Page 88

Chapter

7

Communication Commands This chapter contains the format you should use when sending communication commands to Allen-Bradley processors. Use this key to help learn the conventions that depict the communication commands listed in this chapter: command command name This text describes how the command is used.

• PLC-3 processors that can use the command command format reply format

C command code function code

CMD

FNC command description data varies up to a maximum number of bytes

R

CMD each block represents one byte Unless otherwise stated, values are shown in hexadecimal.

"

Message packets The message packets for these commands include STS and possibly EXT STS fields that contain status and error code information. For more information on these bytes, see Chapter 8, “Message Packet Status Codes (STS, EXT STS).” Protecting data files from write access Using a PLC-5/11, -5/20, 5/30, -5/40, -5/60, or -5/80 processor, you can also specify privileges to protect data files from write access on a DH+ link. Using an SLC 5/02, 5/03, or 5/04 processor, you can specify static file protection to protect data files from write access from any of the communication channels. Important:

In some cases, switch settings on an interface module can disable a command at a PLC/SLC node. For additional information on your module’s switch settings, refer to that module’s user documentation. (For a list of related publications and products, refer to the preface of this manual.)

In addition to the commands listed in this chapter, we’ve also included examples: Section

Page

PLC-5 Type/Data Parameter Examples

7-36

SLC 500 Information

7-38

Reading and Writing SLC 500 Data (using SLC terminology)

7-38

Reading and Writing SLC 500 Data (using PLC-2 terminology)

7-38

Publication 1770-6.5.16 - October 1996

Page 89

7–2

Communication Commands

Use this table to locate commands you want to use. For additional information on the commands, refer to the specified pages. ATTENTION: Using command codes not listed will produce unpredictable results.

! Command

CMD

FNC

Processors Micro- Logix 1000 apply port configuration

0F

8F bit write

0F

02

0F

3A

0F

80 close file

0F

82 diagnostic status

06

03 disable forces

0F

41 disable outputs

07

00 download all request

0F

50 download completed

0F

52 download request

0F

05 echo

06

00 enable outputs

07

01 enable PLC scanning

07

03 enter download mode

07

04 enter upload mode

07

06 exit download/upload mode

07

05 file read

0F

04 file write

0F

03 get edit resource

0F

11 initialize memory

0F

57 modify PLC-2 compatibility file

0F

5E open file

0F

81

04

Â

0F

09 physical write

0F

08 protected bit write

02

 protected typed file read

0F

A7 change mode physical read

4 4 4 4

SLC 500

4 4 4 4

SLC 5/03

SLC 5/04

4

4 4 4 4 4

4

4

4

4

4

4

4

4 4

PLC-2

PLC-3

PLC-5 /250

4➄

4

4

4

4

4

7-4 7-4

4 4

7-5

4

4

4

4

4 4 4

4 4➄

4 4➄

4 4

4 4➄

4

4

4

4

4

7-6 7-6

4

4 4

➄

4 4

7-7 7-7 7-8 7-8

➄

7-9 7-9

4 4 4

4 4 4

7-6

➄

7-9 7-10 7-10

4 4

4 4➄

4 4 4➄ 4➄

4 4

PLC-5/ VME

7-5

7-10 7-11

4

7-11 7-12 7-12 7-13

4 4

4 4

À

This command cannot be executed by channel 0 of a PLC-5/11, -5/20, -5/30, -5/40, -5/60, or -5/80 processor.

Á

The following processors can initiate these commands but cannot respond to them: Processor Series/Revision Processors: Series A / revision M PLC-5/40, -5/40L, -5/60, -5/60L Series A / revision J PLC-5/30 Series A / revision H PLC-5/11, -5/20 Series B / revision J PLC-5/40, -5/40L, -5/60, -5/60L Series C / revision G PLC-5/11, -5/20, -5/20E, -5/30, -5/40, -5/40L, -5/V40, -5V40L, -5/60, -5/60L, -5/80, -5/80E, -5/V80

Â

This command has no FNC byte.

Ã

SLC 500 refers to any SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, or SLC 5/04 processor.

➄

Receive only. Processors with this note cannot send the command; they receive the command from a computer.

Publication 1770-6.5.16 - October 1996

PLC-5

7-5

4 4 4 4

4

4

1774- PLC

Page

7-13

4 4 4

7-13 7-14

4

4

7-15 7-16

Page 90

Communication Commands

Command

CMD

FNC

Processors Micro- Logix 1000 protected typed file write protected typed logical read with three address fields protected typed logical write with three address fields

7–3

SLC 500Ã

SLC 5/03

SLC 5/04

1774- PLC

PLC-2

Page PLC-3

PLC-5

PLC-5 /250

PLC-5/ VME

0F

AF

4

4

4

4

0F

A2

4

4

4

4

4

7-17

0F

AA

4

4

4

4

4Á

7-18 protected write

00

 read bytes physical

0F

17 read diagnostic counters

06

01 reset diagnostic counters

06

07 read link parameters

06

09 read-modify-write

0F

26 read-modify-write N

0F

79 read section size

0F

29 restart request

0F

0A return edit resource

0F

12 set CPU mode

0F

3A set data table size

06

08 set ENQs

06

06 set link parameters

06

0A set NAKs

06

05 set timeout

06

04 set variables

06

02 shutdown

0F

07 typed read

0F

68 typed write

0F

67 unprotected bit write

05

 unprotected read

01

 unprotected write

08

 upload all request (upload)

0F

53 upload completed

0F

55 upload

0F

06 word range read

0F

01 word range write

0F

00 write bytes physical

0F

18

7-16

4 4 4 4

4 4 4

4 4 4

4 4 4

4 4

4 4 4

4 4 4

4

4

4 4

4

4 4

4

4 4

4

4 4

4 4

4 4

4 4

7-19

4➄ 4➄ 4➄

4

7-19 7-19 7-22 7-20

4 4

4

4 4 4 4

4

4 4➄ 4➄ ➄

4

7-20 7-21 7-22 7-23

4

4➄

4

4➀

4➄

4 4 4 4

4 4➀ 4➀

4 4➄ 4➄

4 4 4 4 4 4 4

4 4 4 4 4 4➄ 4➄

4 4 4

4 4 4➄

4

7-24 7-26 7-24 7-25 7-25

4 4 4

4 4 4

4 4 4

À

This command cannot be executed by channel 0 of a PLC-5/11, -5/20, -5/30, -5/40, -5/60, or -5/80 processor.

Á

The following processors can initiate these commands but cannot respond to them: Processor Series/Revision Processors: Series A / revision M PLC-5/40, -5/40L, -5/60, -5/60L Series A / revision J PLC-5/30 Series A / revision H PLC-5/11, -5/20 Series B / revision J PLC-5/40, -5/40L, -5/60, -5/60L Series C / revision G PLC-5/11, -5/20, -5/20E, -5/30, -5/40, -5/40L, -5/V40, -5V40L, -5/60, -5/60L, -5/80, -5/80E, -5/V80

Â

This command has no FNC byte.

Ã

SLC 500 refers to any SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, or SLC 5/04 processor.

➄

Receive only. Processors with this note cannot send the command; they receive the command from a computer.

4 4 4 4 4 4

➀

7-25

➄

7-27 7-27 7-28

4 4

7-28 7-30 7-30 7-31 7-32

4 4

7-33 7-34 7-34 7-34 7-35

4

7-35

Publication 1770-6.5.16 - October 1996

Page 91

7–4

Communication Commands apply port configuration Changes the configuration of some or all ports. If there are no parameters, changes all ports. This command reconfigures the ports based on information in the processor’s physical memory. It is normally used as part of a physical download operation where the processor memory and configuration are to be fully restored. A programming device must have the edit resource to use this command.

• PLC-5 • PLC-5/VME • SLC 5/03 • SLC 5/04

C

DST PSN SRC PSN CMD STS 0F

R

LNH LNH CMD DST PSN SRC PSN STS HI LO 4FH

TNS

FNC 8F

A

TNS

B EXT Data STS

A - number of ports to change is a one-byte field 00 means ports." B - port numbers in this list are two bytes each, low byte first. Data - returned only if there is an EXT STS error 12H. It contains the file and element that relate to the error. LNH - length of the optional portion of the reply packet in bytes.

"

First four words of apply port configuration The first four words are currently unused and unexamined. To assure compatibility with any future use of these bytes, they should be initialized to 0. DST, PSN, and SRC are included for reference only.

bit write (write bit) Modifies the bits at the address specified by either a word symbol, a file symbol plus a word offset, or a logical address. This address must point to a word within a file. The function code is 2. Unlike unprotected writes and protected bit writes, this command can change the bits in a single word only.

• PLC-3 • PLC-5 (receive only) • PLC-5/250

C

DST SRC

CMD 0F STS

TNS

FNC 02

R

SRC DST

CMD 4F STS

TNS

EXT STS

PLC-3 Logical Address (2 - 51 bytes.)

Set Mask

The EXT STS field may be attached to the reply packet only when there is an error.

Publication 1770-6.5.16 - October 1996

Reset Mask

Page 92

Communication Commands

7–5 change mode MicroLogix 1000 Changes the mode of the MicroLogix processor.

• MicroLogix 1000 • SLC 500 • SLC 5/03 • SLC 5/04

C

DST SRC

CMD STS 0F

TNS

FNC Mode 3A xxh

R

SRC DST

CMD STS 4F

TNS

EXT STS

Mode - 01 = change to Program mode (REM program) 02 = change to Run mode The EXT STS field may be attached to the reply packet only when there is an error.

SLC 500 Changes the mode of the SLC processor. For an SLC 5/03 or SLC 5/04 processor, change mode only works when the keyswitch is in the REM position. C

DST SRC

CMD STS 0F

TNS

FNC Mode 80 xxh

R

SRC DST

CMD STS 4F

TNS

EXT STS

Mode - 01 = change to PROGRAM mode (REM program) 06 = change to RUN mode (REM Run) 07 = change to TEST-Cont. Scan Mode (REM Test) 08 = change to TEST-Single Scan Mode (REM Test) 09 = change to TEST-Debug Single Step (REM Test). SLC 500 and SLC 5/01 processors do not support 09 mode The EXT STS field may be attached to the reply packet only when there is an error.

close file

• SLC 500 • SLC 5/03 • SLC 5/04

Closes a file in an SLC 500 processor. When closing program file 0 (in an SLC 500, SLC 5/01, or SLC 5/02 processor) after it has been opened for write, the SLC processor calculates the LRC for the directory, data and internal files. C

DST SRC CMD STS 0F

R

SRC DST

TNS

FNC 82

Tag

CMD EXT 4F STS STS

The EXT STS field may be attached to the reply packet if there is an error.

Publication 1770-6.5.16 - October 1996

Page 93

7–6

Communication Commands diagnostic status Reads a block of status information from an interface module. The reply contains the status information in its DATA field. The status information varies with the type of interface module. (For additional information, see Chapter 10, “Diagnostic Status Information.”) • 1774-PLC • MicroLogix 1000 • PLC-2 • PLC-3 • PLC-5 • PLC-5/250 (receive only) • SLC 500 • SLC 5/03 • SLC 5/04

C

DST SRC CMD STS 06

TNS

FNC 03

R

SRC DST CMD STS 46

TNS

Data (max. 244 bytes)

disable forces Disables the forcing function for I/O. All forcing data is ignored, but remains intact.

• MicroLogix 1000 • PLC-5 • PLC-5/250 (receive only) • SLC 500 • SLC 5/03 • SLC 5/04

C

DST SRC CMD STS 0F

TNS

FNC 41

R

SRC DST CMD STS 4F

TNS

EXT STS disable outputs • 1774-PLC

Publication 1770-6.5.16 - October 1996

Turns off all of the 1774-PLC processor’s outputs. Use this command to disable the outputs before sending a physical write. C

DST SRC CMD STS 07

TNS

R

SRC DST CMD STS 47

TNS

FNC 00

Page 94

Communication Commands

7–7 download all request (download)

• PLC-5 • PLC-5/250 (receive only) • PLC-5/VME

Places a PLC-5 processor in Download mode before downloading a complete system. A “no privilege” error is returned if the requestor does not have privilege to place the processor in Download mode. This error occurs when: • the processor is in Run or Remote Run mode (must be in Program or Remote Program mode) • the processor is being edited • some other node is already downloading to the processor C

DST SRC CMD STS 0F

TNS

FNC 50

R

SRC DST

CMD STS 4F

TNS

EXT STS

The EXT STS field may be attached to the reply packet only when there is an error.

download completed Use after downloading a complete system to place the processor back in the mode that it was in. (For PLC-5 processors, it returns to the mode it was in prior to executing download all request.) • PLC-5 • PLC-5/250 (receive only) • PLC-5/VME • SLC 500 • SLC 5/03 • SLC 5/04

C

DST SRC CMD STS 0F

TNS

FNC 52

R

SRC DST

CMD STS 4F

TNS

EXT STS

The EXT STS field may be attached to the reply packet only when there is an error.

Publication 1770-6.5.16 - October 1996

Page 95

7–8

Communication Commands download request (download privilege)

• PLC-3

Used by a computer to inform an interface module that it wants to perform a download. If the module grants the download privilege, the computer may begin issuing physical reads or physical writes. If another node already has the download privilege, the second node is denied the privilege. Before performing an upload/download, issue diagnostic status to get the last word of memory to read or write. Bytes 11-14 in the diagnostic status reply return E60.0.0 - this is the start of unused memory. Start your read or write at 00 00 00 00. C

DST SRC

CMD STS 0F

TNS

FNC 05

R

SRC DST

CMD STS 4F

TNS

EXT STS

The EXT STS field may be attached to the reply packet only when there is an error.

echo Checks the integrity of transmissions over the communication link. The command message transmits up to 243 bytes of data to a node interface module. The receiving module should reply to this command by transmitting the same data back to the originating node. • 1774-PLC • MicroLogix 1000 • PLC-2 • PLC-3 • PLC-5 • PLC-5/250 (receive only) • SLC 500 • SLC 5/03 • SLC 5/04

Publication 1770-6.5.16 - October 1996

C

DST SRC CMD STS 06

TNS

FNC 00

R

SRC DST CMD STS 46

TNS

Data (max. 243 bytes)

Data (max. 243 bytes)

For SLC 500, SLC 5/01, and SLC 5/02 processors, maximum data size is 95 bytes; for SLC 5/03 and SLC 5/04 processors, maximum data size is 236 bytes.

Page 96

Communication Commands

7–9 enable outputs • 1774-PLC

Returns control of the outputs to the 1774-PLC ladder diagram program. Use this command to cancel the effect of disable outputs. C

DST SRC CMD STS 07

TNS

R

SRC DST CMD STS 47

TNS

FNC 01 enable PLC scanning Restarts the 1774-PLC processor’s program scanner after a physical write has been performed.

• 1774-PLC

C

DST SRC CMD STS 07

TNS

R

SRC DST CMD STS 47

TNS

FNC 03 enter download mode Puts the PLC-2 processor in the download mode. Use this command on a PLC-2 node before sending a physical write to the node. • PLC-2

C

DST SRC CMD STS 07

TNS

R

SRC DST

CMD STS 47

TNS

Important:

FNC 04

For early revisions of the 1771-KA2 and the industrial terminal, when you send an enter download/upload mode, the industrial terminal port is disabled until you send an exit download/upload mode. When the industrial terminal port is disabled, the industrial terminal enters the mode select state. To leave this state, you must manually select a mode at the industrial terminal.

If you are using

Use

•1771-KA/A revision F •1771-KG/A enter download mode before sending physical read commands.

•1771-KA2/B •1771-KG/B or later enter upload mode before sending physical read commands.

Publication 1770-6.5.16 - October 1996

Page 97

7–10

Communication Commands enter upload mode Puts the PLC-2 processor in Upload mode. Use this command on a PLC-2 node before sending a physical read to the node. • PLC-2

C

DST SRC CMD STS 07

TNS

R

SRC DST CMD STS 47

TNS

Important:

FNC 06

When you send an enter upload mode, the industrial terminal port is disabled until you send an exit download/upload mode.

exit download/upload mode Takes the PLC-2 processor out of the Upload or Download mode. Use this command to restart the PLC-2 processor after performing an upload or download operation.

• PLC-2

Important:

Do not send this command after a download/upload command; you must recycle power to the 1771-KA, -KA2, -KG, or 1785-KA3 module to enable industrial terminal communication.

C

DST SRC CMD STS 07

TNS

R

SRC DST CMD STS 47

TNS

FNC 05

You must remove the temporary End statement from the beginning of the program and re-insert the first byte of the program.

file read (read file) Reads data, starting at a file symbol or a block address. This starting address must point to a file of words. • PLC-3 • PLC-5/250

C

DST SRC

CMD 0F STS

TNS

FNC 04

R

SRC DST

CMD 4F STS

TNS

Data - max. 244 bytes or 122 words)

Packet Offset

Total Trans

The DATA field may be replaced by an EXT STS field if there is an error.

Publication 1770-6.5.16 - October 1996

Logical Address (2 - 51 bytes.)

Size