - INT (This setting formats the data in 16-bit words.)

Node

The node address of the adapter.

Open Module Properties

When this box is checked, clicking OK opens additional module properties screens to further configure the drive/adapter. When unchecked, clicking OK closes the drive’s New Module screen. For this example, check this box.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 56

4-20

Configuring the I/O

6. Under Connection Parameters, edit the following information. Box

Assembly Instance

Size

Input

1 The value will vary based on your application (This value is required.) (setting of Parameters 13 - [DPI I/O Cfg] and 26 [M-S Output]) and the size (16-bit or 32-bit) of the Reference/Feedback and Datalinks in the drive. See Table 4.A, Table 4.B or Table 4.C.

Output

2 The value will vary based on your application (This value is required.) (setting of Parameters 13 - [DPI I/O Cfg] and 25 [M-S Input]) and the size (16-bit or 32-bit) of the Reference/Feedback and Datalinks in the drive. See Table 4.A, Table 4.B or Table 4.C.

Configuration 6 0 (This value is required.) (This value is required.)

Depending on the size of the drive’s Reference/Feedback and the number of Datalinks used in your I/O configuration, Table 4.A, Table 4.B, or Table 4.C defines the number of 16-bit words that you need to enter for the Input Size and Output Size boxes. Table 4.A Drives with 16-bit Reference/Feedback and 16-bit Datalinks These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (16-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

D

✔

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

Input

Output

4

2

…0 0001

…0 0001

…0 0001

6

4

…0 0011

…0 0011

…0 0011

8

6

…0 0111

…0 0111

…0 0111

10

8

…0 1111

…0 1111

…0 1111

12

10

…1 1111

…1 1111

…1 1111

Table 4.B Drives with 16-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (32-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

D

✔

• PowerFlex Digital DC drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111

Input

Output

4