PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 3

Pages 29 to 36 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual

The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 20-COMM-C

Page 29

Chapter 3

Configuring the Adapter

This chapter provides instructions and information for setting the parameters in the adapter. Topic

Page

Configuration Tools

3-1

Using the PowerFlex 7-Class HIM to Access Parameters

3-2

Setting the Node Address

3-3

Setting the I/O Configuration

3-3

Setting Master-Slave Hierarchy

3-4

Setting the Reference Adjustment

3-5

Setting a Fault Action

3-5

Resetting the Adapter

3-7

Viewing the Adapter Status Using Parameters

3-7

Updating the Adapter Firmware

3-8

For a list of parameters, see Appendix B, Adapter Parameters. For definitions of terms in this chapter, see the Glossary.

Configuration Tools

The adapter stores parameters and other information in its own nonvolatile storage (NVS) memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters. Tool

See

PowerFlex 7-Class HIM page 3-2

Connected Components Workbench software, version 1.02 or later http://www.ab.com/support/abdrives/webupdate/ software.html, or online help (installed with the software)

DriveExplorer software, version 2.01 or later http://www.ab.com/drives/driveexplorer, or online help (installed with the software)

DriveExecutive software, version 3.01 or later http://www.ab.com/drives/drivetools, or online help (installed with the software)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 30

3-2

Configuring the Adapter

Using the PowerFlex 7-Class If your drive has either an LED or LCD HIM (Human Interface Module), it can be used to access parameters in the adapter as shown below. We HIM to Access Parameters recommend that you read through the steps for your HIM before performing the sequence. For additional information, see the drive documentation or the PowerFlex 7-Class HIM Quick Reference, publication 20HIM-QR001.

Using an LED HIM Step

Example Screens

1. Press the ALT key and then the Device Sel (Sel) key to display the Device Screen. 2. Press the or key to scroll to the adapter. Letters represent files in the drive, and numbers represent ports. The adapter is usually connected to port 5. 3. Press the (Enter) key to enter your selection. A parameter database is constructed, and then the first parameter is displayed. 4. Edit the parameters using the same techniques that you use to edit drive parameters.

Using an LCD HIM Step

Example Screens

1. In the main menu, press the Device Select. 2. Press the or key to scroll to

(Enter) key to enter your selection.

3. Press the or key to scroll to the adapter (20-COMM-C or 20-COMM-Q). 4. Press the (Enter) key to select the adapter. A parameter database is constructed, and then the main menu for the adapter is displayed. 5. Edit the parameters using the same techniques that you use to edit drive parameters.

F-> Stopped Auto 0.00 Hz Main Menu: Diagnostics Parameter Device Select Port 5 Device 20-COMM-C Main Menu: Diagnostics Parameter Device Select

NOTE: All configuration procedures throughout this chapter use the PowerFlex 7-Class LCD HIM to access parameters in the adapter and show example LCD HIM screens. TIP: When using a PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, see its User Manual, publication 20-HIM-UM001.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 31

Configuring the Adapter

Setting the Node Address

3-3

If the adapter Node Address switches (Figure 2.1) are set to ‘00’ (Program) the value of Parameter 03 - [CN Addr Cfg] determines the node address. When in any other combination of positions, the Node Address switches determine the node address. 1. Set the value of Parameter 03 - [CN Addr Cfg] to a unique node address. Default = 02

Port 5 Device 20-COMM-C Parameter #: 03 CN Addr Cfg 2 0 <> 63

2. Reset the adapter (see Resetting the Adapter on page 3-7). When the node address is correctly configured and the adapter is connected to an operational network, the NET A status indicator should be steady green or flashing green.

Setting the I/O Configuration

The I/O configuration determines the data that is sent to and from the drive. Logic Command/Status, Reference/Feedback, and Datalinks may be enabled or disabled. (Datalinks allow you to read/write directly to parameters in the drive using implicit I/O.) A ‘1’ enables the I/O and a ‘0’ disables the I/O. 1. Set the bits in Parameter 13 - [DPI I/O Cfg]. Port 5 Device 20-COMM-C Parameter #: 13 DPI I/O Cfg xxxxxxxxxxx0 0 0 0 1 Cmd/Ref b00

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A

2

Datalink B

3

Datalink C

4

Datalink D

5…15

Not Used

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’. 2. If a controller is used to control the drive, set adapter Parameters 25 [M-S Input] and 26 - [M-S Output] for Master-Slave Hierarchy. For details, see Setting Master-Slave Hierarchy on page 3-4. 3. If Logic Command/Reference is enabled, configure the parameters in the drive to accept the Logic Command and Reference from the adapter. For example, set Parameter 90 - [Speed Ref A Sel] in a PowerFlex 70 or 700 drive to ‘22’ (DPI Port 5) so that the drive uses the Reference from the adapter. Also, verify that the mask parameters (for example, Parameter 276 - [Logic Mask]) in the drive are configured to receive the desired logic from the adapter. See the documentation for your drive for details. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 32

3-4

Configuring the Adapter

4. If you enabled one or more Datalinks, configure parameters in the drive to determine the source and destination of data in the Datalinks. When using Datalinks, up to 8 drive [Data In xx] parameters (300…307) and/or up to 8 [Data Out xx] parameters (310…317) must be assigned to point to the appropriate drive parameters for your application. See Chapter 4 for an example. 5. Reset the adapter (see Resetting the Adapter on page 3-7). The adapter is ready to receive I/O. You must now configure the adapter to receive I/O from the master. See Setting Master-Slave Hierarchy.

Setting Master-Slave Hierarchy

A hierarchy determines the type of device with which the adapter exchanges data. In a Master-Slave hierarchy, the adapter exchanges data with a master, such as a bridge or scanner (1756-CNB/CNBR, 1747-SCNR, and so forth). 1. Enable the desired I/O in Parameter 13 - [DPI I/O Cfg]. See Setting the I/O Configuration on page 3-3. 2. Set the bits in Parameter 25 - [M-S Input]. This parameter determines the data received from the master by the drive. A ‘1’ enables the I/O and a ‘0’ disables the I/O. Port 5 Device 20-COMM-C Parameter #: 25 M-S Input xxxxxxxxxxx0 0 0 0 1 Cmd/Ref b00

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A Input

2

Datalink B Input

3

Datalink C Input

4

Datalink D Input

5…15

Not Used

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’. 3. Set the bits in Parameter 26 - [M-S Output]. This parameter determines the data transmitted from the drive to the bridge or scanner. A ‘1’ enables the I/O and a ‘0’ disables the I/O. Port 5 Device 20-COMM-C Parameter #: 26 M-S Output xxxxxxxxxxx0 0 0 0 1 Status/Fdbk b00

Bit

Description

0

Status/Feedback (Default)

1

Datalink A Output

2

Datalink B Output

3

Datalink C Output

4

Datalink D Output

5…15

Not Used

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’. 4. Reset the adapter (see Resetting the Adapter on page 3-7).

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 33

Configuring the Adapter

3-5

The adapter is ready to receive I/O from the master (that is, scanner). You must now configure the scanner to recognize and transmit I/O to the adapter. See Chapter 4, Configuring the I/O.

Setting the Reference Adjustment

A Reference Adjustment is a percent scaling factor for the Reference from the network. It can be set between 0.00…200.00% to allow the drive’s Reference to either match the network Reference (equal to 100.00%), scale below the network Reference (less than 100.00%), or scale above the network Reference (more than 100.00%).

!

ATTENTION: To guard against equipment damage and/or personal injury, note that changes to adapter Parameter 27 - [Ref Adjust] take effect immediately. A drive receiving its Reference from the adapter will receive the newly scaled Reference, resulting in a change of speed.

If the adapter is receiving a Reference, set Parameter 27 - [Ref Adjust] to the desired scaling factor. Port 5 Device 20-COMM-C Parameter #: 27 Ref Adjust 100.00 % 0.00 <> 200.00

Default = 100.00%

The adjustment takes effect as soon as it is entered.

Setting a Fault Action

By default, when I/O communication is disrupted (for example, a cable is disconnected) or the controller is idle (in program mode or faulted), the drive responds by faulting if it is using I/O from the network. You can configure a different response to these faults: • Disrupted I/O communication by using Parameter 10 - [Comm Flt Action] • An idle controller by using Parameter 11 - [Idle Flt Action]

!

ATTENTION: Risk of injury or equipment damage exists. Parameters 10 - [Comm Flt Action] and 11 - [Idle Flt Action] let you determine the action of the adapter and connected drive if I/O communication is disrupted or the controller is idle. By default, these parameters fault the drive. You can set these parameters so that the drive continues to run, however, precautions should be taken to verify that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or faulted controller). 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 34

3-6

Configuring the Adapter

Changing the Fault Action Set the values of Parameters 10 - [Comm Flt Action] and 11 - [Idle Flt Action] to an action that meets your application requirements. Value

Action

Description

0

Fault

The drive is faulted and stopped. (Default)

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent ‘0’ values for data. This does not command a stop.

3

Hold Last

The drive continues in its present state.

4

Send Flt Cfg

The drive is sent the data that you set in the fault configuration parameters (Parameters 15 - [Flt Cfg Logic] through 24 - [Flt Cfg D2 In]).

Port 5 Device 20-COMM-C Parameter #: 10 Comm Flt Action 0 Fault

Port 5 Device 20-COMM-C Parameter #: 11 Idle Flt Action 0 Fault

Changes to these parameters take effect immediately. A reset is not required. If communication is disrupted and then is re-established, the drive will automatically receive commands over the network again.

Setting the Fault Configuration Parameters When setting Parameter 10 - [Comm Flt Action] or 11 - [Idle Flt Action] to ‘Send Flt Cfg’, the values in the following parameters are sent to the drive after an I/O communication fault and/or idle fault occurs. You must set these parameters to values required by your application. Parameter

Description

15 - [Flt Cfg Logic]

A 16-bit value sent to the drive for Logic Command.

16 - [Flt Cfg Ref]

A 32-bit value (0…4294967295) sent to the drive as a Reference or Datalink.

17 - [Flt Cfg x1 In] through 24 - [Flt Cfg x2 In]

Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most significant word of the value must be set to zero (0) or a fault will occur.

Changes to these parameters take effect immediately. A reset is not required.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 35

Configuring the Adapter

Resetting the Adapter

3-7

Changes to switch settings and some adapter parameters require that you reset the adapter before the new settings take effect. You can reset the adapter by power cycling the drive or by using Parameter 09 - [Reset Module].

!

ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.

Set Parameter 09 - [Reset Module] to ‘1’ (Reset Module). Port 5 Device 20-COMM-C Parameter #: 09 Reset Module 1 Reset Module

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

When you enter ‘1’ (Reset Module), the adapter will be immediately reset. When you enter ‘2’ (Set Defaults), the adapter will set all adapter parameters to their factory-default values. After performing a Set Defaults, enter ‘1’ (Reset Module) so that the new values take effect. The value of this parameter will be restored to ‘0’ (Ready) after the adapter is reset.

The following parameters provide information about the status of the adapter. You can view these parameters at any time. Parameter 04 - [CN Addr Act]

Description The node address used by the adapter. This will be one of the following values:

Bit Definition

Not Used

Not Used

Datalink D

Datalink C

Datalink B

Datalink A

Cmd/Ref

• The address set by the rotary switches. • The value of Parameter 03 - [CN Addr Cfg]. • An old address of the switches or parameter if they have been changed and the adapter has not been reset. 06 - [CN Rate Act] The data rate used by the adapter. 07 - [Ref/Fdbk Size] The size of the Reference/Feedback. It will either be 16 bits or 32 bits. It is set in the drive and the adapter automatically uses the correct size. 08 - [Datalink Size] The size of the Datalinks. It will either be 16 bits or 32 bits. It is set in the drive and the adapter automatically uses the correct size. 12 - [CN Active Cfg] Source from which the adapter node address is taken. This will be either ‘0’ (Switches) or ‘1’ (EEPROM) in which the address from Parameter 03 - [CN Addr Cfg] is stored. The source is determined by the settings of the adapter Node Address switches. 14 - [DPI I/O Act] The Reference/Feedback and Datalinks used by the adapter. This value is the same as Parameter 13 - [DPI I/O Cfg] unless the parameter was changed and the adapter was not reset. Not Used

Viewing the Adapter Status Using Parameters

Default Bit x 7 x 6 x 5

0 4

0 3

0 2

0 1

1 0

0 = I/O disabled 1 = I/O enabled

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 36

3-8

Configuring the Adapter

Updating the Adapter Firmware

The adapter firmware can be updated over the network or serially through a direct connection from a computer to the drive using a 1203-USB or 1203-SSS serial converter. When updating firmware over the network, you can use the Allen-Bradley ControlFLASH software tool, the built-in update capability of DriveExplorer Lite or Full software, or the built-in update capability of DriveExecutive software. When updating firmware through a direct serial connection from a computer to a drive, you can use the same Allen-Bradley software tools described above, or you can use HyperTerminal software set to the X-modem protocol. To obtain a firmware update for this adapter, go to http://www.ab.com/ support/abdrives/webupdate. This website contains all firmware update files and associated Release Notes that describe the following items: • Firmware update enhancements and anomalies • How to determine the existing firmware revision • How to update firmware using ControlFLASH, DriveExplorer, DriveExecutive, or HyperTerminal software

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P