For the Allen-Bradley 20-COMM-C

Page 193

Chapter 7

Troubleshooting

This chapter provides information for diagnosing and troubleshooting potential problems with the adapter and network.

Understanding the Status Indicators

Topic

Page

Understanding the Status Indicators

7-1

PORT Status Indicator

7-2

MOD Status Indicator

7-2

NET A and NET B Status Indicators

7-3

Viewing Adapter Diagnostic Items

7-4

Viewing and Clearing Events

7-6

The adapter has four status indicators. They can be viewed on the adapter or through the drive cover. Location on drive may vary.

➊ ➋ ➌ ➍

➊ ➋ ➌ ➍

Item

Indicator Name

Description

See

➊

PORT

DPI Connection Status page 7-2

➋

MOD

Adapter Status page 7-2

➌

NET A

ControlNet Channel A Status page 7-3

➍

NET B

ControlNet Channel B Status page 7-3

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 194

7-2

Troubleshooting

PORT Status Indicator

This red/green bicolor LED indicates the status of the adapter’s connection to the drive as shown in the table below.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly connected to the drive.

• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive (or adapter if mounted in a DPI External Comms Kit).

Flashing Red

The adapter is not receiving a ping message from the drive.

• Verify that cables are securely connected and not damaged. Replace cables if necessary. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit).

Steady Red

The drive has refused an I/O connection from the adapter.

Important: Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) after making any of the following corrections:

Another DPI peripheral is using the same DPI port as the adapter.

• Verify that all DPI cables on the drive are securely connected and not damaged. Replace cables if necessary. • Verify that the DPI drive supports Datalinks. • Configure the adapter to use a Datalink that is not already being used by another peripheral.

Steady Orange

The adapter is connected to a product that does not support Allen-Bradley DPI communications.

Connect the adapter to a product that supports Allen-Bradley DPI communications (for example, a PowerFlex 7-Class drive).

Flashing Green The adapter is establishing an I/O connection to the drive.

No action required. Normal behavior if no DPI I/O is enabled.

Steady Green

No action required.

The adapter is properly connected and is communicating with the drive.

MOD Status Indicator

This red/green bicolor LED indicates the status of the adapter as shown in the table below.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly connected to the drive.

• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive (or adapter if mounted in a DPI External Comms Kit).

Flashing Red

The adapter has failed the firmware test.

• Clear faults in the adapter.

The adapter firmware is being updated.

• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit). • If cycling power does not correct the problem, the adapter parameter settings may have been corrupted. Reset defaults and reconfigure the adapter. • If resetting defaults does not correct the problem, update the adapter with the latest firmware revision.

Steady Red

The adapter has failed the hardware test.

• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit). • Replace the adapter.

Flashing Green The adapter is operational, but is not transferring I/O data to a controller.

• Place the scanner in RUN mode. • Program the controller to recognize and transmit I/O to the adapter. • Configure the adapter for the program in the controller. • Normal behavior if no DPI I/O is enabled.

Steady Green

No action required.

The adapter is operational and transferring I/O data to a controller.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 195

Troubleshooting

NET A and NET B Status Indicators

7-3

These red/green bicolor LEDs indicate the status for the ControlNet Channel A and Channel B network connections as shown in the tables below. Depending on the state of these LEDs, they should be interpreted together or independently.

Indicators Interpreted Together Status

Cause

Corrective Actions

Both LEDs Off

A reset occurred or the adapter is not powered.

Apply power to the drive (or adapter if mounted in a DPI External Comms Kit) and network.

Both LEDs Steady Red

A link interface failed.

• Check media for broken cables, loose connectors, missing terminators, and so forth. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter. If the problem persists, contact Rockwell Technical Support.

LEDs Alternately Flashing Red/Green

The adapter is in self-test mode.

No action required. The adapter will exit this mode when the self-test is completed.

LEDs Alternately Flashing Red/Off

There is a bad node configuration.

• Verify that all node addresses are unique. • Check the adapter’s configuration. • Check media for broken cables, loose connectors, missing terminators, etc. • Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter.

Indicator Interpreted Independently Status

Cause

Corrective Actions

One channel LED is Steady Off.

That channel is disabled or not supported.

Program the network for redundant media, if required.

One channel LED is Flashing Red/Green.

There is an invalid link configuration for that channel.

• Cycle power to the drive (or adapter if mounted in a DPI External Comms Kit) or reset the adapter. • Reset the controller. • If the problem persists, contact Rockwell Technical Support.

One channel LED is Flashing Red/Off.

The channel is not receiving network activity.

Check media for broken cables, loose connectors, missing terminators, and so forth.

One channel LED is Flashing Green/Off.

A temporary channel error has occurred, or the channel is in listen-only mode.

Verify the controller is present on the network and working.

One channel LED is Steady Green.

Normal operation for that channel.

No action required.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 196

7-4

Troubleshooting

Viewing Adapter Diagnostic If you encounter unexpected communications problems, the adapter’s diagnostic items may help you or Rockwell Automation personnel Items troubleshoot the problem. Adapter diagnostic items can be viewed with any of these drive configuration tools:

• • • •

LCD PowerFlex 7-Class HIM (Diagnostics/Device Items) Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.01 or later DriveExecutive software, version 3.01 or later

Using the HIM to View Adapter Diagnostic Items Step

Example Screen

1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.

3. Press the adapter.

(Enter) key to display the Diagnostics menu in the

4. Repeat steps 2 and 3 to enter the Device Items option. 5. Press the or

Main Menu: Diagnostics Parameter Device Select Device Item # Reference

3 key to scroll through the items.

Table 7.A Adapter Diagnostic Items

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

No.

Name

Description

1

Common Logic Cmd

The present value of the Common Logic Command being transmitted to the drive by this adapter.

2

Prod Logic Cmd

The present value of the Product Logic Command being transmitted to the drive by this adapter from the controller.

3

Reference

The present value of the Reference being transmitted to the drive by this adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.

4

Common Logic Sts

The present value of the Common Logic Status being received from the drive by this adapter.

5

Prod Logic Sts

The present value of the Product Logic Status being received from the drive by this adapter from the controller.

6

Feedback

The present value of the Feedback being received from the drive by this adapter. Note that a 16-bit value will be sent as the Most Significant Word of the 32-bit field.

7

Datalink A1 In

8

Datalink A2 In

The present value of respective Datalink In being transmitted to the drive by this adapter. (If not using a Datalink, this parameter should have a value of zero.)

9

Datalink B1 In

10

Datalink B2 In

11

Datalink C1 In

12

Datalink C2 In

13

Datalink D1 In

14

Datalink D2 In

Page 197

Troubleshooting

7-5

Table 7.A Adapter Diagnostic Items (Continued) No.

Name

Description

15

Datalink A1 Out

16

Datalink A2 Out

17

Datalink B1 Out

The present value of respective Datalink Out being received from the drive by this adapter. (If the drive indicates a 16-bit datalink size, the value appears in the least significant 16 bits of this diagnostic item, and the most significant 16 bits of this diagnostic item are zero.)

18

Datalink B2 Out

19

Datalink C1 Out

20

Datalink C2 Out

21

Datalink D1 Out

22

Datalink D2 Out

23

DPI Rx Errors

The present value of the DPI Receive error counter.

24

DPI Rx Error Max

The maximum value (since reset) of the DPI Receive error counter.

25

DPI Tx Errors

The present value of the DPI Transmit error counter.

26

DPI Tx Error Max

The maximum value (since reset) of the DPI Transmit error counter.

27

Node Address SW

The present value of the adapter node address switches.

28

Boot Flash Count

The number of times the boot firmware in the adapter has been updated.

29

App Flash Count

The number of times the application firmware in the adapter has been updated.

30

M-S Input Size

The size of data transferred from the network to the drive.

31

M-S Output Size

The size of data transferred from the drive to the network.

32

OPT Status

The operating status of optional I/O board in the DPI External Comms Kit. For the meanings of the individual bits, see Viewing Optional I/O Diagnostic Items on page 8-4.

33

OPT RX Errors

Number of optional I/O board receive errors.

34

OPT FW Version

Firmware version of optional I/O board (in DPI External Comms Kit).

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 198

7-6

Troubleshooting

Viewing and Clearing Events

The adapter has an event queue to record significant events that occur in the operation of the adapter. When such an event occurs, an entry is put into the event queue. You can view the event queue with any of these drive configuration tools: • • • •

LCD PowerFlex 7-Class HIM Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.01 or later DriveExecutive software, version 1.01 or later

The event queue can contain up to 32 entries. Eventually the event queue will become full, since its contents are retained through adapter resets. At that point, a new entry replaces the oldest entry. Only an event queue clear operation or adapter power cycle will clear the event queue contents. Resetting the adapter to defaults has no effect on the event queue.

Using the HIM to View and Clear Events Step

Example Screen

Viewing Events 1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.

3. Press the adapter.

(Enter) key to display the Diagnostics menu in the

4. Repeat steps 2 and 3 to enter the Events option and then View Event Queue option.

Main Menu: Diagnostics Parameter Device Select

Event Q: Ping Time Flt

1

5. Press the or key to scroll through events. The most recent event is Event 1. Clearing Events 1. Access parameters in the adapter. See Using the PowerFlex 7-Class HIM to Access Parameters on page 3-2. 2. Press the or key to scroll to Diagnostics.

3. Press the adapter.

(Enter) key to display the Diagnostics menu in the

4. Repeat steps 2 and 3 to enter the Events option and then the Clear Event option or Clr Event Queue option. A message will pop up to confirm that you want to clear the message or queue. 5. Press the (Enter) key to confirm your request. If Clr Event Queue was selected, all event queue entries will then display ‘No Event’.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Dgn: Events View Event Queue Clear Event Clr Event Queue

E3

Page 199

Troubleshooting

7-7

Events Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Allen-Bradley personnel troubleshoot the problem. The following events may appear in the event queue. Table 7.B Adapter Events Code

Event

Description

1

No Event

Empty event queue entry.

2

DPI Bus Off Flt

A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.

3

Ping Time Flt

A ping message was not received on DPI within the specified time.

4

Port ID Flt

The adapter is not connected to a correct port on a DPI product.

5

Port Change Flt

The DPI port changed after start up.

6

Host Sent Reset

The drive sent a reset event message.

7

EEPROM Sum Flt

The EEPROM in the adapter is corrupt.

8

Online @ 125kbps

The adapter detected that the drive is communicating at 125 kbps.

9

Online @ 500kbps

The adapter detected that the drive is communicating at 500 kbps.

10

Bad Host Flt

The adapter was connected to an incompatible product.

11

Dup Port Flt

Another peripheral with the same port number is already in use.

12

Type 0 Login

The adapter has logged in for Type 0 control.

13

Type 0 Time Flt

The adapter has not received a Type 0 status message within the specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the specified time.

17

Reserved

Not used.

18

Control Disabled

The adapter has sent a ‘Soft Control Disable’ command to the drive.

19

Control Enabled

The adapter has sent a ‘Soft Control Enable’ command to the drive.

20

Message Timeout

A Client-Server message sent by the adapter was not completed within 1 sec.

21

Flt Cfg Error

One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.

22

App CRC Flt

Startup sequence detected corrupt application firmware.

23

App Updated

New application firmware was detected.

24

CN Comm Flt

The adapter detected a communications fault on the network.

25

CN Sent Reset

The adapter received a reset from the network.

26

CN Close Flt

An I/O connection from the network to the adapter was closed.

27

CN Idle Flt

The adapter is receiving ‘idle’ packets from the network.

28

CN Open

An I/O connection from the network to the adapter has been opened.

29

CN Timeout Flt

An I/O connection from the network to the adapter has timed out.

30

PCCC IO Close

The device sending PCCC Control messages to the adapter has set the PCCC Control Timeout to zero.

31

PCCC IO Open

The adapter has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).

32

PCCC IO Time Flt

The adapter has not received a PCCC Control message for longer than the PCCC Control Timeout.

33

Watchdog T/O Flt

The software detects a failure.

34

EEPROM Init

Startup sequence detected a blank EEPROM map revision.

35

DPI Fault Clear

The drive issued this because a fault was cleared.

36

Normal Startup

The adapter successfully started up.

37

Manual Reset

The adapter was reset by changing its Reset Module parameter.

38

OPT Open

The adapter began exchanging I/O data with the I/O option of the DPI External Comms Kit. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 200

7-8

Troubleshooting

Table 7.B Adapter Events (Continued) Code

Event

Description

39

OPT Close

The adapter forced a fault condition on the I/O option of the DPI External Comms Kit.

40

OPT Timeout

Communication between the adapter and I/O option of the DPI External Comms Kit was disrupted.

41

CN Link Up

The adapter successfully joined the ControlNet network.

42

CN Link Down

The adapter lost its connection to the ControlNet network.

43

Dup CN Addr

The adapter detected a duplicate ControlNet node address.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P