PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual: Chapter 1

Pages 13 to 18 of 270, from PowerFlex ControlNet Adapters 20-COMM-C (Coax), 20-COMM-Q (Fiber) User Manual

The original document is the PDF (6.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 20-COMM-C

Page 13

Chapter 1

Getting Started The adapter is intended for installation into a PowerFlex 7-Class drive and is used for network communication. The 20-COMM-C Series B coax adapter, firmware 2.xxx or later, or 20-COMM-Q Series A fiber adapter, firmware 2.xxx or later, can also be installed in an External DPI Comms Kit (20-XCOMM-DC-BASE). For PowerFlex 750-Series drives, we recommend using the 20-750-CNETC Coaxial ControlNet option module instead of the 20-COMM-C adapter. However, this manual does include information on using the 20-COMM-C or 20-COMM-Q adapter with PowerFlex 750-Series drives - but there are operating limitations. For details, see Compatible Products on page 1-3. Topic

Page

Components

1-1

Features

1-2

Compatible Products

1-3

Required Equipment

1-3

Safety Precautions

1-5

Quick Start

1-6

Components

20-COMM-C Coax Adapter

20-COMM-Q Fiber Adapter

➊

➊

➋

➋

➌

➍

➎

➌

➍

➎

Item

Part

Description

➊

Status Indicators

Four status indicators that indicate the status of the DPI, the adapter, and network connection. See Chapter 7, Troubleshooting.

➋

DPI Connector

A 20-pin, single-row shrouded male header. An Internal Interface cable is connected to this connector and a connector on the drive.

➌

20-COMM-C: Channel A Coax Receptacle

Channel A BNC connection to the network.

20-COMM-Q: Channel A Fiber Receptacles

Channel A V-pin connection to the network.

20-COMM-C: Channel B Coax Receptacle

Channel B (redundant) BNC connection to the network.

20-COMM-Q: Channel B Fiber Receptacles

Channel B (redundant) V-pin connection to the network.

Node Address Switches

Switches to set the node address. See Setting the Node Address Switches on page 2-2.

➍ ➎

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 14

1-2

Getting Started

Features

The features of the adapter include the following: • Typical mounting in a PowerFlex 7-Class drive. The 20-COMM-C Series B coax adapter, firmware 2.xxx or later, or 20-COMM-Q Series A fiber adapter, firmware 2.xxx or later, can also be installed in a DPI External Comms Kit and used with the kit’s optional I/O board. See Chapter 8, Using the Adapter in a DPI External Comms Kit (20-XCOMM-DC-BASE) for more information. DPI External Comms Kit Compatibility Adapter

Operation With

Type

Series

Firmware Revision

20-COMM-C (coaxial)

A B

20-COMM-Q (fiber)

A

DPI External Comms Kit (20-XCOMM-DC-BASE)

Optional I/O Board (20-XCOMM-IO-OPT1)

1.xxx

No

No

2.xxx

Yes

No

1.xxx

No

No

2.xxx and later

Yes

Yes

1.xxx

No

No

2.xxx and later

Yes

Yes

• Captive screws to secure and ground the adapter to the drive or, when mounted in a DPI External Comms Kit, to the kit’s metal enclosure. • Compatibility with various configuration tools to configure the adapter and connected host drive, including the following tools: – PowerFlex HIM (Human Interface Module) on the drive, if available – Connected Components Workbench software, version 1.02 or later – DriveExplorer software, version 2.01 or later – DriveExecutive software, version 3.01 or later • Switches to set a node address before applying power to the PowerFlex drive, or you can disable the switches and use an adapter parameter to configure the node address. • Status indicators that report the status of the drive communications, the adapter, and network. They are visible when the drive cover is open or closed. • Parameter-configured I/O (Logic Command/Reference and up to four pairs of Datalinks) to accommodate application requirements. • Explicit Messaging support. • Master-Slave hierarchy that can be configured to transmit data to and from a controller on the network. • User-defined fault actions to determine how the adapter and connected PowerFlex drive respond to the following: – I/O messaging communication disruptions (Comm Flt Action) – Controllers in idle mode (Idle Flt Action) • Access to any PowerFlex drive and its connected peripherals on the network to which the adapter is connected. 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 15

Getting Started

Compatible Products

1-3

At the time of publication, the adapter is compatible with the following products: • PowerFlex 70 drives with standard or enhanced control

• PowerFlex 750-Series drives (1)

• PowerFlex 700 drives with standard or vector control

• PowerFlex Digital DC drives

• PowerFlex 700H drives

• DPI External Comms Kit

• PowerFlex 700S drives with Phase I or Phase II control

• SMC™ Flex smart motor controllers

• PowerFlex 700L drives with 700 vector control or 700S control

• SMC-50 smart motor controllers

(1)

The 20-COMM-C or 20-COMM-Q adapter can be used with PowerFlex 750-Series drives, but the adapter must have firmware revision 3.001 or later. Also, the adapter has the following limitations and differences: - Only the first 16 bits of the Logic Command and Logic Status words are used. - Speed Reference and Feedback scaling are Hz (or RPM) x 1000 (depending on the setting of drive parameter 300 - [Speed Units]. Instead of using the 20-COMM-C adapter with the PowerFlex 750-Series drive, the 20-750-CNETC Coaxial ControlNet option module should be used whenever possible. Please see the PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001, for drive parameter information and the 20-750-CNETC ControlNet Option Module User Manual, publication 750COM-UM003, for network communication module information.

Required Equipment

Some of the equipment that is required for use with the adapter is shipped with the adapter, but some you must supply yourself.

Equipment Shipped with the Adapter When you unpack the adapter, verify that the package includes the following: ❑ One 20-COMM-C coax or 20-COMM-Q fiber adapter ❑ One 2.54 cm (1 in.) long and one 15.24 cm (6 in.) long Internal Interface cable (only one cable is needed to connect the adapter to the drive; for which cable to use, see Figure 2.2 on page 2-4) ❑ One PowerFlex 7-Class DPI (Drive Peripheral Interface) Network Communication Adapter Installation Instructions, publication 20COMM-IN004 TIP: When mounting the 20-COMM-C or 20-COMM-Q adapter in a PowerFlex 750-Series drive, you must use a 20-750-20COMM or 20-750-20COMM-F1 Communication Carrier Card, publication 750COM-IN001 - and the 20-COMM-C or 20-COMM-Q adapter must have firmware revision 3.001 or later.

User-Supplied Equipment To install and configure the adapter, you must supply the following: ❑ A small flathead screwdriver ❑ ControlNet cable (for details, see to the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002, or the ControlNet Fiber Media Planning and Installation Guide, publication CNET-IN001) 20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 16

1-4

Getting Started

❑ Drive and adapter configuration tool, such as the following: – PowerFlex 20-HIM-xx HIM – RSNetWorx for ControlNet software, version 6.00 or later – Connected Components Workbench software, version 1.02 or later Connected Components Workbench is the recommended stand-alone software tool for use with PowerFlex drives. You can obtain a free copy by: • Internet download at http://www.ab.com/support/abdrives/ webupdate/software.html • Requesting a DVD at http://www.ab.com/onecontact/controllers/ micro800/ Your local distributor may also have copies of the DVD available. Connected Components Workbench software cannot be used to configure SCANport-based drives or Bulletin 160 drives. – DriveExplorer software, version 2.01 or later This software tool has been discontinued and is now available as freeware at http://www.ab.com/support/abdrives/webupdate/ software.html. There are no plans to provide future updates to this tool and the download is being provided ‘as-is’ for users that lost their DriveExplorer CD, or need to configure legacy products not supported by Connected Components Workbench software. – DriveExecutive software, version 3.01 or later A Lite version of DriveExecutive software ships with RSLogix 5000, RSNetWorx MD, FactoryTalk AssetCentre, and ItelliCENTER software. All other versions are purchasable items: • 9303-4DTE01ENE Drive Executive software • 9303-4DTS01ENE DriveTools SP Suite (includes DriveExecutive and DriveObserver software) • 9303-4DTE2S01ENE DriveExecutive software upgrade to DriveTools SP Suite (adds DriveObserver software) DriveExecutive software updates (patches, and so forth) can be obtained at http://www.ab.com/support/abdrives/webupdate/ software.html. It is highly recommended that you periodically check for and install the latest update. ❑ Controller configuration tool, such as RSLogix 5, RSLogix 500, or RSLogix 5000 software ❑ A computer connection to the ControlNet network via a communication card, such as 1784-PCC, 1784-KTCX, or 1770-KFC

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 17

Getting Started

Safety Precautions

1-5

Please read the following safety precautions carefully.

!

!

!

! !

! !

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove all power from the PowerFlex drive, and then verify power has been discharged before installing or removing an adapter. ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the product using an adapter. Failure to comply may result in injury and/or equipment damage. ATTENTION: Risk of equipment damage exists. The adapter contains electrostatic discharge (ESD) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, see Guarding Against Electrostatic Damage, publication 8000-4.5.2. ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting an adapter. ATTENTION: Risk of injury or equipment damage exists. Parameters 10 - [Comm Flt Action] and 11 - [Idle Flt Action] let you determine the action of the adapter and connected drive if communication is disrupted or the controller is idle. By default, these parameters fault the drive. You can set these parameters so that the drive continues to run, however, precautions should be taken to verify that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or a controller in idle state). ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing. ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example. There are many variables and requirements with any application. Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 18

1-6

Getting Started

Quick Start

This section is provided to help experienced users quickly start using the adapter. If you are unsure how to complete a step, refer to the referenced chapter. Step Action

See

1

Review the safety precautions for the adapter.

Throughout this manual

2

Verify that the PowerFlex drive is properly installed.

Drive User Manual

Install the adapter. b. Connect the adapter to the drive with the Internal Interface cable.

PowerFlex 7-Class DPI Network Communication Adapter Installation Instructions, publication 20COMM-IN004, and c. Use the captive screws to secure and ground the adapter to the drive.

Chapter 2, Installing the Adapter

3 a. Verify that the PowerFlex drive is not powered.

d. Connect the adapter to the network with a ControlNet cable. NOTE: When installing the adapter in either of the following products, see the listed publication for instructions: • DPI External Comms Kit - see the 20-XCOMM-DC-BASE Installation Instructions, publication 20COMM-IN001, supplied with the kit. • PowerFlex 750-Series drive - see the 20-750-20COMM and 20-750-20COMM-F1 Communication Carrier Cards Installation Instructions, publication 750COM-IN001, supplied with the card. 4

Apply power to the adapter. a. Verify that the adapter is installed correctly.

Chapter 2, Installing the Adapter

The adapter receives power from the drive. b. Apply power to the drive. The status indicators should be green. If they flash red, there is a problem. See Chapter 7, Troubleshooting. c. Configure and verify key drive parameters. 5

Configure the adapter for your application. Set adapter parameters for the following functions as required by your application:

Chapter 3, Configuring the Adapter

• Node address • I/O configuration • Master-Slave hierarchy • Fault actions 6

Configure the controller to communicate with the adapter. Use configuration tools, such as RSNetWorx for ControlNet software and RSLogix software, to configure the master on the network to recognize the adapter and drive.

7

Create a ladder logic program. Use a controller configuration tool, such as RSLogix software, to create a ladder logic program that enables you to do the following: • Control the connected drive, via the adapter, by using I/O. • Monitor or configure the drive using explicit messages.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Chapter 4, Configuring the I/O

Chapter 5, Using the I/O Chapter 6, Using Explicit Messaging