PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 4, pages 67 to 74

Pages 67 to 74 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual

The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 20-COMM-C

Page 67

Configuring the I/O

4-31

Configuring Parameters for Network I/O Because the I/O for the drive is defined in the next subsection Use RSNetWorx for ControlNet Software to Configure the I/O and Save It to the 1747-SCNR Scanner on page 4-31, there is no need to configure any I/O inside the RSLogix 500 project, version 7.00 or later, until using the I/O as described in Chapter 5. However, to get the adapter to operate with the I/O created in Chapter 5, you need to configure the adapter to accept the I/O and drive to point to the appropriate Datalinks. 1. Set adapter parameters 13 - [DPI I/O Cfg], 25 - [M-S Input], and 26 [M-S Output] to values that meet your application requirements. For this example, the adapter I/O parameters are set to these values. Adapter Parameter No.

Setting

13 - [DPI I/O Cfg] xxxx xxxx xxx1 1111

25 - [M-S Input] xxxx xxxx xxx1 1111

26 - [M-S Output] xxxx xxxx xxx1 1111

2. Reset the adapter (see Resetting the Adapter on page 3-7) or power cycle the drive. For the drive speed reference and Datalink parameter values and the adapter setup parameter values, see Drive and Adapter Parameter Settings on page 5-40.

Use RSNetWorx for ControlNet Software to Configure the I/O and Save It to the 1747-SCNR Scanner To establish an I/O configuration that can be used between the controller and drive over a ControlNet network, you must first create an I/O image for the SLC 500 controller’s 1747-SCNR scanner. 1. Start RSNetWorx for ControlNet software. 2. In the RSNetWorx for ControlNet window, select File > New to display the New File screen. 3. Select ‘ControlNet Configuration’ as the network configuration type. 4. Click OK.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 68

4-32

Configuring the I/O

5. Select Network > Online to display the Browse for Network screen.

6. Expand the communication path from your computer to the 1747-SCNR scanner. The following screen shows our example navigating to devices that are on a ControlNet network. Depending on the communication link you are using, the navigation path may be different.

7. After selecting a valid path to the ControlNet network (for this example, ControlNet, ControlNet), click OK.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 69

Configuring the I/O

4-33

As the selected ControlNet path is browsed, RSNetWorx for ControlNet software creates a graph view window that shows a graphical representation of the devices on the network.

If the icon for the drive (for this example, PowerFlex 70 EC) on the network appears as Unrecognized Device, you must download the EDS file for that PowerFlex drive from the Rockwell Automation website. a. Go to the website http://www.rockwellautomation.com/resources/ eds. b. On the website search screen in the Network entry field, enter the type of network (for this example, ControlNet), which enables the use of the other search fields. c. In the Keyword entry field, enter the type of PowerFlex drive (for this example, PowerFlex 70EC), noting that this field is space sensitive. d. Click Search. Due to the large number of EDS files, this search may take seconds or up to several minutes. e. On the search results screen in the Details & Download Column, click the ‘Download’ hyperlink for the EDS file. f.

Click Save on the File Download screen to save the EDS file to an appropriate location on your computer.

g. Launch the EDS Hardware Installation Tool by clicking the Microsoft Windows Start button and selecting Programs > Rockwell Software > RSLinx Tools > EDS Hardware Installation Tool. Follow the screen prompts to add the EDS file for use with your project.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 70

4-34

Configuring the I/O h. Reboot the computer and repeat steps 1 through 7 at the beginning of this subsection. The Unrecognized Device icon in the RSNetWorx for ControlNet graph view window in step 7 should have been replaced by a drive icon (for this example, the icon for a PowerFlex 70 EC drive). 8. Select Network > Enable Edits or check the Edits Enabled box in the RSNetWorx for ControlNet project window. If the 1747-SCNR scanner has a different I/O configuration than the configuration now being saved, the Online/Offline mismatch dialog box will appear.

a. When both Options choices are available, click ‘Use offline data (download)’. When this choice is dimmed (grayed out), you must click ‘Use online data (upload)’. b. Click OK. TIP: If a message box reports that the download cannot be completed because the controller is not in Program mode, click Change Mode to place the controller in Remote Run mode and continue the download. 9. In the RSNetWorx for ControlNet graph view window, right-click the 1747-SCNR icon and choose Scanlist Configuration to display the Scanlist Configuration screen.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 71

Configuring the I/O

4-35

10. Right-click the PowerFlex 70 EC drive row in the screen and select Insert Connection… to display the Connection Properties screen.

a. In this screen, leave the Connection Name box at the default value shown. b. For the Requested Packet Interval box, choose a value that is suitable for your application, but is at least 5 ms. c. For the Input Size and Output Size boxes, use the pull-down menu to choose the number of words that are required for your I/O. The size will depend on the I/O that you enabled in the adapter using Parameter 13 - [DPI I/O Cfg]. For this example, an Input Size of ‘12’ and an Output Size of ‘10’ are selected. Depending on the size of the drive’s Reference/Feedback and the number of Datalinks used in your I/O configuration, Table 4.G, Table 4.H, or Table 4.I defines the number of 16-bit words that you need to enter for the Input Size and Output Size boxes. Table 4.G Drives with 16-bit Reference/Feedback and 16-bit Datalinks These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (16-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

D

✔

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

Input

Output

4

2

…0 0001

…0 0001

…0 0001

6

4

…0 0011

…0 0011

…0 0011

8

6

…0 0111

…0 0111

…0 0111

10

8

…0 1111

…0 1111

…0 1111

12

10

…1 1111

…1 1111

…1 1111

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 72

4-36

Configuring the I/O

Table 4.H Drives with 16-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control Logic Command/ Status

Ref/Fdbk (16-bit)

Datalinks (32-bit) A

B

C

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

Table 4.I

D

✔ ✔

• PowerFlex Digital DC drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111

Input

Output

4

Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Logic Command/ Status

Ref/Fdbk (32-bit)

Datalinks (32-bit)

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

✔

A

B

C

D

✔

• PowerFlex 753 drives • PowerFlex 755 drives

User Configured Settings Size in Words

Par. 13 Par. 25 [DPI I/O Cfg] [M-S Input]

Par. 26 [M-S Output]

Input

Output

6

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

11. Because N files are used in Using the I/O, Chapter 5 and memory files cannot be used for 32-bit REAL (floating point) data, the default Input Address M1:e.3 and Output Address M0:e.3 will need to be converted later using COP instructions in the ladder logic program. For now, leave these address fields at their defaults, and click OK. An address row (in blue text) will be added below the PowerFlex 70 EC drive row. 12. Select File > Save to save the I/O configuration file to the 1747-SCNR scanner. The Save Configuration dialog box appears.

TIP: When both Save Type choices are available, we recommend to click the ‘Optimize and re-write schedule for all connections’.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 73

Configuring the I/O

4-37

13. Click OK to download the I/O configuration to the scanner. A warning will appear about communication and I/O disruption on the network. 14. Click Yes. If this is the first time that you saved the project, the Save As dialog box appears. a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 74

4-38

Configuring the I/O

Notes: