Page 172
Chapter
10
Diagnostic Status Information In chapter 8, we showed you the diagnostic status message packet format. When you send diagnostic status to a node, the node returns bytes of data. Use this chapter to interpret the data returned from the node (DH, DH+, or DH485 interface) that received the diagnostic status. It contains these sections: Section
Page
1747 Cat. Nos.
10-2
1761, 1770, and 1771 Cat. Nos.
10-5
1773, 1775, and 1779 Cat. Nos.
10-11
1784 Cat. Nos.
10-15
1785 Cat. Nos.
10-16
5130 Cat. Nos.
10-23
Important:
The values shown in the following tables are in hexadecimal format. (For more on the hexadecimal numbering system, refer to Chapter 11, “Data Encoding.”)
Publication 1770-6.5.16 - October 1996
Page 173
10–2
Diagnostic Status Information
1747 Cat. Nos.
For status information from these cat. nos.
See page
1747-KE
10-2
1747-L20, -L30, -L40, -L511, -L514, -L524 (SLC 500, SLC 5/01 and SLC 5/02 processors)
10-3
1747-L532, -L542 (SLC 5/03 and SLC 5/04 processors)
10-4
1747-KE Status Bytes Bytes
Bits
Contents
Description
1 2 3 4 5
1 2 3 4 0-4 5-7 all all
Mode/Status Type Extender Extended Interface Type Not used Series/Revision
00 (no modes) FE 2C 00 = 0 release1; = 1 release 2, etc. = 0 series A; = 1 series B, etc. 1770-KF3 00
6 - 16 17 - 24
Publication 1770-6.5.16 - October 1996
Bulletin Number/Name (in ASCII) Product Specific Information
Page 174
Diagnostic Status Information
10–3
1747-L20, -L30, -L40, -L511, -L514, -L524 (SLC 500, SLC 5/01 and SLC 5/02 processors) Status Bytes Bytes
Bits
Contents
Description
1 2 3 4
0-7 0-7 0-7 0-7 mode/status type extender extended interface type extended processor type
5
0-4 series/revision
00 EE 1F 1A = 20, 30, & 40 I/O SLC fixed controllers 18 = 1747-L511, -L514 SLC 5/01 controller 25 = 1747-L524 and SLC 5/02 controller = 0 (firmware release1) = 1 (firmware release 2), etc. = 0 (series A) = 1 (series B), etc. 500 - 20 = 1747-L20 (SLC 500 fixed controller) 500 - 30 = 1747-L30 (SLC 500 fixed controller) 500 - 40 = 1747-L40 (SLC 500 fixed controller) 5/01 = 1747-L511 & -L514 5/02 = 1747-L524
5-7 6 - 16 all bulletin number/name (in ASCII)
Product-specific Information 17 all major error word 18 all major error word 0-4 19 processor mode status/control word
20
21 22 23 24
5 6 7 0 1 2 3 4 5 6 7 0-7 0-7 0-7 0 1 2-7 processor mode status/control word (high byte)
program ID processor RAM size (in Kbytes) directory file corrupted not used program owner node address low byte high byte 0 = download 1 = program 2 = reserved 3 = idle due to SUS instruction 4 = reserved 5 = reserved 6 = run 7 = test continuous scan 8 = test single scan 9-31 = reserved forces active forces installed communication active protection power loss startup protect fault➀ load memory module on error load memory module always➀ load memory module and run➀ major error - processor halted locked➀ first pass bit➀ low byte high byte
=0 = 00 - 1F: program owner node address = 3F: no program owner
➀ SLC 5/02 processors only.
Publication 1770-6.5.16 - October 1996
Page 175
10–4
Diagnostic Status Information
1747-L532, -L541, -L542, -L543 (SLC 5/03 and SLC 5/04 processors) Status Bytes Bytes
Bits
Contents
Description
2 3
0-5 6 7 0-7 0-7 mode/status
00 testing edits edits in processor EE
4
0-7 extended processor type
5
0-4 series/revision
1 type extender extended interface type
5-7 6 - 16 bulletin number/name (in ASCII) Product-specific Information 17 all major error word 18 all major error word 19 processor mode 0-4 status/control word
20
21 22 23 all
5 6 7 0 1 2 3 4 5 6 7 0-7 0-7 0-7
Publication 1770-6.5.16 - October 1996 processor mode status/control word (high byte)
program ID processor RAM size (in Kbytes)
20 = DH485 on port 0 (RS-232)➀ 31 = DH+ on port 1 via domino plug➁ 34 = DF1 full-duplex protocol on port 0 36 = DF1 half-duplex protocol on port 0 49 = rack type 1747-L534➀ 5B = rack type 1747-L534➁ = 0 firmware release1 = 1 firmware release 2, etc. = 0 series A = 1 series B, etc. 5/03 = 1747-L532 5/04 = 1747-L542 low byte high byte 00000 = download 00001 = remote PROG 00011 = idle due to SUS instruction 00110 = remote RUN 00111 = remote TEST; continuous scan 01000 = remote TEST; single scan 01001 = remote TEST; continuous step 10000 = download 10001 = PROG 11011 = idle due to SUS instruction 11110 = RUN forces active forces installed communication active protection power loss startup protect fault load memory module on error load memory module always load memory module and run major error - processor halted locked first pass bit low byte high byte
Page 176
Diagnostic Status Information
Bytes
Bits
Contents
24
0 directory file corrupted
1 2-7 not used program owner node address
10–5
Description
=0 = 00-1F for nodes 0 through 31 = 3E for nodes 20 through FF = 3F: no program owner
➀ SLC 5/03 processors only. ➁ SLC 5/04 processors only.
1761, 1770, and 1771 Cat. Nos.
For status information from these cat. nos.
See page
1761-L16AWA, -L16BBB, -L16BWB, -L32AWA, -L32BWA, -L32BWB (MicroLogix 1000 processors)
10-6
1770-KF3
10-7
1771-KA, -KA2, -KC/KD, -KE/KF, -KG, -KGM, 1770-KF2 and 1774-KA
10-7
Publication 1770-6.5.16 - October 1996
Page 177
10–6
Diagnostic Status Information
1761-L16AWA, -L16BBB, -L16BWB, -L32AWA, -L32BWA, -L32BWB (MicroLogix 1000 processors) Status Bytes Bytes 1 2 3
Bits 0-7 0-7 0-7
Contents mode/status type extender extended interface type
4 5
0-7 0-4 extended processor type series/revision
5-7 6 - 16 bulletin number/name (in ASCII) Product-specific Information 17 all major error word 18 all major error word 19 processor mode 0-4 status/control word
20
21 22 23 24
Description 00 EE 34 = DF1 full-duplex protocol on port 0 20 = DH485 58 = 0 firmware release1 = 1 firmware release 2, etc. = 0 series A = 1 series B, etc.
all
5 6 7 0 1 2 3 4 5 6 7 0-7 0-7 0-7 0 1 2-7
Publication 1770-6.5.16 - October 1996 processor mode status/control word (high byte)
program ID processor RAM size (in Kbytes) directory file corrupted not used program owner node address low byte high byte 00000 = download 00001 = remote PROG 00011 = idle due to SUS instruction 00110 = RUN 00111 = TEST; continuous scan 01000 = TEST; single scan forces active forces installed communication active fault override startup protect fault reserved reserved always run major error - processor halted locked first pass bit low byte high byte 8 =0 = 3F; no program owner
Page 178
Diagnostic Status Information
10–7
1770-KF3 Status Bytes Bytes
Bits
Contents
Description
1 2 3 4 5
1 2 3 4 0-4 5-7 all all
Mode/Status Type Extender Extended Interface Type Not used Series/Revision
00 (no modes) FE 2C 00 = 0 release1; = 1 release 2, etc. = 0 series A; = 1 series B, etc. 1770-KF3 00
6 - 16 17 - 24
Bulletin Number/Name (in ASCII) Product Specific Information
1771-KA2, -KA, -KC/KD, -KE, -KF, -KG, -KGM, 1770-KF2 Status Bytes Bytes
Bits
Contents
Description
1
0-2
Operating status of PLC processor
For the 1770-KF2, this byte is always 0. For other modules: 0 = Program load mode 1 = Test mode 2 = Run mode 3 = (not used) 4 = Remote Program load 5 = Remote test 0 = normal communication; 1 = No communication with PLC processor 0 = Normal; 1 = Download or upload mode 0 = Normal; 1 = Format error in communication zone of PLC program always zero 0 = 1771-KC,-KD module 1 = 1771-KA2 or (1771-KA) module 2 = 1771-KA4 module 3 = 1771-KE,-KF or 1770-KF2 module 4 = 1771-KG module 5 = 1771-KGM module
3 4 5
2
6-7 0-3
Type of interface module and processor
4-7
0 = PLC processor 1 = PLC-2 processor 2 = PLC-2/20 (LP1) Processor 3 = Mini-PLC-2 processor 5 = PLC-2/20 (LP2) processor 6 = PLC-2/02, 2/15,-2/16, or -2/17 processor 7 = PLC-2/30 processor F = computer
3-4 all
5-6 all
Octal address of the start of the PLC program. For the 1770-KF2, these bytes are always 0. Memory size
7-8 all
Diagnostic address
The ladder logic starts at the end of the data table. To find the physical end of PLC-2 memory, look for FFFF after the address in bytes 3 and 4. The FFFF must appear at a 1/2 Kbyte junction. Size of memory (in number of bytes) for 1774-PLC processor; zero for all other processors. Starting byte address of diagnostic counters and timers.
Publication 1770-6.5.16 - October 1996
Page 179
10–8
Diagnostic Status Information
Bytes 9
Bits
Contents
Description
0-4
Series and revision level of interface module. 1770-KF2/A identifies itself as Series in byte 9, bits 5 to 7. Series B 1770-KF2 identifies itself as Series E, and so on. 1771-KA identifies itself as a Series A. 1771-KA2 Series A identifies itself as a Series B, and so on. Settings of the option switches on the node interface module.
0 = Revision A 1 = Revision B, etc.
5-7
10121
0-7
0-1
2
3 4 5 6 7
0 1 2 3 4 5-7
Publication 1770-6.5.16 - October 1996
0 = Series A 1 = Series B, etc.
This byte is not used in replies by 1771-KC/KD or -KE/KF modules. For the other modules, the bits of this byte are defined as follows. 1771-KA and 1771-KA2 modules 1771-KA2 status information is opposite of 1771-KA, as noted. 0 = 57,600 bits per second baud rate for DH link (undefined for 1771-KA2) 1 = Undefined 2 = Undefined 3 = Undefined (57,600 for 1771-KA2) 0 = All other PLC-2 Family processors (PLC-2 processor for 1771-KA2) 1 = PLC-2 processor (all other PLC-2 processors for 1771-KA2) 0 = Protected commands enabled (disabled for 1771-KA2) 1 = Protected commands disabled (enabled for 1771-KA2) 0 = Unprotected commands enabled (disabled for 1771-KA2) 1 = Unprotected commands disabled (enabled for 1771-KA2) not used 0 = Physical writes enabled (disabled for 1771-KA2) 1 = Physical writes disabled (enabled for 1771-KA2) 0 = Transmission unprotected commands enabled (disabled for 1771-KA2) 1 = Transmission unprotected commands disabled (enabled for 1771-KA2) 1771-KG Module (Series A) 0 = Full-duplex protocol; 1 = Half-duplex protocol 0 = Physical writes disabled; 1 = Physical writes enabled 0 = Unprotected commands disabled; 1 = Unprotected commands enabled 0 = Embedded responses disabled; 1 = Embedded responses enabled 0 = No parity; 1 = Even parity Asynchronous link baud rate 0 = 110 bps 1 = 300 bps 2 = 600 bps 3 = 1200 bps 4 = 2400 bps 5 = 4800 bps 6 = 9600 bps 7 = 19200 bps
Page 180
Diagnostic Status Information
Bytes
Bits 1 2 4, 3, 0
5-7
Contents
10–9
Description 1771-KG Module (Series B) 0 = second module; 1 = first module 0 = accept physical/unprotected reads and writes disabled 1 = accept physical/unprotected reads and writes enabled Binary values: Value Parity Error Embedded Protocol Check Responses 000 none BCC disabled full-duplex 100 even BCC disabled full-duplex 010 none BCC enabled full-duplex 110 even BCC enabled full-duplex 001 none BCC disabled half-duple x 101 even BCC disabled half-duple x 011 none CRC enabled full-duplex 111 none CRC disabled half-duple x Asynchronous link baud rate: 0 = 110 bps 1 = 300 bps 2 = 600 bps 3 = 1200 bps 4 = 2400 bps 5 = 4800 bps 6 = 9600 bps 7 = 19200 bps
Publication 1770-6.5.16 - October 1996