For the Allen-Bradley 20-COMM-C

Page 75

Chapter 5

Using the I/O

This chapter provides information and examples that explain how to control, configure, and monitor a PowerFlex 7-Class drive using the configured I/O. Topic

Page

About I/O Messaging

5-1

Understanding the I/O Image

5-2

Using Logic Command/Status

5-8

Using Reference/Feedback

5-8

Using Datalinks

5-11

Example Ladder Logic Program Information

5-13

ControlLogix Controller Example

5-14

PLC-5 Controller Example

5-23

SLC 500 Controller Example

5-38

!

About I/O Messaging

ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example. There are many variables and requirements with any application. Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.

On CIP-based networks, including ControlNet, I/O connections are used to transfer the data which controls the PowerFlex drive and sets its Reference. I/O can also be used to transfer data to and from Datalinks in PowerFlex 7-Class drives. The adapter provides many options for configuring and using I/O, including the following: • Configuring the size of I/O by enabling or disabling the Logic Command/Reference and Datalinks • Setting a Master-Slave hierarchy Chapter 3, Configuring the Adapter, and Chapter 4, Configuring the I/O, discuss how to configure the adapter and controller on the network for these options. The defines the different options. This chapter discusses how to use I/O after you have configured the adapter and controller.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 76

5-2

Using the I/O

Understanding the I/O Image The terms ‘input’ and ‘output’ are defined from the controller’s point of view. Therefore, output I/O is data that is produced by the controller and consumed by the adapter. Input I/O is status data that is produced by the adapter and consumed as input by the controller. The I/O image will vary based on the following: • Size (either 16-bit or 32-bit) of the Reference/Feedback words and Datalink words used by the drive. To determine the size of the Reference/Feedback and Datalinks, view adapter Parameters 07 - [Ref/ Fdbk Size] and 08 - [Datalink Size]. For information to access parameters, see Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. • Configuration of I/O (Parameter 13 - [DPI I/O Cfg]). If all I/O is not enabled, the image is truncated. The image always uses consecutive words starting at word 0. • ControlLogix/CompactLogix Controllers only - The drive profile used in RSLogix 5000 software (drive Add-on Profile in version 16.00 or later, Classic Profile in versions 13.00…15.00, or Generic Profile in all versions).

ControlLogix Controller Image Because the drive Add-on Profile in RSLogix 5000 software, version 16.00 or later, and the Classic Profile, versions 13.00…15.00, provide descriptive controller tags, the I/O image (tag size and location) is automatically configured based on the drive being used. When using the Generic Profile (page 4-18) in RSLogix 5000 software, however, controller tags are not descriptive or defined. The ControlLogix controller I/O image changes depending on the size of the drive’s Reference/Feedback and Datalinks, and the number of Datalinks used. Table 5.A, Table 5.B, and Table 5.C show the I/O image when using various PowerFlex drives, and all Datalinks enabled.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 77

Using the I/O

5-3

Table 5.A ControlLogix Controller I/O Image for Drives with 16-bit Reference/ Feedback and 16-bit Datalinks – Using Generic Profile These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Word 0 1 2 3 4 5 6 7 8 9

Output I/O Logic Command Reference Datalink In A1 Datalink In A2 Datalink In B1 Datalink In B2 Datalink In C1 Datalink In C2 Datalink In D1 Datalink In D2

Word 0 1 2 3 4 5 6 7 8 9 10 11

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

Input I/O Pad Word Pad Word Logic Status Feedback Datalink Out A1 Datalink Out A2 Datalink Out B1 Datalink Out B2 Datalink Out C1 Datalink Out C2 Datalink Out D1 Datalink Out D2

Table 5.B ControlLogix Controller I/O Image for Drives with 16-bit Reference/ Feedback and 32-bit Datalinks – Using Generic Profile These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Output I/O Logic Command Reference Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

• PowerFlex Digital DC drives

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Input I/O Pad Word Pad Word Logic Status Feedback Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 78

5-4

Using the I/O

Table 5.C ControlLogix Controller I/O Image for Drives with 32-bit Reference/ Feedback and 32-bit Datalinks – Using Generic Profile These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Output I/O Logic Command Not Used Reference (LSW) Reference (MSW) Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

• PowerFlex 753 drives • PowerFlex 755 drives Input I/O Pad Word Pad Word Logic Status Not Used Feedback (LSW) Feedback (MSW) Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

PLC-5 Controller Image The I/O image for the PLC-5 controller changes depending on the size of the drive’s Reference/Feedback and Datalinks, and the number of Datalinks used. Table 5.D, Table 5.E, and Table 5.F show the I/O image when using various PowerFlex drives, and all Datalinks enabled.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 79

Using the I/O

5-5

Table 5.D PLC-5 Controller I/O Image for Drives with 16-bit Reference/Feedback and 16-bit Datalinks These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Word 0 1 2 3 4 5 6 7 8 9

Output I/O Logic Command Reference Datalink In A1 Datalink In A2 Datalink In B1 Datalink In B2 Datalink In C1 Datalink In C2 Datalink In D1 Datalink In D2

Word 0 1 2 3 4 5 6 7 8 9

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

Input I/O Logic Status Feedback Datalink Out A1 Datalink Out A2 Datalink Out B1 Datalink Out B2 Datalink Out C1 Datalink Out C2 Datalink Out D1 Datalink Out D2

Table 5.E PLC-5 Controller I/O Image for Drives with 16-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control

• PowerFlex Digital DC drives

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Output I/O Logic Command Reference Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

Input I/O Logic Status Feedback Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 80

5-6

Using the I/O

Table 5.F PLC-5 Controller I/O Image for Drives with 32-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Output I/O Logic Command Not Used Reference (LSW) Reference (MSW) Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

• PowerFlex 753 drives • PowerFlex 755 drives Input I/O Logic Status Not Used Feedback (LSW) Feedback (MSW) Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

SLC 500 Controller Image The I/O image for the SLC 500 controller changes depending on the size of the drive’s Reference/Feedback and Datalinks, and the number of Datalinks used. Table 5.G, Table 5.H, and Table 5.I show the I/O image when using various PowerFlex drives, and all Datalinks enabled.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 81

Using the I/O

5-7

Table 5.G SLC 500 Controller I/O Image for Drives with 16-bit Reference/Feedback and 16-bit Datalinks These products include the following: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 700 drives with standard control • PowerFlex 700H drives Word 0 1 2 3 4 5 6 7 8 9

Output I/O Logic Command Reference Datalink In A1 Datalink In A2 Datalink In B1 Datalink In B2 Datalink In C1 Datalink In C2 Datalink In D1 Datalink In D2

Word 0 1 2 3 4 5 6 7 8 9 10 11

• SMC Flex smart motor controllers • SMC-50 smart motor controllers

Input I/O Pad Word Pad Word Logic Status Feedback Datalink Out A1 Datalink Out A2 Datalink Out B1 Datalink Out B2 Datalink Out C1 Datalink Out C2 Datalink Out D1 Datalink Out D2

Table 5.H SLC 500 Controller I/O Image for Drives with 16-bit Reference/Feedback and 32-bit Datalinks These products include the following: • PowerFlex 700 drives with vector control • PowerFlex 700L drives with 700 control Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Output I/O Logic Command Reference Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

• PowerFlex Digital DC drives

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Input I/O Pad Word Pad Word Logic Status Feedback Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 82

5-8

Using the I/O

Table 5.I

SLC 500 Controller I/O Image for Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following: • PowerFlex 700S drives with Phase I or Phase II control • PowerFlex 700L drives with 700S control Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Using Logic Command/ Status

Output I/O Logic Command Not Used Reference (LSW) Reference (MSW) Datalink In A1 (LSW) Datalink In A1 (MSW) Datalink In A2 (LSW) Datalink In A2 (MSW) Datalink In B1 (LSW) Datalink In B1 (MSW) Datalink In B2 (LSW) Datalink In B2 (MSW) Datalink In C1 (LSW) Datalink In C1 (MSW) Datalink In C2 (LSW) Datalink In C2 (MSW) Datalink In D1 (LSW) Datalink In D1 (MSW) Datalink In D2 (LSW) Datalink In D2 (MSW)

Word 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

• PowerFlex 753 drives • PowerFlex 755 drives Input I/O Pad Word Pad Word Logic Status Not Used Feedback (LSW) Feedback (MSW) Datalink Out A1 (LSW) Datalink Out A1 (MSW) Datalink Out A2 (LSW) Datalink Out A2 (MSW) Datalink Out B1 (LSW) Datalink Out B1 (MSW) Datalink Out B2 (LSW) Datalink Out B2 (MSW) Datalink Out C1 (LSW) Datalink Out C1 (MSW) Datalink Out C2 (LSW) Datalink Out C2 (MSW) Datalink Out D1 (LSW) Datalink Out D1 (MSW) Datalink Out D2 (LSW) Datalink Out D2 (MSW)

The Logic Command is a 16-bit word of control data produced by the controller and consumed by the adapter. The Logic Status is a 16-bit word of status data produced by the adapter and consumed by the controller. PowerFlex 750-Series drives have a 32-bit Logic Command/Status - but when using a 20-COMM-C or 20-COMM-Q adapter only the first 16 bits can be used. This manual contains the bit definitions for most compatible products available at the time of publication in Appendix D, Logic Command/Status Words. For other products, see their documentation.

Using Reference/Feedback

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

The Reference is produced by the controller and consumed by the adapter. The Feedback is produced by the adapter and consumed by the controller. The size of the Reference/Feedback is determined by the drive and can be displayed with adapter Parameter 07 - [Ref/Fdbk Size]. Size

Valid Values

16-bit

-32768 to 32767

32-bit

-2147483648 to 2147483647

Page 83

Using the I/O

5-9

When the Reference and Feedback are enabled, and a ControlLogix controller with a drive Add-on Profile or Classic Profile is used, specific controller tags are automatically created, sized (16-bit or 32-bit), and placed in the I/O image.

PowerFlex 70/700/700H and PowerFlex 700L Drives with 700 Control The Reference/Feedback value is a scaled engineering value; it is not in Hertz or RPM. The Reference uses a ‘32767’ scale. The ‘32767’ endpoint of the scale is equal to the value of drive parameter 55 - [Maximum Freq], which has a default value of 130 Hz. For these drives, default scaling is 0…15123 which is equal to 0…60.0 Hz. This is based on the formula shown below. Reference/Feedback scaling is limited by drive parameter 82 - [Maximum Speed]. If the default value of 60 Hz. for parameter 82 - [Maximum Speed] is changed, the speed Reference/Feedback scaling also changes. To determine Reference/Feedback scaling, use the following formula: (Parameter 82 ÷ Parameter 55) * 32767 = Scaling Using drive parameter 82 and 55 default values, speed Reference/Feedback scaling is: (60 Hz ÷ 130 Hz) * 32767 = 15123 Therefore, 0…15123 = 0…60.0 Hz. If parameter 82 - [Maximum Speed] is changed to 90 Hz, then: (90 Hz ÷ 130 Hz) * 32767 = 22685 Therefore, 0…22685 = 0…90.0 Hz.

Par. 55 - [Maximum Freq]

A graphic representation of this Reference/Feedback scaling is shown below. 130 Hz 90 Hz 60 Hz aximum

- [M Par. 82

Speed]

0 Hz 0

15123

22685

32767

Scaling = (Parameter 82 ÷ Parameter 55) * 32767

For PowerFlex 70 drives with enhanced control, firmware 2.xxx or later, or PowerFlex 700 drives with vector control, firmware 3.xxx or later, drive parameter 298 - [DPI Ref Select] was added to simplify scaling for the speed Reference/Feedback. When drive parameter 298 - [DPI Ref Select] is set to its default ‘0’ (Max Freq), the speed Reference/Feedback scaling is as shown above. However, when parameter 298 - [DPI Ref Select] is set to ‘1’ (Max Speed), the speed Reference/Feedback scaling is equal to parameter 82 - [Max Speed]: Parameter 82 = Scaling Using the parameter 82 default value, speed Reference/Feedback scaling is: 0…32767 = 0…60.0 Hz. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P