PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 7
Pages 193 to 200 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual
The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 20-COMM-C
Page 193
Chapter 7
Troubleshooting
This chapter provides information for diagnosing and troubleshooting potential problems with the adapter and network.
Understanding the Status Indicators
Topic
Page
Understanding the Status Indicators
7-1
PORT Status Indicator
7-2
MOD Status Indicator
7-2
NET A and NET B Status Indicators
7-3
Viewing Adapter Diagnostic Items
7-4
Viewing and Clearing Events
7-6
The adapter has four status indicators. They can be viewed on the adapter or through the drive cover. Location on drive may vary.
➊ ➋ ➌ ➍
➊ ➋ ➌ ➍
Item
Indicator Name
Description
See
➊
PORT
DPI Connection Status page 7-2
➋
MOD
Adapter Status page 7-2
➌
NET A
ControlNet Channel A Status page 7-3
➍
NET B
ControlNet Channel B Status page 7-3
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 194
7-2
Troubleshooting
PORT Status Indicator
This red/green bicolor LED indicates the status of the adapter’s connection to the drive as shown in the table below.
Status
Cause
Corrective Action
Off
The adapter is not powered or is not properly connected to the drive.
• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive (or adapter if mounted in a DPI External Comms Kit).
Flashing Red
The adapter is not receiving a ping message from the drive.
• Verify that cables are securely connected and not damaged. Replace cables if necessary. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit).
Steady Red
The drive has refused an I/O connection from the adapter.
Important: Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) after making any of the following corrections:
Another DPI peripheral is using the same DPI port as the adapter.
• Verify that all DPI cables on the drive are securely connected and not damaged. Replace cables if necessary. • Verify that the DPI drive supports Datalinks. • Configure the adapter to use a Datalink that is not already being used by another peripheral.
Steady Orange
The adapter is connected to a product that does not support Allen-Bradley DPI communications.
Connect the adapter to a product that supports Allen-Bradley DPI communications (for example, a PowerFlex 7-Class drive).
Flashing Green The adapter is establishing an I/O connection to the drive.
No action required. Normal behavior if no DPI I/O is enabled.
Steady Green
No action required.
The adapter is properly connected and is communicating with the drive.
MOD Status Indicator
This red/green bicolor LED indicates the status of the adapter as shown in the table below.
Status
Cause
Corrective Action
Off
The adapter is not powered or is not properly connected to the drive.
• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive (or adapter if mounted in a DPI External Comms Kit).
Flashing Red
The adapter has failed the firmware test.
• Clear faults in the adapter.
The adapter firmware is being updated.
• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit). • If cycling power does not correct the problem, the adapter parameter settings may have been corrupted. Reset defaults and reconfigure the adapter. • If resetting defaults does not correct the problem, update the adapter with the latest firmware revision.
Steady Red
The adapter has failed the hardware test.
• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit). • Replace the adapter.
Flashing Green The adapter is operational, but is not transferring I/O data to a controller.
• Place the scanner in RUN mode. • Program the controller to recognize and transmit I/O to the adapter. • Configure the adapter for the program in the controller. • Normal behavior if no DPI I/O is enabled.
Steady Green
No action required.
The adapter is operational and transferring I/O data to a controller.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 195
Troubleshooting
NET A and NET B Status Indicators
7-3
These red/green bicolor LEDs indicate the status for the ControlNet Channel A and Channel B network connections as shown in the tables below. Depending on the state of these LEDs, they should be interpreted together or independently.
Indicators Interpreted Together Status
Cause
Corrective Actions
Both LEDs Off
A reset occurred or the adapter is not powered.
Apply power to the drive (or adapter if mounted in a DPI External Comms Kit) and network.
Both LEDs Steady Red
A link interface failed.
• Check media for broken cables, loose connectors, missing terminators, and so forth. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter. If the problem persists, contact Rockwell Technical Support.
LEDs Alternately Flashing Red/Green
The adapter is in self-test mode.
No action required. The adapter will exit this mode when the self-test is completed.
LEDs Alternately Flashing Red/Off
There is a bad node configuration.
• Verify that all node addresses are unique. • Check the adapter’s configuration. • Check media for broken cables, loose connectors, missing terminators, etc. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter.
Indicator Interpreted Independently Status
Cause
Corrective Actions
One channel LED is Steady Off.
That channel is disabled or not supported.
Program the network for redundant media, if required.
One channel LED is Flashing Red/Green.
There is an invalid link configuration for that channel.
• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter. • Reset the controller. • If the problem persists, contact Rockwell Technical Support.
One channel LED is Flashing Red/Off.
The channel is not receiving network activity.
Check media for broken cables, loose connectors, missing terminators, and so forth.
One channel LED is Flashing Green/Off.
A temporary channel error has occurred, or the channel is in listen-only mode.
Verify the controller is present on the network and working.
One channel LED is Steady Green.
Normal operation for that channel.
No action required.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 196
7-4
Troubleshooting
Viewing Adapter Diagnostic If you encounter unexpected communications problems, the adapter’s diagnostic items may help you or Rockwell Automation personnel Items troubleshoot the problem. Adapter diagnostic items can be viewed with any of these drive configuration tools:
• • • •
LCD PowerFlex 7-Class HIM (Diagnostics/Device Items) Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.01 or later DriveExecutive software, version 3.01 or later
Using the HIM to View Adapter Diagnostic Items Step
Example Screen
1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.
3. Press the adapter.
(Enter) key to display the Diagnostics menu in the
4. Repeat steps 2 and 3 to enter the Device Items option. 5. Press the or
Main Menu: Diagnostics Parameter Device Select Device Item # Reference
3 key to scroll through the items.
Table 7.A Adapter Diagnostic Items
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
No.
Name
Description
1
Common Logic Cmd
The present value of the Common Logic Command being transmitted to the drive by this adapter.
2
Prod Logic Cmd
The present value of the Product Logic Command being transmitted to the drive by this adapter from the controller.
3
Reference
The present value of the Reference being transmitted to the drive by this adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.
4
Common Logic Sts
The present value of the Common Logic Status being received from the drive by this adapter.
5
Prod Logic Sts
The present value of the Product Logic Status being received from the drive by this adapter from the controller.
6
Feedback
The present value of the Feedback being received from the drive by this adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.
7
Datalink A1 In
8
Datalink A2 In
The present value of respective Datalink In being transmitted to the drive by this adapter. (If not using a Datalink, this parameter should have a value of zero.)
9
Datalink B1 In
10
Datalink B2 In
11
Datalink C1 In
12
Datalink C2 In
13
Datalink D1 In
14
Datalink D2 In
Page 197
Troubleshooting
7-5
Table 7.A Adapter Diagnostic Items (Continued) No.
Name
Description
15
Datalink A1 Out
16
Datalink A2 Out
17
Datalink B1 Out
The present value of respective Datalink Out being received from the drive by this adapter. (If the drive indicates a 16-bit datalink size, the value appears in the least significant 16 bits of this diagnostic item, and the most significant 16 bits of this diagnostic item are zero.)
18
Datalink B2 Out
19
Datalink C1 Out
20
Datalink C2 Out
21
Datalink D1 Out
22
Datalink D2 Out
23
DPI Rx Errors
The present value of the DPI Receive error counter.
24
DPI Rx Error Max
The maximum value (since reset) of the DPI Receive error counter.
25
DPI Tx Errors
The present value of the DPI Transmit error counter.
26
DPI Tx Error Max
The maximum value (since reset) of the DPI Transmit error counter.
27
Node Address SW
The present value of the adapter node address switches.
28
Boot Flash Count
The number of times the boot firmware in the adapter has been updated.
29
App Flash Count
The number of times the application firmware in the adapter has been updated.
30
M-S Input Size
The size of data transferred from the network to the drive.
31
M-S Output Size
The size of data transferred from the drive to the network.
32
OPT Status
The operating status of optional I/O board in the DPI External Comms Kit. For the meanings of the individual bits, see Viewing Optional I/O Diagnostic Items on page 8-4.
33
OPT RX Errors
Number of optional I/O board receive errors.
34
OPT FW Version
Firmware version of optional I/O board (in DPI External Comms Kit).
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 198
7-6
Troubleshooting
Viewing and Clearing Events
The adapter has an event queue to record significant events that occur in the operation of the adapter. When such an event occurs, an entry is put into the event queue. You can view the event queue with any of these drive configuration tools: • • • •
LCD PowerFlex 7-Class HIM Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.01 or later DriveExecutive software, version 1.01 or later
The event queue can contain up to 32 entries. Eventually the event queue will become full, since its contents are retained through adapter resets. At that point, a new entry replaces the oldest entry. Only an event queue clear operation or adapter power cycle will clear the event queue contents. Resetting the adapter to defaults has no effect on the event queue.
Using the HIM to View and Clear Events Step
Example Screen
Viewing Events 1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.
3. Press the adapter.
(Enter) key to display the Diagnostics menu in the
4. Repeat steps 2 and 3 to enter the Events option and then View Event Queue option.
Main Menu: Diagnostics Parameter Device Select
Event Q: Ping Time Flt
1
5. Press the or key to scroll through events. The most recent event is Event 1. Clearing Events 1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.
3. Press the adapter.
(Enter) key to display the Diagnostics menu in the
4. Repeat steps 2 and 3 to enter the Events option and then the Clear Event option or Clr Event Queue option. A message will pop up to confirm that you want to clear the message or queue. 5. Press the (Enter) key to confirm your request. If Clr Event Queue was selected, all event queue entries will then display ‘No Event’.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Dgn: Events View Event Queue Clear Event Clr Event Queue
E3
Page 199
Troubleshooting
7-7
Events Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Allen-Bradley personnel troubleshoot the problem. The following events may appear in the event queue. Table 7.B Adapter Events Code
Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt
A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.
3
Ping Time Flt
A ping message was not received on DPI within the specified time.
4
Port ID Flt
The adapter is not connected to a correct port on a DPI product.
5
Port Change Flt
The DPI port changed after start up.
6
Host Sent Reset
The drive sent a reset event message.
7
EEPROM Sum Flt
The EEPROM in the adapter is corrupt.
8
Online @ 125kbps
The adapter detected that the drive is communicating at 125 kbps.
9
Online @ 500kbps
The adapter detected that the drive is communicating at 500 kbps.
10
Bad Host Flt
The adapter was connected to an incompatible product.
11
Dup Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for Type 0 control.
13
Type 0 Time Flt
The adapter has not received a Type 0 status message within the specified time.
14
DL Login
The adapter has logged into a Datalink.
15
DL Reject Flt
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.
16
DL Time Flt
The adapter has not received a Datalink message within the specified time.
17
Reserved
Not used.
18
Control Disabled
The adapter has sent a ‘Soft Control Disable’ command to the drive.
19
Control Enabled
The adapter has sent a ‘Soft Control Enable’ command to the drive.
20
Message Timeout
A Client-Server message sent by the adapter was not completed within 1 sec.
21
Flt Cfg Error
One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.
22
App CRC Flt
Startup sequence detected corrupt application firmware.
23
App Updated
New application firmware was detected.
24
CN Comm Flt
The adapter detected a communications fault on the network.
25
CN Sent Reset
The adapter received a reset from the network.
26
CN Close Flt
An I/O connection from the network to the adapter was closed.
27
CN Idle Flt
The adapter is receiving ‘idle’ packets from the network.
28
CN Open
An I/O connection from the network to the adapter has been opened.
29
CN Timeout Flt
An I/O connection from the network to the adapter has timed out.
30
PCCC IO Close
The device sending PCCC Control messages to the adapter has set the PCCC Control Timeout to zero.
31
PCCC IO Open
The adapter has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).
32
PCCC IO Time Flt
The adapter has not received a PCCC Control message for longer than the PCCC Control Timeout.
33
Watchdog T/O Flt
The software detects a failure.
34
EEPROM Init
Startup sequence detected a blank EEPROM map revision.
35
DPI Fault Clear
The drive issued this because a fault was cleared.
36
Normal Startup
The adapter successfully started up.
37
Manual Reset
The adapter was reset by changing its Reset Module parameter.
38
OPT Open
The adapter began exchanging I/O data with the I/O option of the DPI External Comms Kit. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P
Page 200
7-8
Troubleshooting
Table 7.B Adapter Events (Continued) Code
Event
Description
39
OPT Close
The adapter forced a fault condition on the I/O option of the DPI External Comms Kit.
40
OPT Timeout
Communication between the adapter and I/O option of the DPI External Comms Kit was disrupted.
41
CN Link Up
The adapter successfully joined the ControlNet network.
42
CN Link Down
The adapter lost its connection to the ControlNet network.
43
Dup CN Addr
The adapter detected a duplicate ControlNet node address.
20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P