For the Allen-Bradley 20-COMM-C
Page 211
Appendix C
ControlNet Objects
This appendix presents information about the ControlNet objects that can be accessed using Explicit Messages. For information on the format of Explicit Messages and example ladder logic programs, see Chapter 6, Using Explicit Messaging. Object
Class Code
Page
Hex.
Dec.
Identity Object
0x01
1
C-2
Assembly Object
0x04
4
Register Object
0x07
7
Parameter Object (1)
0x0F
Parameter Group Object (1)
0x10
Object
Class Code
Page
Hex.
Dec.
DPI Parameter Object
0x93
147
C-16
C-3
DPI Fault Object
0x97
151
C-22
C-4
DPI Alarm Object
0x98
152
C-24
15
C-5
DPI Diagnostic Object
0x99
153
C-26
16
C-7
DPI Time Object
0x9B
155
C-28
Host DPI Parameter Object (2)
0x9F
159
C-30
PCCC Object
0x67
103
C-8
DPI Device Object
0x92
146
C-13
(1) These objects are not supported when the adapter is used with a PowerFlex 750-Series drive. (2)
This object is supported only when the adapter is used with a PowerFlex 750-Series drive.
TIP: See the ControlNet specification for more information about ControlNet objects. Information about the ControlNet specification is available on the ODVA website (http://www.odva.org).
Supported Data Types Data Type BOOL BOOL[n] BYTE CONTAINER DINT DWORD INT LWORD REAL SHORT_STRING SINT STRING[n] STRUCT TCHAR UDINT UINT USINT WORD
Description 8-bit value -- low bit is true or false Array of n bits 8-bit unsigned integer 32-bit parameter value - sign extended if necessary 32-bit signed integer 32-bit unsigned integer 16-bit signed integer 64-bit unsigned integer 32-bit floating point 1-byte length indicator + that many characters 8-bit signed integer Array of n characters Structure name only - no size in addition to elements 8 or 16-bit character 32-bit unsigned integer 16-bit unsigned integer 8-bit unsigned integer 16-bit unsigned integer
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 212
C-2
ControlNet Objects
Identity Object
Class Code Hexadecimal Decimal 0x01 1
Services Service Code 0x01 0x05 0x0E
Implemented for: Class Instance Yes Yes Yes Yes Yes Yes
Service Name Get_Attributes_All Reset Get_Attribute_Single
Instances The number of instances depends on the number of components in the device connected to the adapter. This number of components can be read in Instance 0, Attribute 2. Instance 0 1 2…15
Description Class Host Peripherals on Ports 1…14
Class Attributes Attribute ID 2
Access Rule Name Get Max Instance
Data Type WORD
Description Total number of instances
Instance Attributes Attribute ID Access Rule Name 1 Get Vendor ID 2 Get Device Type
Data Type WORD WORD
3 4
WORD STRUCT of: BYTE BYTE WORD
DWORD SHORT_STRING
5
Get
Product Code Revision: Major Minor Status
6 7
Get Get
Serial Number Product Name
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Get Get
Description 1 = Allen-Bradley 120 (20-COMM-C) 129 (20-COMM-Q) Number identifying product name and rating Value varies Value varies Bit 0 = Owned Bit 2 = Configured Bit 10 = Recoverable fault Bit 11 = Unrecoverable fault Unique 32-bit number Product name and rating
Page 213
ControlNet Objects
Assembly Object
C-3
Class Code Hexadecimal Decimal 0x04 4
Services Implemented for: Service Code Class Instance 0x0E Yes Yes 0x10 Yes Yes
Service Name Get_Attribute_Single Set_Attribute_Single
Instances Instance 1 2
Description All I/O data being read from the DPI device (read-only) All I/O data being written to the DPI device (read/write)
Class Attributes Attribute ID 1 2 100
Access Rule Get Get Set
Name Revision Max Instance Control Timeout
Data Type WORD WORD WORD
Description 2 2 Control timeout in seconds
Instance Attributes Attribute ID 1 2
Access Rule Name Get Number of Members Get Member List
3 4
Conditional (1) Data Get Size
Data Type Description WORD 1 ARRAY of STRUCT: Size of member data WORD Size of member path WORD Member path Packed EPATH Array of Bits Data to be transferred WORD Size of assembly data in bits
(1) For instance 1, access rule for the data attribute is Get. For instance 2, access rule is Get/Set.
Important: Setting an assembly object attribute can be done only when the Control Timeout (class attribute 100) has been set to a non-zero value.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 214
C-4
ControlNet Objects
Register Object
Class Code Hexadecimal Decimal 0x07 7
Services Service Code Implemented for: Class Instance 0x0E Yes Yes 0x10 Yes Yes
Service Name Get_Attribute_Single Set_Attribute_Single
Instances Instance 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Description All I/O data being read from the DPI device (read-only) All I/O data written to the DPI device (read/write) Logic Status and Feedback data (read-only) Logic Command and Reference data (read/write) Datalink A (input data from device to scanner) (read only) Datalink A (output data from scanner to device) (read/write) Datalink B (input data from device to scanner) (read only) Datalink B (output data from scanner to device) (read/write) Datalink C (input data from device to scanner) (read only) Datalink C (output data from scanner to device) (read/write) Datalink D (input data from device to scanner) (read only) Datalink D (output data from scanner to device) (read/write) Logic Status and Feedback Data (read-only) Mask (1) (read/write) Logic Status (read-only) Logic Command (read/write) Feedback (read-only) Reference (read/write)
(1) The mask command word is set to the value of the first word of the data where there are ones in the second word of the data. Command = (word 1 and not word 2) or (word 1 and word 2). This only controls specified bits in the Logic Command data to the DPI product and does not change the Reference value.
Class Attributes Attribute ID 100
Access Rule Name Set Control Timeout
Data Type Description WORD Control timeout in seconds
Instance Attributes Attribute ID Access Rule Name 1 Get Bad Flag
Data Type BOOL
2
Get
BOOL
3 4
Get Size Conditional (1) Data
(1)
Direction
WORD ARRAY of BITS
Description If set to 1, then attribute 4 may contain invalid data. 0 = good 1 = bad Direction of data transfer 0 = Producer Register (drive to network) 1 = Consumer Register (network to drive) Size of register data in bits Data to be transferred
For this attribute, the Access Rule is Get if Direction = 0. The Access Rule is Set if Direction = 1.
Important: Setting a Register object attribute can only be done when the Control Timeout (class attribute 100) has been set to a non-zero value.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 215
ControlNet Objects
Parameter Object
C-5
Class Code Hexadecimal Decimal 0x0F 15
Important: This object is not supported when the adapter is used with a PowerFlex 750-Series drive.
Services Service Code Implemented for: Class Instance 0x01 Yes Yes 0x05 Yes No 0x0E Yes Yes 0x10 No Yes 0x4B No Yes
Service Name Get_Attributes_All Reset Get_Attribute_Single Set_Attribute_Single Get_Enum_String
Instances The number of instances depends on the number of parameters in the DPI drive. The adapter parameters are appended to the list of drive parameters. The total number of parameters can be read in Instance 0, Attribute 2.
Last Drive Parameter n Attributes (1) Adapter Parameter 1 Attributes … n n+1 …
…
Description Class Attributes Drive Parameter 1 Attributes
…
Instance 0 1 n+m
Last Adapter Parameter m Attributes (2)
(1) n represents the number of parameters in the drive. (2)
m represents the number of parameters in the adapter.
Class Attributes Attribute ID Access Rule 1 Get 2 Get 8 Get
Name Revision Max Instance Parameter Class Descriptor
Data Type WORD WORD WORD
9 10
Configuration Assembly Instance Native Language
WORD BYTE
Get Set
Description 1 Number of parameters 0 = False, 1 = True Bit 0 = Supports parameter instances Bit 1 = Supports full attributes Bit 2 = Must do NVS save command Bit 3 = Parameters are stored in NVS 0 0 = English 1 = French 2 = Spanish 3 = Italian 4 = German 5 = Japanese 6 = Portuguese 7 = Mandarin Chinese 8 = Russian 9 = Dutch
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 216
C-6
ControlNet Objects
Instance Attributes Attribute ID Access Rule Name (1) 1 Parameter Value 2 Get Link Path Size
Data Type
Description
(2)
(3)
BYTE
0 = No link specified n = The size of Attribute 3 in bytes (4)
3 4
Get Get
Link Path Descriptor
WORD
5
Get
Data Type
BYTE
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get
Data Size Parameter Name String Units String Help String Minimum Value Maximum Value Default Value Scaling Multiplier Scaling Divisor Scaling Base Scaling Offset Multiplier Link Divisor Link Base Link Offset Link Decimal Precision
BYTE SHORT_STRING SHORT_STRING SHORT_STRING
Null string
(2)
(3)
(2)
(3)
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
(3) (3)
(3)
WORD WORD WORD WORD WORD WORD WORD WORD BYTE
(3)
Specified in descriptor, data type, and data size. Value varies based on parameter instance. (4) See the ControlNet specification for a description of the link path. (3)
(3)
(2)
(1) Access rule is defined in Bit 4 of instance attribute 4 (0 = Get/Set, 1 = Get). (2)
0 = False, 1 = True Bit 1 = Supports ENUMs Bit 2 = Supports scaling Bit 3 = Supports scaling links Bit 4 = Read only Bit 5 = Monitor Bit 6 = Extended precision scaling 1 = WORD (16-bit) 2 = UINT (16-bit) 3 = INT (16-bit) 5 = SINT 6 = DINT 8 = USINT 9 = UDINT 11 = REAL 23 = SHORT_STRING 24 = BYTE 25 = DWORD
(3) (3) (3) (3) (3) (3) (3) (3)
Page 217
ControlNet Objects
Parameter Group Object
C-7
Class Code Hexadecimal Decimal 0x10 16
Important: This object is not supported when the adapter is used with a PowerFlex 750-Series drive.
Services Service Code Implemented for: Class Instance 0x01 Yes Yes 0x0E Yes Yes 0x10 Yes No
Service Name Get_Attributes_All Get_Attribute_Single Set_Attribute_Single
Instances The number of instances depends on the number of groups in the device. A group of adapter parameters is appended to the list of groups in the device. The total number of groups can be read in Instance 0, Attribute 2.
…
Description Class Attributes Drive Group 1 Attributes
…
Number 0 1 n n+1
Last Drive Group Attributes Adapter Group Attributes
Class Attributes Attribute ID 1 2 8
Access Rule Get Get Set
Name Parameter Group Version Max Instance Native Language
Data Type WORD WORD BYTE
Description 1 Total number of groups 0 = English 1 = French 2 = Spanish 3 = Italian 4 = German 5 = Japanese 6 = Portuguese 7 = Mandarin Chinese 8 = Russian 9 = Dutch
Instance Attributes Access Rule Get Get Get Get Get
Name Group Name String Number of Members in Group 1st Parameter Number in Group 2nd Parameter Number in Group …
Attribute ID 1 2 3 4 n
Data Type SHORT_STRING WORD WORD WORD WORD
Description Group name Number of parameters in group (1) (1) (1)
(1) Value varies based on group instance.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 218
C-8
ControlNet Objects
PCCC Object
Class Code Hexadecimal Decimal 0x67 103
Services Service Code Implemented for: Class Instance 0x4B No Yes 0x4C No Yes
Service Name Execute_PCCC Execute_DH+
Instances Not supported.
Class Attributes Not supported.
Instance Attributes Not supported.
Message Structure for Execute_PCCC Request Name Length Vendor Serial Number Other CMD STS TNSW FNC PCCC_ params
Data Type USINT UINT UDINT
Description Length of requestor ID Vendor number of requestor ASA serial number of requestor
Product Specific USINT USINT UINT USINT ARRAY of USINT
Identifier of user, task, etc. on the requestor Command byte 0 Transport word Function code; not used for all CMDs. CMD/FNC specific parameters
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Response Name Data Type Length USINT Vendor UINT Serial UDINT Number Other Product Specific CMD USINT STS USINT TNSW UINT EXT_STS USINT PCCC_ ARRAY of results USINT
Description Length of requestor ID Vendor number of requestor ASA serial number of requestor Identifier of user, task, etc. on the requestor Command byte Status byte Transport word. Same value as the request. Extended status; not used for all CMDs. CMD/FNC specific result data
Page 219
ControlNet Objects
C-9
Message Structure for Execute_DH+ Request Name DLink DSta DUser SLink SSta SUser CMD STS TNSW FNC PCCC_ params
Data Type UINT USINT USINT UINT USINT USINT USINT USINT UINT USINT ARRAY of USINT
Description Destination Link ID Destination Station number Destination “User” number Source Link ID Source Station number Source User number Command byte 0 Transport word Function code; not used for all CMDs CMD/FNC specific parameters
Response Name DLink DSta DUser SLink SSta SUser CMD STS TNSW EXT_STS PCCC_ results
Data Type UINT USINT USINT UINT USINT USINT USINT USINT UINT USINT ARRAY of USINT
Description Destination Link ID Destination Station number Destination “User” number Source Link ID Source Station number Source User number Command byte Status byte Transport word. Same value as the request. Extended status; not used for all CMDs CMD/FNC specific result data
The adapter supports the following PCCC command types: CMD 0x06 0F 0F 0F 0F 0F 0F 0F 0F 0F
FNC 0x03 67 68 95 A2 AA A1 A9 00 01
Description Identify host and some status PLC-5 typed write PLC-5 typed read Encapsulate other protocol SLC 500 protected typed read with 3 address fields SLC 500 protected typed write with 3 address fields SLC 500 protected typed read with 2 address fields SLC 500 protected typed write with 2 address fields Word range read Word range write
For more information regarding PCCC commands, see DF1 Protocol and Command Set Manual, publication 1770-6.5.16.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P