PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Appendix D
Pages 247 to 254 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual
The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 20-COMM-C
Page 247
Appendix D
Logic Command/Status Words This appendix presents the definitions of the Logic Command and Logic Status words that are used for some products that can be connected to the adapter. If the Logic Command/Logic Status for the product that you are using is not listed, refer to your product’s documentation.
PowerFlex 70/700/700H, and Logic Command Word 700L (with 700 Control) Drives Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x (1)
x x x x x
0 x
Command Stop (1) Start (1)(2) Jog Clear Faults Direction
Local Control MOP Increment Accel Rate
Decel Rate
Reference Select (3)
MOP Decrement
Description 0 = Not Stop 1 = Stop 0 = Not Start 1 = Start 0 = Not Jog (Par. 100) 1 = Jog 0 = Not Clear Faults 1 = Clear Faults 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control 0 = No Local Control 1 = Local Control 0 = Not Increment 1 = Increment 00 = No Command 01 = Accel Rate 1 Command (Par. 140) 10 = Accel Rate 2 Command (Par. 141) 11 = Hold Accel Rate 00 = No Command 01 = Decel Rate 1 Command (Par. 142) 10 = Decel Rate 2 Command (Par. 143) 11 = Hold Decel Rate 000 = No Command 001 = Ref A Select (Par. 90) 010 = Ref B Select (Par. 93) 011 = Preset 3 (Par. 103) 100 = Preset 4 (Par. 104) 101 = Preset 5 (Par. 105) 110 = Preset 6 (Par. 106) 111 = Preset 7 (Par. 107) 0 = Not Decrement 1 = Decrement
A ‘0 = Not Stop’ condition (logic 0) must first be present before a ‘1 = Start’ condition will start the drive. The Start command acts as a momentary Start command. A ‘1’ will start the drive, but returning to ‘0’ will not stop the drive.
(2) This Start will not function if a digital input (parameters 361…366) is programmed for 2-Wire Control (option 7, 8, or 9). (3)
This Reference Select will not function if a digital input (parameters 361…366) is programmed for ‘Speed Sel 1, 2, or 3’ (option 15, 16, or 17). Note that Reference Select is ‘Exclusive Ownership’ – see drive User Manual for more information.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 248
D-2
Logic Command/Status Words
Logic Status Word Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x
(1)
x x x x x
See ‘Owners’ in drive User Manual for further information.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
0 x
Status Ready Active Command Direction Actual Direction Accel Decel Alarm Fault At Speed Local Control (1)
Reference
Description 0 = Not Ready (Par. 214) 1 = Ready 0 = Not Active (Running) 1 = Active 0 = Reverse 1 = Forward 0 = Reverse 1 = Forward 0 = Not Accelerating 1 = Accelerating 0 = Not Decelerating 1 = Decelerating 0 = No Alarm (Par. 211 and 212) 1 = Alarm 0 = No Fault (Par. 243) 1 = Fault 0 = Not At Reference 1 = At Reference 000 = Port 0 (TB) 001 = Port 1 010 = Port 2 011 = Port 3 100 = Port 4 101 = Port 5 110 = Port 6 111 = No Local 0000 = Ref A Auto (Par. 90) 0001 = Ref B Auto (Par. 93) 0010 = Preset 2 Auto 0011 = Preset 3 Auto 0100 = Preset 4 Auto 0101 = Preset 5 Auto 0110 = Preset 6 Auto 0111 = Preset 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = DPI 6 Manual 1111 = Jog Ref
Page 249
Logic Command/Status Words
PowerFlex 700S (Phase II Control) and 700L (with 700S Control) Drives
D-3
Logic Command Word
Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x x x x x x
0 x
Command Normal Stop Start (1) Jog 1 Clear Fault (2) Unipolar Direction
Description 0 = Not Normal Stop 1 = Normal Stop 0 = Not Start 1 = Start 0 = Not Jog using [Jog Speed 1] (Par. 29) 1 = Jog using [Jog Speed 1] (Par. 29) 0 = Not Clear Fault 1 = Clear Fault 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control
Reserved Jog 2
0 = Not Jog using [Jog Speed 2] (Par. 39) 1 = Jog using [Jog Speed 2] (Par. 39) Current Limit Stop 0 = Not Current Limit Stop 1 = Current Limit Stop Coast Stop 0 = Not Coast to Stop 1 = Coast to Stop Reserved Reserved Spd Ref Sel0 Bits Spd Ref Sel1 14 13 12 Spd Ref Sel2 0 0 0 = Spd Ref A (Par. 27) 0
0
1 = Spd Ref B (Par. 28)
0
1
0 = Preset 2 (Par. 15)
0
1
1 = Preset 3 (Par. 16)
1
0
0 = Preset 4 (Par. 17)
1
0
1 = Preset 5 (Par. 18)
1
1
0 = Preset 6 (Par. 19)
1
1
1 = Preset 7 (Par. 20)
Reserved
(1)
A Not Stop condition (logic bit 0 = 0, logic bit 8 = 0, and logic bit 9 = 0) must first be present before a 1 = Start condition will start the drive.
(2)
To perform this command, the value must switch from ‘0’ to ‘1’.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 250
D-4
Logic Command/Status Words
Logic Status Word Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x x x x x x
0 x
Status Active Running Command Direction Actual Direction Accel Decel Jogging Fault Alarm Flash Mode Run Ready At Limit (1) Tach Loss Sw At Zero Spd At Setpt Spd Enable
Description 0 = Not Active 1 = Active 0 = Not Running 1 = Running 0 = Reverse 1 = Forward 0 = Reverse 1 = Forward 0 = Not Accelerating 1 = Accelerating 0 = Not Decelerating 1 = Decelerating 0 = Not Jogging 1 = Jogging 0 = No Fault (Par. 323, 324, 325) 1 = Fault 0 = No Alarm (Par. 326, 327, 328) 1 = Alarm 0 = Not in Flash Mode 1 = In Flash Mode 0 = Not Ready to Run (Par. 156) 1 = Ready to Run 0 = Not At Limit (Par. 304) 1 = At Limit 0 = Not Tach Loss Sw 1 = Tach Loss Sw 0 = Not At Zero Speed 1 = At Zero Speed 0 = Not At Setpoint Speed 1= At Setpoint Speed 0 = Not Enabled 1 = Enabled
(1) See Parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 251
Logic Command/Status Words
D-5
PowerFlex 750-Series Drives Important: When using a 20-COMM-C or 20-COMM-Q adapter with a PowerFlex 750-Series drive, the upper word (bits 16…31) of the Logic Command and Logic Status words are not accessible and cannot be used. Only when using a PowerFlex 750-Series drive with a 20-750 communication Option Module, or the PowerFlex 755 drive’s embedded EtherNet/IP adapter, is the upper word accessible and used.
Logic Command Word Logic Bits 31…15 14 13 12 11 10 9
8
7
6
5
4
3
2 x x x x x x x x x x x x x x
1
0 Command x Normal Stop x
Start (1) Jog 1 (2) Clear Fault (3) Unipolar Direction
Manual Reserved Accel Time
Decel Time
Ref Select 1 Ref Select 2 Ref Select 3
Description 0 = Not Normal Stop 1 = Normal Stop 0 = Not Start 1 = Start 0 = Not Jog 1 (Par. 556) 1 = Jog 1 0 = Not Clear Fault 1 = Clear Fault 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control 0 = Not Manual 1 = Manual 00 = No Command 01 = Use Accel Time 1 (Par. 535) 10 = Use Accel Time 2 (Par. 536) 11 = Use Present Time 00 = No Command 01 = Use Decel Time 1 (Par. 537) 10 = Use Decel Time 2 (Par. 538) 11 = Use Present Time 000 = No Command 001 = Ref A Select (Par. 545) 010 = Ref B Select (Par. 550) 011 = Preset 3 (Par. 573) 100 = Preset 4 (Par. 574) 101 = Preset 5 (Par. 575) 110 = Preset 6 (Par. 576) 111 = Preset 7 (Par. 577)
Reserved
(1)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition will start the drive.
(2)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog 1/Jog 2 condition will jog the drive. A transition to a ‘0’ will stop the drive.
(3)
To perform this command, the value must switch from ‘0’ to ‘1’.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 252
D-6
Logic Command/Status Words
Logic Status Word Logic Bits 31…15 14 13 12 11 10 9
8
7
6
5
4
3
2 x x x x x x x x x x x x x x
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
1
0 Command x Run Ready x
Active Command Direction Actual Direction Accelerating Decelerating Alarm Fault At Setpt Spd Manual Spd Ref ID 0 Spd Ref ID 1 Spd Ref ID 2 Spd Ref ID 3 Spd Ref ID 4
Reserved
Description 0 = Not Ready to Run (Par. 933) 1 = Ready to Run 0 = Not Active 1 = Active 0 = Reverse 1 = Forward 0 = Reverse 1 = Forward 0 = Not Accelerating 1 = Accelerating 0 = Not Decelerating 1 = Decelerating 0 = No Alarm (Par. 959 and 960) 1 = Alarm 0 = No Fault (Par. 952 and 953) 1 = Fault 0 = Not at Setpoint Speed 1 = At Setpoint Speed 0 = Manual Mode Not Active 1 = Manual Mode Active 00000 = Reserved 00001 = Auto Ref A (Par. 545) 00010 = Auto Ref B (Par. 550) 00011 = Auto Preset Speed 3 (Par. 573) 00100 = Auto Preset Speed 4 (Par. 574) 00101 = Auto Preset Speed 5 (Par. 575) 00110 = Auto Preset Speed 6 (Par. 576) 00111 = Auto Preset Speed 7 (Par. 577) 01000 = Reserved 01001 = Reserved 01010 = Reserved 01011 = Reserved 01100 = Reserved 01101 = Reserved 01110 = Reserved 01111 = Reserved 10000 = Man Port 0 10001 = Man Port 1 10010 = Man Port 2 10011 = Man Port 3 10100 = Man Port 4 10101 = Man Port 5 10110 = Man Port 6 10111 = Reserved 11000 = Reserved 11001 = Reserved 11010 = Reserved 11011 = Reserved 11100 = Reserved 11101 = Man Port 13 (embedded ENET) 11110 = Man Port 14 (Drive Logix) 11111 = Alternate Man Ref Sel
Page 253
Logic Command/Status Words
D-7
PowerFlex Digital DC Drives Logic Command Word Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x x x x x x
0 x
Command Stop (1) Start (1)(2) Jog Clear Faults Direction
Local Control MOP Increment Accel Rate
Decel Rate
Reference Select (3)
MOP Decrement
Description 0 = Not Stop 1 = Stop 0 = Not Start 1 = Start 0 = Not Jog (Par. 266) 1 = Jog 0 = Not Clear Faults 1 = Clear Faults 00 = No Command 01 = Forward Command 10 = Reverse Command 11 = Hold Direction Control 0 = No Local Control 1 = Local Control 0 = Not Increment 1 = Increment 00 = No Command 01 = Use Accel Rate 1 (Par. 660) 10 = Use Accel Rate 2 (Par. 24) 11 = Use Present Time 00 = No Command 01 = Use Decel Rate 1 (Par. 662) 10 = Use Decel Rate 2 (Par. 32) 11 = Use Present Time 000 = No Command 001 = Ref. 1 (Spd Ref A, Par. 44) 010 = Ref. 2 (Spd Ref B, Par. 48) 011 = Ref. 3 (Preset Spd 3, Par. 156) 100 = Ref. 4 (Preset Spd 4, Par. 157) 101 = Ref. 5 (Preset Spd 5, Par. 158) 110 = Ref. 6 (Preset Spd 6, Par. 159) 111 = Ref. 7 (Preset Spd 7, Par. 160) 0 = Not Decrement 1 = Decrement
(1) A ‘0 = Not Stop’ condition (logic 0) must first be present before a ‘1 = Start’ condition will start the drive. The Start command acts as a momentary
Start command. A ‘1’ will start the drive, but returning to ‘0’ will not stop the drive. (2)
This Start will not function if a digital input (parameters 133…144) is programmed for 2-Wire Control (option 5 ‘Run’, 6 ‘Run Forward’, or 7 ‘Run Reverse’).
(3)
This Reference Select will not function if a digital input (parameters 133…144) is programmed for ‘Speed Sel 1, 2, or 3’ (option 17, 18, or 19). Note that Reference Select is ‘Exclusive Ownership’ – see drive User Manual for more information.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 254
D-8
Logic Command/Status Words
Logic Status Word Logic Bits 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1 x x x x x x x x x x
(1)
x x x x x
See ‘Owners’ in drive User Manual for further information.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
0 x
Status Ready
Description 0 = Not Ready (Par. 1403) 1 = Ready Active 0 = Not Active (Running) 1 = Active Command 0 = Reverse Direction 1 = Forward Actual Direction 0 = Reverse 1 = Forward Accel 0 = Not Accelerating 1 = Accelerating Decel 0 = Not Decelerating 1 = Decelerating Alarm 0 = No Alarm (Par. 1380) 1 = Alarm Fault 0 = No Fault (Par. 1351) 1 = Fault At Speed 0 = Not At Reference 1 = At Reference 000 = Port 0 (TB) Local Control (1) 001 = Port 1 010 = Port 2 011 = Port 3 100 = Port 4 101 = Port 5 110 = Reserved 111 = No Local Reference Source 0000 = Spd Ref A Auto (Par. 44) 0001 = Spd Ref B Auto (Par. 48) 0010 = Preset Spd 2 Auto 0011 = Preset Spd 3 Auto 0100 = Preset Spd 4 Auto 0101 = Preset Spd 5 Auto 0110 = Preset Spd 6 Auto 0111 = Preset Spd 7 Auto 1000 = Term Blk Manual 1001 = DPI 1 Manual 1010 = DPI 2 Manual 1011 = DPI 3 Manual 1100 = DPI 4 Manual 1101 = DPI 5 Manual 1110 = Reserved 1111 = Jog Ref