Installation Instructions - PHOTOSWITCH® Series 9000 On/Off and Timing Photoelectric Sensors All Sensors
Polarized Retroreflective
Retroreflective
Sensing Distance, Transmitted Beam ClearSightTM
Standard Diffuse
Long Range Diffuse
Extended Range Diffuse
1.2m (4ft)
1.5m (5ft)
3.0m (10ft)
4.2m (14ft)
Fiber Optic
Source 61m (200ft)
Receiver Depends on Light Source Selected
152m (500ft)
78mm(3in) Reflector
9.1m (30ft)
4.9m (16ft), - - 32mm(1.25in) Reflector
3.6m (12ft)
2m (6.5ft), - - 16mm(0.625in) Reflector
3m (10ft)
1m (3ft), - Transmitting LED
Visible Red 660nm
Infrared 880mn, Yellow: Power, Green: Output, and Red: Margin/SCP
Field of View
Visible Red 660nm
Infrared 880mn
Yellow: Power, Green: Output, and Red: Margin/SCP
1.5°
3.5°
6.5°
3.5°
1.5°
Depends on Fiber Optic Selected
Sensitivity Adjustment
Single Turn Potentiometer
Single‐Turn Potentiometer
Operating Temperature
-34°C to +70°C (-29°F to +158°F) Except models with solid state and relay output (see page 8).
-34°C to +70°C (-29°F to +158°F)
Relative Humidity
5% to 95%
5% to 95%
Housing/Lens Material
Valox®/Acrylic
Valox®/Acrylic
Operating Environment
Glass Infrared
Depends on Fiber Optic Selected, Infrared 880nm
Indicators
Plastic Visible Red
NEMA 3, 4X, 6P, 12, 13, IP67
NEMA 3, 4X, 6P, 12, 13, IP67
Approvals
UL listed, CSA certified, CE marked for all applicable directives
UL listed, CSA certified, CE marked for all applicable directives
Protections
All Versions: False Pulse, Solid State Output Versions: Short Circuit and Overload, DC Versions: Reverse Polarity
All Versions: False Pulse, Solid State Output Versions: Short Circuit and Overload, DC Versions: Reverse Polarity
Vibration
10-55 Hz, 1 mm amplitude, Meets or exceeds IEC 947-5-2
10-55 Hz, 1 mm amplitude, Meets or exceeds IEC 947-5-2
Shock
30G with 1 ms pulse duration, Meets or exceeds IEC 947-5-2
30G with 1 ms pulse duration, Meets or exceeds IEC 947-5-2
10-40V DC Sensors - NPN and PNP Catalog Number - 2m 300V cable
42G¡U-9200
42G¡C-9200
42G£P-9000
42GRP-9040
42GRP-9070
42GRL-9000
42GRL-9040
42G¡R-9000
42G¡F-9100
42G¡F-9000
Catalog Number - 4‐pin DC micro QD
42G¡U-9000-QD
42G¡U-9200-QD
42G¡C-9200-QD
42G£P-9000-QD
42GRP-9040-QD
42GRP-9070-QD
42GRL-9000-QD
42GRL-9040-QD
42G¡R-9000-QD
42G¡F-9100-QD
42G¡F-9000-QD
Catalog Number - 4‐pin mini QD
42G¡U-9000-QD1
42G¡U-9200-QD1
42G¡C-9200-QD1
42G£P-9000-QD1
42GRP-9040-QD1
42GRP-9070-QD1
42GRL-9002-QD
42GRL-9042-QD
42G¡R-9000-QD1
42G¡F-9100-QD1
Supply Current
30mA
50mA
15mA
Output Energized
Light/Dark Selectable
Light/dark selectable
Not applicable
Light/Dark Selectable
Load Current
250mA
250mA
Not applicable
250mA
Leakage Current
10A
10A
Not applicable
Power Consumption
4VA max
4VA max
Response Time
2ms ©
2ms ©
2ms ©
2ms ©
25mA
42G¡F-9000-QD1 30mA
10 4VA max
2ms
2ms
Not applicable
5ms
2ms
10-55V DC/20-40V AC Sensors - SPDT EM Relay Catalog Number - 2m 300V cable
42G¡U-9001
42G¡U-9201, 42G¡P-9001
42GRP-9041, - 42GRR-9001
42G¡F-9101
42G¡F-9001
Catalog Number - 5‐pin mini QD
42G¡U-9001-QD
42G¡U-9201-QD, 42G¡P-9001-QD
42GRP-9041-QD, - 42GRR-9001-QD
42G¡F-9101-QD
42G¡F-9001-QD
Supply Current
40mA, 40mA, 35mA
40mA
Output Energized
Light/Dark Selectable, Light/Dark Selectable
Not applicable
Light/Dark Selectable
Light/Dark Selectable
Load Current
2A/132V AC, 1A/264V AC, 1A/150V DC, 2A/132V AC, 1A/264V AC, 1A/150V DC, 2A/132V AC, 1A/264V AC, 1A/150V DC
Leakage Current
Not applicable, Not applicable, Power Consumption Response Time
2.2 watts/1.6VA max 15ms ¢, 15ms ¢, 2.2 watts/1.6VA max 15ms ¢
15ms
2A/132V AC, 1A/264V AC, 1A/150V DC Not applicable, - 3.0VA max, 23ms
15ms
70-264V DC/60-264V AC Sensors - SPDT EM Relay Catalog Number - 2m 300V cable
42G¡U-9002
42G¡U-9202
42G¡C-9202
42G¡P-9002
42GRP-9042
42GRP-9072, - 42G¡R-9002
42G¡F-9102
42G¡F-9002
Catalog Number - 5‐pin mini QD
42G¡U-9002-QD
42G¡U-9202-QD
42G¡C-9202-QD
42G¡P-9002-QD
42GRP-9042-QD
42GRP-9072-QD, - 42G¡R-9002-QD
42G¡F-9102-QD
42G¡F-9002-QD
Supply Current
15mA
15mA, Output Energized
Light/Dark Selectable
Light/Dark Selectable, Load Current
2A/132V AC, 1A/264V AC, 1A/150V DC
2A/132V AC, 1A/264V AC, 1A/150V DC
Leakage Current, Power Consumption
4 watts/4VA max
Response Time
15ms ¢
15ms ¢
15ms ¢
10mA, 2A/132V AC, 1A/264V AC, 1A/150V DC, 15ms ¢
4VA max, 15ms
15ms, 15mA Light/Dark Selectable
Not applicable 4VA max 23ms
15ms
70-264V AC/DC Sensors - Solid State Isolated N.O. Catalog Number - 2m 300V cable
42G¡U-9003
42G¡U-9203
42G¡C-9203
42G¡P-9003
42GRP-9043, - - 42GRR-9003
42G¡F-9103
42G¡F-9003
Catalog Number - 4‐pin mini QD
42G¡U-9003-QD
42G¡U-9203-QD
42G¡C-9203-QD
42G¡P-9003-QD
42GRP-9043-QD, - - 42GRR-9003-QD
42G¡F-9103-QD
42G¡F-9003-QD
Catalog Number - 4‐pin AC micro QD
42G¡U-9003-QD1
42G¡U-9203-QD1
42G¡C-9203-QD1
42G¡P-9003-QD1
42GRP-9043-QD1, - 42GRL-9043-QD1
42GRR-9003-QD1
42G¡F-9103-QD1
15mA
15mA
15mA Light/Dark Selectable
42G¡F-9003-QD1
Supply Current
15mA
Output Energized
Light/Dark Selectable
Not applicable
Light/Dark Selectable
Load Current
300mA
Not applicable
300mA
300mA
Leakage Current
1mA at 264V AC/DC
Not applicable
1mA at 264V AC/DC
1mA at 264V AC/DC
Power Consumption Response Time
4 watts/4VA max 2ms ©
2ms ©
2ms ©
2ms ©
2ms, 4VA max
4VA max
4VA max, - 15ms
2ms
¡ = “R” for On/Off or “T” for timer version; © = 5ms for timer versions; ¢ = 18ms for timer versions; £ = “L” for linear sense potentiometer, “S” for teachable version, “R” for nonlinear sense pot., or “T” for timer version. Transmitted Beam Source rated 10--264V AC/DC. Red: illuminates when margin ≤0.5x (no target) and ≥2.5x (target) 100mA for 42GSP and 9000 and 42GLP--9000 models.
1
Page 2
Wiring Diagrams All Models Except Transmitted Beam Source Cable Model: 9_ _0
4-pin DC Micro QD Model: 9_ _0--QD Brown White: NPN Black: PNP
Load
3
Load
3 Blue
( -- )
Cable Model: 9_ _3
1
(+)
White Black
Load
~
Blue
( -- )
(+)
4 White 1 Black
~
4 3
( -- )
AC/DC Micro QD Model: 9_ _3--QD1
3 Brown
2
Load
2 Blue
AC/DC Mini QD Model: 9_ _3--QD Brown
1
Load
1 Black: PNP
4
( -- )
(+)
4 White: NPN
2
Load
4 Black: PNP
Load
3 Brown
(+)
2 White: NPN
Blue
4-pin DC Mini QD Model: 9_ _0--QD1
1 Brown
(+)
Load
~
2 Blue
2 Red w/White
3 ( -- )
1
~
Load
3 Red
4
~
(+)
4 Green No Conn.
2
1 Red w/Black
( -- )
~
3
2
4
1
Load can be placed on either black or white wire to create sourcing or sinking respectively.
Cable Model: 9_ _1, 9_ _2
5-pin AC/DC Mini QD Model: 9_ _1--QD, 9_ _2--QD
Brown
(+)
Black (NO)
~
4 Brown
~
White (NC)
5 White (NC)
3
Orange (C)
3 Orange (C)
4
Blue
( -- )
~
2 Blue
Transmitted Beam Source Cable Model: 42GRL--90_ _
T
(+)
1 Black (NO)
Brown
Blue
( -- )
2
1 5
~
AC/DC Mini QD Model: 42GRL--90_2--QD (+)
( -- )
3 Brown
T
~
1 Black 4 White
~
2 Blue
DC Micro QD Model: 42GRL--90_0--QD (+)
~
Not Used
3
Not Used ( -- )
~
T
2 1 4
1 Brown 2 White 4 Black 3 Blue
(+)
~
Not Used
2 3
Not Used ( -- )
~
1 4
4-pin DC Micro QD Model: 42GRL--90_3--QD1
T
1 Red w/Black 4 Green 3 Red 2 Red w/White
(+)
~
Not Used
3
2
Not Used
4
1
( -- )
~
2
Page 3
Typical Response Curves Polarized Retroreflective
4
32mm (1.25) Reflector
2
0.6m (2ft)
1.5m (5ft)
3m (10ft)
15m (50ft)
150mm (6in)
Operating Distance
Operating Margin
42GRP-904X
254mm (10in)
2.5m (8.3ft)
4000
1000
1000
400
400
100 40
10
4
4
3m (10ft)
15m (50ft)
White Paper 216mm x 279.4mm (8.5 x 11)
4000
1.0mm (0.04I) Plastic Fiber Coiled
10 1.0mm (0.04I) Plastic Fiber
1 25.4mm 76.2mm (1.0in) (3.0in)
0.3m (12in)
0.6m (23in)
Operating Distance
1.5m (59in)
Operating Margin
2.3mm (0.09I) Glass Fiber
0.02 (0.5mm) Plastic Fiber Coiled
1.0mm (0.04in) Plastic Fiber 1.0mm (0.04in) Plastic Fiber‐Coiled 0.5mm (0.02in) Plastic Fiber
3.18mm (0.125) Glass Fiber
100 40
1.52mm (0.06) Glass Fiber
10 0.69m (0.027) Glass Fiber
4
2.5mm (0.1in)
25mm (1.0in)
150mm 0.3m (6.0in) (12in)
0.6m (24in) Operating Distance
1.0mm (0.04in) Plastic Fiber
1.0mm (0.04in) Plastic Fiber‐Coiled
100 40
0.5mm (0.02in) Plastic Fiber
10
0.5mm (0.06in) Plastic Fiber‐Coiled
1 2.54mm (0.1in)
25.4mm 76.2mm (1.0in) (3.0in)
0.3m 0.6m (12in) (24in)
2.5mm (0.1in)
25mm (1.0in)
0.3m 0.6m (12in) (24in)
Operating Distance
10000
10000
4000
4000 3.18mm (125) Glass Fiber 1.52mm (0.060) Glass Fiber
400
76mm (3.0in)
Infrared Fiber Optic Retroreflective
100 0.69mm (0.027) Glass Fiber 40
With 78mm (3) Reflector
1000 0.125 (3.18mm) Glass Fiber
400 100 40
10
10
4
4
1
1
6m (20ft)
400
4
1000
400
3m (10ft)
1.5mm (0.6in) Glass Fiber 1000
0.5mm (0.02in Plastic Fiber Bundle
Infrared Fiber Optic Transmitted Beam
1000
400
40
150m (500ft)
1.5m (5ft)
4000
Operating Distance
Infrared Fiber Optic Standard Diffuse 10000
100
30m (100ft)
0.6m (2ft)
10000
1 1.8m (5ft)
0.3m (1ft)
Visible Red Fiber Optic Transmitted Beam
2.3mm (0.09in)Glass Fiber
40
10
0.3m (1ft)
150mm (6in)
Operating Distance
White Paper 216mm X 279.4mm (8.5 x 11)
100
1
With 76mm (3) Reflector
51mm (2in)
2540mm (100in)
Visible Red Fiber Optic Standard Diffuse
Operating Distance
10000 0.5mm (0.02I) Plastic Fiber
254mm (10in) Operating Distance
10000
25.4m (83ft)
Visible Red Fiber Optic Retroreflective 4000
25.4mm (1in)
15m (50ft)
4000
Operating Distance
2.54mm (0.1in)
6m (20ft)
10000
1
1000
3m (10ft)
Operating Margin
42GRP-907X
25.4mm (1in)
1.5m (5ft)
Transmitted Beam, 61m (200ft), 152m (500ft) Light Source
1000
10
0.3m (1ft)
Operating Distance
Long Range Diffuse
100
1
1 51mm (2in)
Operating Margin
0.3m (1ft)
10 8 4
1 51mm (2in)
Operating Margin
92-90 Reflector
20
16mm (0.625) Reflector
2
1
Operating Margin
92-39 Reflector
Operating Margin
10 8 4
16 (0.625) Reflector
2
20
Operating Margin
32 (1.25) Reflector
White Paper, 216mm x 279.4mm (8.5 x 11)
40 76mm (3) Reflector
Operating Margin
Operating Margin
10 8
100 80
40
76 (3) Reflector
20
Standard Diffuse
10
Operating Margin
40
4
ClearSight Clear Object Detector
100 80
100 80
Operating Margin
Retroreflective
0.060 (1.52mm) Glass Fiber 0.027 (0.69mm) Glass Fiber
1 2.5mm (0.1in)
25mm (1.0in)
150mm 0.3m 0.6m (6.0in) (12in) (24in) Operating Distance
2.5mm (0.1in)
25mm (1.0in)
150mm 0.3m 0.6m (6.0in) (12in) (24in)
1.5m (59in)
Operating Distance
3
Page 4
Dimensions - mm (inches) All Cable Versions Except Fiber Optic
Fiber Optic
55.62 (2.190)
2.190 (55.62) 15.24 (0.600) 20.96 (0.825)
7.62 (0.300) 103.63 (4.080) Max. Travel
103.63 (4.080) Max. Travel
74.93 (2.950) Ref
74.93 (2.950) Ref 42.41 (1.670)
Cable Length 2m (6.5ft ) 6.5 (0.255/0.245) Dia.
M30 X 1.5 External Thread 1/2 NPSM Internal Thread
42.42 (1.670)
6.12 (0.241)
5.21 (0.205) X 8.13 (0.320) Slot, 2 PLCS
15.87 (0.625)
M30 X 1.5 External Thread 1/2 NPSM Internal Thread
5.46 (0.215) 24.69 (0.970)
16.76 (0.660) 32.66 (1.286)
41.91 (1.650)
40.00 (1.575)
20.96 (0.825)
7.62 (0.300)
15.87 (0.625)
Cable Length 2m (6.5ft) 6.47/6.22 6.25 (0.25) Dia.
16.76 (0.660)
5.46 (0.215) 24.64 (0.970) 30.35 (1.195)
32.66 (1.286)
41.91 (1.650)
40.00 (1.575)
30.35 (1.195)
5.21 (0.205) X 8.13 (0.320) Slot, 2 Plcs
Mounting Hole Centerline
Mounting Hole Centerline
ClearSight 9000 Versions
2.54 (0.10)
65.23 (2.568)
Cable Version
120
100.6 (3.96) Max. Travel
20.96 (0.825) 13.41 (0.528)
14.73 (0.580)
Top View 25.1 (0.99) 32.89 (1.295)
79.63 (3.135)
Cable Length 2m (6.5ft) 6.47/6.22 (0.255/0.245) Dia. M30 x 1.5 External Thread 1/2 NPSM Internal Thread
16.76 (0.660) 32.59 (1.283)
Connector Version
Micro Style
13.97 (0.550)
1/2-20 UNF 2 Keyways (AC) M12 x 1 1 Keyway (DC)
39.5 (1.55)
47.88 (1.885)
42.41 (1.670) 5.21 (0.205) x 8.13 (0.32) Slot, 2 Plcs.
68.07 (2.68)
5.46 (0.215) 15.87 (0.625)
} Centerline of Slots
24.64 (0.97) 30.35 (1.195)
41.91 (1.65)
Mini Style
17.78 (0.700)
7/8-16UN 1 Keyway
4
Page 5
Accessories - mm (inches)
Operational Notes
Swivel/Tilt Mounting Assembly #60--2439
Ambient Temperature Ratings 80 75
Ambient Temperature, _C
70
28.6 (1.13) 57.15 (2.25)
65 60 55 50 45
7.95 50.08 (0.31) (2.0)
40 60
Swivel/Tilt Mounting Assembly #60--2681 for ClearSight 9000 10_ Adjustment in each direction
110
160
210
260
Supply Voltage, V AC/DC
All models of the Series 9000 with the exception of those with the solid-state output (42Gxx--9xx3) and the EM-relay output (42Gxx--9xx2) have a maximum operating temperature of +70_C (+158_F). The maximum operating temperature of the 42Gxx--9xx3 and 42Gxx--9xx2 models can be determined from the graph shown above. That temperature is based on the supply voltage fed to the sensor. For example, if the operating voltage is 120V AC the maximum operating temperature would be +70_C (+158_F). An operating voltage of 220V AC would limit the ambient operating temperature to +55_C (+131_F). Operation of the sensor at ambient temperatures which exceed these limits could result in sensor failure.
Mounting and Wiring 28.6 (1.13) 87.0 (3.42)
Securely mount the sensor on a firm, stable surface or support. A mounting which is subject to excessive vibration or shifting may cause intermittent operation. Rockwell Automation offers a wide variety of fixed and adjustable mounting brackets as well as reflectors and quick disconnect cables. Refer to www.ab.com/sensors for further information on these products. The sensor is supplied with the hardware kit #129--130 which contains a plastic mounting nut, lock washer, 2 M5 x 0.8 x 53 screws and nuts. Once securely mounted, the sensor may be wired as indicated in the wiring diagrams.
7.95 50.08 (0.31) (2.0)
Vertical Height Adjustment Brackets #60--2721 = height 4 inches #60--2722 = height 6 inches
101.6 (4.0)
#60--2723 = height 8 inches
M5 x 0.8 x 53 Combination Screws and Nuts (Supplied)
#60--2724 = height 10 inches 22.2 (1.88)
139.7 152.4 (5.5) (6.0)
H
7.0 (0.275)
Hardware Kit (Supplied)
5
Page 6
Installing Fiber Optic Cables (42GxF--9xxx versions only)
42GRx - Top View Detail
1. Ensure that the fiber optic cable locking lever on the sensor is in the UNLOCKED position. 2. Insert the fiber optic cable until the internal clip mechanism is engaged. 3. Rotate the locking lever to the LOCK position. 4. Mount the fiber optic cable sensing tip end as appropriate.
Light/Dark Operate Switch
Sensitivity Adjustment UNLOCK
LED Status Indicators
1. Set lever to UNLOCK position.
2. Insert fibers.
The Series 9000 photoelectric sensor also contains a two-position selector switch. This switch is used to select either light- or dark-operate mode of the sensor. In light-operate mode, the sensor output will turn ON when light is being reflected back to it (reflector for retroreflective, source for transmitted beam, or target for diffuse). In dark-operate mode, the sensor output will turn OFF when no light is being reflected back to it. The table below describes the function of the three LED status indicators. Label
LOCK
Green
Margin
Red
Power
3. Rotate lever to LOCK position.
Wiring the Sensor The Series 9000 photoelectric sensor is available in one of three different connection types as identified on page 1. Rockwell Automation recommends the use of the 889 Series of cordsets and patchcords on the quick disconnect models. All external wiring should conform to the National Electrical Code and all applicable local codes.
Configuring the Sensor - All models except 42GSP--9000 Use the information below to align and configure the sensor.
User Interface Using an instrument screwdriver, open the top cover of the sensor to gain access to the user interface panel. This panel contains a single-turn sensitivity adjustment knob, a two-position mode selector switch, along with three LED status indicators. Using the same screwdriver, the sensitivity can be increased (clockwise) or decreased (counterclockwise) to meet the application requirements. The factory default setting for all versions is maximum sensitivity.
Color
Output
Yellow
State
Status
OFF
Output de-energized, SCP active
ON
Output energized
OFF
Margin < 2.5
ON
Margin >2.5
Flashing
Output SCP active
OFF
Sensor not powered
ON
Sensor powered
Sensor Alignment The red LED indicator is an alignment aid which indicates that a margin of 2.5X has been reached. This means that the sensor is receiving at least 2.5 times the signal strength back from the target needed to trigger an output signal. In general, it is desirable to have a higher margin to help overcome any deteriorating environmental conditions, i.e. dust buildup on the sensor’s lens. When aligning the sensor, the best performance can be obtained if this margin indicator is illuminated with the target in place. It is recommended to leave the sensitivity at its default maximum setting and change it only when necessary. Transmitted Beam Versions 1. Visually align the emitter and receiver units (emitter and receiver fibers) until the green output LED turns ON (with light-operate mode) or turns OFF (with dark-operate mode). 2. To be certain that the beam is centered, it is required to sweep the emitter or receiver in the horizontal and vertical plane and determine at what position the output indicator goes ON and then goes OFF. Set the sensor (or fiber optics) midway between both positions. The red margin LED should also be ON when the beam is unbroken.
CAUTION: Damage to single-turn sensitivity adjustment knob will occur if turned beyond min/max steps. After initial sensor configuration ensure that the user interface cover is closed tightly to maintain specified environmental ratings!
6
Page 7
Retroreflective and Polarized Retroreflective Versions 1. Visually align the sensor (or fiber optic cable) on the reflector until the green output LED turns ON (with light-operate mode) or turns OFF (with dark-operate mode). Also verify that the red margin LED is on. 2. To be certain that the beam is centered, it is required to sweep the sensor in the horizontal and vertical plane and determine at what position the output indicator goes ON and then goes OFF. Set the sensor (or fiber optics) midway between both positions. 3. Break the beam with the object to be detected and check if the output indicator turns ON (dark-operate mode). If this does not occur, turn down the sensitivity adjustment until it does. Restore the light beam by removing the object and check if the output indicator turns OFF again and that the red margin LED comes ON. If this does not occur, increase the size of the reflector or decrease the distance between the reflector and the sensor. Diffuse Mode 1. Visually align the sensor (or fiber optic cable) on the object until the green output LED turns ON (with light-operate mode) or turns OFF (dark-operate mode). 2. To be certain that the beam is centered, it is required to sweep the sensor in the horizontal and vertical plane and determine at what position the output indicator goes ON and then goes OFF. Set the sensor (or fiber optics) midway between both positions. 3. Remove the object in front of the sensor and eliminate any background signals by turning down the sensitivity adjustment, if such background signals exist. Replace the object and verify that the output LED goes ON and that the margin LED is ON. If the sensor continues to pick up background reflections it will be necessary to eliminate those reflections (i.e. paint with a nonreflective color) or to replace the sensor with a background suppression, sharp cutoff diffuse, or retroreflective sensing mode version. Configuring the Sensor - 42FSP- 9000 Models Use the information below to align and configure the sensor.
42GSP - Top View Detail Light/Dark Operate Pushbutton
Teach Button LED Status Indicators
Configuring the Sensor - 42GTx Models In addition to the switch and knob, some versions of the Series 9000 photoelectric sensor contain a four-bank DIP switch (S1...S4) and two rotary knobs (R2 and R3). These are used to configure internal ON, OFF, and ONE-SHOT time delays making it possible to provide some degree of local control in an application. Timing Sensors - Top View Detail Short/Long Off Delay
User Interface Using an instrument screwdriver, open the top cover of the sensor to gain access to the user interface panel. This panel contains two pushbuttons and three LED status indicators. The left pushbutton is used to put the sensor into teach mode while the righthand one is for light/dark operate selection.
Short/Long On Delay
One Shot/ Time Delay
With the sensor pointed at the light condition (target), momentarily press the Teach button until the RED indicator turns ON. After three seconds, this indicator will flash indicating it is ready to receive the dark condition (background). The RED indicator will momentarily remain steady, then turn OFF. This indicates that the teach operation was successful.
On Delay Adjustment
Red Margin/ SCP Indicator
Green Output Indicator
Light/Dark Operate
Teach Mode The teach mode of the 42GSP--9000 enables the sensor to learn both the light and dark conditions presented to it and to automatically adjust sensitivity to its optimal level for the application. This mode replaces the adjustment screw of a conventional photoelectric sensor.
The 42GSP--9000 photoelectric sensor also contains a two position pushbutton. This button is used to select either light or dark operate mode of the sensor. In light operate mode, the sensor output will turn ON when light is being reflected back to it (indicated by the output LED being ON). In dark operate mode, the sensor output will turn ON when no light is being reflected back to it.
Sensitivity Adjustment
Yellow Power Indicator S1 S2 S3 S4
Off Delay Adjustment
Note that these timers are nonretriggerable. The timing can be set for short (0–1.5 sec) or long (0–15 sec) duration using the DIP switches and adjusted via the two 15-turn rotary knobs. Use the illustration below to aid in configuring these timers.
The table below describes the function of the three LED status indicators. Label OUT SET/SCP
PWR/STAB
Color Yellow Red
Green
State
Status
OFF
Output de-energized
ON
Output energized
OFF
Normal operation
ON
Teach Mode Active present dark condition
Flashing
Teach Mode Active present light condition, Output SCP active
OFF
Sensor not powered
ON
Sensor powered
Flashing
Unstable margin condition
IMPORTANT:After initial sensor configuration ensure that the user interface cover is closed tightly to maintain specified environmental ratings! 42GRL Models PWR
9003
DEFAULT
Note that for the 9003 models, the switch must be pushed to the left towards “9003.” For all other models, the switch must be pushed to the right towards “Default.”
7
Page 8
Typical ON/OFF Timing Diffuse (Light Operate) Nonretriggerable
Typical One-Shot Timing Diffuse (Light Operate) Nonretriggerable
Target Target
T1 One-Shot ON/OFF
T2
Delayed One-Shot
Timing: OFF Delay
T1 is adjusted via the off delay potentiometer with either a long (0--15sec) or short (0--1.5sec) dip switch setting. T2 is adjusted via the on delay potentiometer with either a long (0--15sec) or short (0--1.5sec) dip switch setting. Timing: ON Delay
ON DELAY OFF DELAY
Publication PN--158404 DIR 10000321004 Ver 01 August 2014 Printed in USA
Timing: ON/OFF Delay
Application Example Product is coming down a conveyor, if the product is a white box, a kicker located 3 seconds down the conveyor is activated to push the box down another conveyor. The kicker should extend and retract for 1 second. The sensor is a 42GTP--9000. In this application an ON and OFF delay is required. Set the first DIP switch (S1) to TD position. Switch (S2) will be set to LT position. Switch (S3) will be set to L position for a 3 second delay. Switch (S4) will be set to the S position. The delay will be adjusted by turning the ON delay pot clockwise until the proper delay time is set. The OFF delay pot will be turned clockwise so to set the one second OFF delay.
Visit our web site at: http://www.ab.rockwellautomation.com PHOTOSWITCHR is a registered trademark of Allen-Bradley Company. ValoxR is a registered trademark of General Electric Company.
8