For the Allen-Bradley 20-COMM-C

Page 205

Appendix A

Specifications

This appendix presents the specifications for the adapter.

Communications

Electrical

Mechanical

Topic

Page

Communications

A-1

Electrical

A-1

Mechanical

A-1

Environmental

A-2

Regulatory Compliance

A-2

Network Protocol Data Rate Media: 20-COMM-C 20-COMM-Q

ControlNet 5 Mbps (fixed) Coax with BNC connector Fiber with V-pin type connector

Connection Limits

20 simultaneous CIP messaging connections Unlimited input-only I/O connections One of the following connection types: • 1 exclusive-owner I/O connection • Up to 3 redundant-owner I/O connections • 1 listen-only I/O connection

Requested Packet Interval (RPI)

5 ms minimum

Packet Rate

Up to 400 total I/O packets per second (200 in and 200 out)

Drive Protocol Data Rates

DPI 125 kbps or 500 kbps

Consumption Drive Network

275 mA at 5 V DC supplied by the host (drive or DPI External Comms Kit) None

Dimensions Height Length Width

16 mm (0.62 inches) 103 mm (4.00 inches) 80 mm (3.12 inches)

Weight

85 g (3 oz.)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 206

A-2

Specifications

Environmental

Regulatory Compliance

Temperature Operating Storage

-10…50 °C (14…122 °F) -40…85 °C (-40…185 °F)

Relative Humidity

5…95% non-condensing

Atmosphere

Important: The adapter must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the adapter is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.

Certification

Specification

UL

UL508C cUL

CAN / CSA C22.2 No. 14-M91

CE

EN50178 and EN61800-3

CTick

EN61800-3

NOTE: This is a product of category C3 according to IEC 61800-3. It is not intended for operation in a domestic environment.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 207

Appendix B

Adapter Parameters

This appendix provides information about the adapter parameters. For configuration tools to monitor or change parameter values of the drive, adapter, and other connected peripherals, see Configuration Tools on page 3-1.

Parameter List

Parameter No.

Name and Description

Details

01

[DPI Port] Displays the port to which the adapter is connected. This will usually be port 5.

Minimum: Maximum: Type:

0 7 Read Only

[DPI Data Rate]

Values:

Displays the data rate used by the drive. This data rate is set in the drive and the adapter detects it.

Type:

0 = 125 kbps 1 = 500 kbps Read Only

02

03

[CN Addr Cfg] Sets the ControlNet node address used by the adapter when the Node Address switches are set to ‘00’. (Updates Parameter 04 - [CN Addr Act] after reset).

04

[CN Addr Act] Displays the actual ControlNet node address used by the adapter.

05

[CN Rate Cfg] Sets the network data rate (megabits per second) at which the adapter communicates. (Updates Parameter 06 - [CN Rate Act] after a reset.)

06

08

Minimum: Maximum: Type:

1 99 Read Only

Default: 0 = 5 Mbps Values: 0 = 5 Mbps Type: Read/Write Reset Required: Yes Values: Type:

0 = 5 Mbps Read Only

[Ref/Fdbk Size]

Values:

Displays the size of the Reference/Feedback. The drive determines the size of the Reference/ Feedback.

Type:

0 = 16-bit 1 = 32-bit Read Only

[Datalink Size]

Values:

Displays the size of each Datalink word. The drive determines the size of Datalinks.

Type:

[CN Rate Act] Displays the actual network data rate (megabits per second) used by the adapter.

07

Default: 2 Minimum: 1 Maximum: 99 Type: Read/Write Reset Required: Yes

0 = 16-bit 1 = 32-bit Read Only

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 208

B-2

Adapter Parameters

Parameter No.

Name and Description

Details

09

[Reset Module]

Default: Values:

No action if set to ‘0’ (Ready). Resets the adapter if set to ‘1’ (Reset Module). Restores the adapter to its factory default settings if set to ‘2’ (Set Defaults). This parameter is a command. It will be reset to ‘0’ (Ready) after the command has been performed.

! 10

ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting I/O that controls the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting a connected adapter.

[Comm Flt Action] Sets the action that the adapter and drive will take if the adapter detects that I/O communication has been disrupted. This setting is effective only if I/O that controls the drive is transmitted through the adapter. When communication is re-established, the drive will automatically receive commands over the network again.

!

11

Sets the action that the adapter and drive will take if the adapter detects that the controller is in program mode or faulted. This setting is effective only if I/O that controls the drive is transmitted through the adapter. When the controller is put back in Run mode, the drive will automatically receive commands over the network again.

12

0 = Fault 0 = Fault 1 = Stop 2 = Zero Data 3 = Hold Last 4 = Send Flt Cfg Type: Read/Write Reset Required: No

Default: Values:

0 = Fault 0 = Fault 1 = Stop 2 = Zero Data 3 = Hold Last 4 = Send Flt Cfg Type: Read/Write Reset Required: No

ATTENTION: Risk of injury or equipment damage exists. Parameter 11 - [Idle Flt Action] lets you determine the action of the adapter and connected drive when the controller is idle. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run, however, precautions should be taken to verify that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a faulted controller).

[CN Active Cfg] Displays the source from which the adapter node address is taken. This will either be ‘0’ (Switches) or ‘1’ (EEPROM) in which the address from Parameter 03 - [CN Addr Cfg] is stored. The source is determined by the settings of the adapter Node Address switches.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Default: Values:

ATTENTION: Risk of injury or equipment damage exists. Parameter 10 [Comm Flt Action] lets you determine the action of the adapter and connected drive if I/O communication is disrupted. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run, however, precautions should be taken to verify that the setting of this parameter does not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).

[Idle Flt Action]

!

0 = Ready 0 = Ready 1 = Reset Module 2 = Set Defaults Type: Read/Write Reset Required: No

Values: Type:

0 = Switches 1 = EEPROM Read Only

Page 209

Adapter Parameters

B-3

Parameter No.

Name and Description

Details

13

[DPI I/O Cfg] xxx0 0001 0 = I/O Disabled 1 = I/O Enabled Type: Read/Write Reset Required: Yes

15

[Flt Cfg Logic] Sets the Logic Command data that is sent to the drive if any of the following is true: • Parameter 10 - [Comm Flt Action] is set to ‘4’ (Send Flt Cfg) and I/O communication is disrupted.

Not Used

Not Used

Not Used

Datalink D

Datalink C

Datalink B

Datalink A

Cmd/Ref x 7 x 6 x 5

0 4

0 3

0 2

0 1

1 0

Bit Values:

0 = I/O Disabled 1 = I/O Enabled Read Only

Bit Definition

Datalink D

Datalink C

Datalink B

Datalink A

Cmd/Ref

Type:

Not Used

Displays the I/O that the adapter is actively transmitting. The value of this parameter will usually be equal to the value of Parameter 13 [DPI I/O Cfg].

Default Bit

Not Used

[DPI I/O Act]

Bit Definition

Not Used

14

Default: Sets the I/O that is transferred through the adapter. Bit Values:

Default Bit x 7 x 6 x 5

0 4

0 3

0 2

0 1

1 0

Default: 0000 0000 0000 0000 Minimum: 0000 0000 0000 0000 Maximum: 1111 1111 1111 1111 Type: Read/Write Reset Required: No

• Parameter 11 - [Idle Flt Action] is set to ‘4’ (Send Flt Cfg) and the controller is idle. The bit definitions will depend on the product to which the adapter is connected. See Appendix D or the documentation for the drive being used. 16

[Flt Cfg Ref] Sets the Reference data that is sent to the drive if any of the following is true: • Parameter 10 - [Comm Flt Action] is set to ‘4’ (Send Flt Cfg) and I/O communication is disrupted. • Parameter 11 - [Idle Flt Action] is set to ‘4’ (Send Flt Cfg) and the controller is idle.

17 18 19 20 21 22 23 24

[Flt Cfg A1 In] [Flt Cfg A2 In] [Flt Cfg B1 In] [Flt Cfg B2 In] [Flt Cfg C1 In] [Flt Cfg C2 In] [Flt Cfg D1 In] [Flt Cfg D2 In] Sets the data that is sent to the Datalink in the drive if any of the following is true: • Parameter 10 - [Comm Flt Action] is set to ‘4’ (Send Flt Cfg) and I/O communication is disrupted. • Parameter 11 - [Idle Flt Action] is set to ‘4’ (Send Flt Cfg) and the controller is idle.

Default: 0 Minimum: 0 Maximum: 4294967295 Type: Read/Write Reset Required: No Important: If the drive uses a 16-bit Reference, the most significant word of this value must be set to zero (0) or a fault will occur. Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Default: 0 Minimum: 0 Maximum: 4294967295 Type: Read/Write Reset Required: No Important: If the drive uses 16-bit Datalinks, the most significant word of this value must be set to zero (0) or a fault will occur.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 210

B-4

Adapter Parameters

Parameter No.

Name and Description

Details

25

[M-S Input]

Default: Bit Values:

Not Used

Not Used

Not Used

Datalink D Input

Datalink C Input

Datalink B Input

Datalink A Input

Cmd/Ref x 6 x 5

0 4

0 3

0 2

0 1

1 0

27

[Ref Adjust] Sets the percent scale factor for the Reference received from the network.

!

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Cmd/Ref

Default Bit

Datalink A Output

Bit Definition

Datalink B Output xxx0 0001 0 = I/O Disabled 1 = I/O Enabled Type: Read/Write Reset Required: Yes Datalink C Output

Default: Bit Values:

Datalink D Output

Sets the Master-Slave output data. This data is produced by the adapter and consumed by the Master device (for example, scanner).

x 7

Not Used

[M-S Output]

Default Bit

Not Used

26

Bit Definition

Not Used

Sets the Master-Slave input data. This data is produced by the scanner and consumed by the adapter.

xxx0 0001 0 = I/O Disabled 1 = I/O Enabled Type: Read/Write Reset Required: Yes x 7 x 6 x 5

0 4

0 3

0 2

0 1

1 0

Default: 100.00% Minimum: 0.00% Maximum: 200.00% Type: Read/Write Reset Required: No

ATTENTION: To guard against equipment damage and/or personal injury, note that changes to Parameter 27 - [Ref Adjust] take effect immediately. A drive receiving its Reference from the adapter will receive the newly scaled Reference, resulting in a change of speed.