The text of a manual · part 23 of 31
DF1 Protocol and Command Set Reference Manual: 10 - Diagnostic Status Information, pages 190 to 196
Pages 190 to 196 of 251, from DF1 Protocol and Command Set Reference Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 5250-LP and Allen-Bradley 5250-MLP1
Page 190
Diagnostic Status Information
10–19
1785-KE Status Bytes Bytes
Bits
Contents
Description
1 2
Operating status of PLC processor. Type of interface module and processor
3 4 5-6 all 0-3 4-7 all all all
For the 1785-KE, this byte is always 0. E = Check interface module expansion byte (byte3) F = Computer 19 = 1785-KE 00 = not used low byte first.
7-8 9 all 0-4
Interface Module Expansion Byte This is a pointer to the Active Node Table This is a pointer to diagnostic counters Series and revision level of the module
5-7 10
0-1 2 3-7
Settings of the option switched on the module low byte first. 0 = Revision A 1 = Revision B, etc. 0 = Series A 1 = Series B, etc. 0 = 57,600 bits per second Data Highway Plus baud rate DSR Option Switch Settings; bit set to 0 is ON
Publication 1770-6.5.16 - October 1996
Page 191
10–20
Diagnostic Status Information
1785-LT (PLC-5/15) and 6008-LTV (PLC-5 VME) Status Bytes Bytes
Bits
Contents
Description
1
0-2
Operating status of PLC-5 processor
0 = Program load 1 = Not used 2 = Run mode 3 = Not used 4 = Remote program load 5 = Remote test 6 = Remote run 7 = Not used
3 4 5 6 7 2
3-6 7
0-3 4-7
0-4
Processor Type
Size of user memory Series and revision of the PLC-5
5-7 8 9 all all
Processor number on DH+ link I/O address
10
0 1 2 5 6 all all 0 4 all all
I/O and communication parameters
11 - 12 13 -14 15 16 17
Publication 1770-6.5.16 - October 1996
Number of data table files Number of program type files Forcing status Memory protect indication Bad RAM indication
0 = Normal 1 = Major processor fault 0 = Normal 1 = Download mode Not used 0 = Not testing edits 1 = Testing edits 0 = No edits in processor 1 = edits in processor B = PLC-5 B = 1785-LT (PLC-5/15) C = 6008-LTV (PLC-5 VME) low word first, low byte first 0 = Revision A 1 = Revision B, etc. 0 = Series A 1 = Series B, etc. Address of the processor if it is an adapter. If it is a scanner, value is 0FDH. 0 = Double density 1 = Adapter mode 1 = Module group 4 top half 1 = Adapter is half rack 1 = Data Highway Plus at 115K baud low byte first low byte first 1 = Forces active 1 = Forces are present in the tables. non-zero means memory is protected non-zero means RAM is bad, must be cleared
Page 192
Diagnostic Status Information
10–21
1785-LT3 (PLC-5/12) and 1785-LT2 (PLC-5/25) Status Bytes Bytes
Bits
Contents
Description
1
0-2
Operating status of PLC-5 processor
0 = Program load 1 = Not used 2 = Run mode 3 = Not used 4 = Remote program load 5 = Remote test 6 = Remote run 7 = Not used
3 4 5 6 7 2
0-3 4-7
3 4-7 8
Processor Type Processor Expansion Byte
0-4
Size of user memory Series and revision of the PLC-5
5-7 9 10 all all
Processor number on DH+ Link all I/O address
11
0 1 2 5 6 all all 0 4 all all
I/O and communication parameters
12 - 13 14 - 15 16 17 18
Number of data table files Number of data type files Forcing status 1 = Forces are present in the tables. Memory protect indication Bad RAM indication
0 = Normal 1 = Major processor fault 0 = Normal 1 = Download mode Not used 0 = Not testing edits 1 = Testing edits 0 = Not testing edits 1 = Testing edits B = PLC-5 E = Expansion byte 13 = 1785-LT3 (PLC-5/12) 14 = 1785-LT2 (PLC-5/25) low word first, low byte first 0 = Revision A 1 = Revision B, etc. 0 = Series A 1 = Series B, etc. Address of the processor if it is an adapter. If it is a scanner, value is 0FDH. 0 = Double density 1 = Adapter mode 1 = Module group 4 top half 1 = Adapter is half rack 1 = Data Highway Plus at 115K baud low byte first low byte first 1 = Forces active 1 = Forces are present in the tables. non-zero means memory is protected non-zero means RAM is bad, must be cleared
Publication 1770-6.5.16 - October 1996
Page 193
10–22
Diagnostic Status Information
1785-L11B, -L20B, -L20E, -L30B, -L40B, -L40E, -L40L, -L60B, -L60L Status Bytes Bytes
Bits
Contents
Description
1
0-2
Operating status of PLC-5 processor
0 = Program load 1 = Not used 2 = Run mode 3 = Not used 4 = Remote program load 5 = Remote test 6 = Remote run 7 = Not used 0 = Normal 1 = Major processor fault 0 = Normal 1 = Download mode Not used 0 = Not testing edits 1 = Testing edits 0 = Not testing edits 1 = Testing edits B = PLC-5 E = Expansion byte 15 = 1785-L40B (PLC-5/40) 22 = 1785-LT4 (PLC-5/10) 23 = 1785-L60B (PLC-5/60) 28 = 1785-L40L (PLC-5/40) 29 = 1785-L60L (PLC-5/60) 31 = 1785-L11B (PLC-5/11) 32 = 1785-L20B (PLC-5/20) 33 = 1785-L30B (PLC-5/30) 4A = 1785-L20E (PLC-5/20E) 4B = 1785-L40E (PLC-5/40E) 55 = 1785-L80B (PLC-5/25) 59 = 1785-L80E (PLC-5/80E) low word first, low byte first 0 = Revision A 1 = Revision B, etc. 0 = Series A 1 = Series B, etc.
3 4 5 6 7 2 3
4-7 8
0-3 4-7
Processor Type all 0-4
Size of user memory Series and revision of the PLC-5
Processor Expansion Byte
5-7 9 10 all all
Processor number on DH+ Link all I/O address
11
0 1 2 5 6 all all 0 1-3
I/O and communication parameters
12 - 13 14 - 15 16
17 18
4 all all
Publication 1770-6.5.16 - October 1996
Number of data table files Number of data type files Forcing status Sub-revision number of the PLC-5 processor 1 = Forces are present in the tables. Memory protect indication Bad RAM indication
Address of the processor if it is an adapter. If it is a scanner, value is 0FDH. 0 = Double density 1 = Adapter mode 1 = Module group 4 top half 1 = Adapter is half rack 1 = Data Highway Plus at 115K baud low byte first low byte first 1 = Forces active
1 = Forces are present in the tables non-zero means memory is protected non-zero means RAM is bad, must be cleared
Page 194
Diagnostic Status Information
Bytes
Bits
Contents
Description
19 all
Debug mode
20 - 21 22 - 23 24 - 25 26 - 27 28 - 29 30 - 31 32 - 33 34 - 35 36 all all all all all all all all all
Hold point file Hold point element Edit time stamp seconds Edit time stamp minute Edit time stamp hour Edit time stamp day Edit time stamp month Edit time stamp year Port number this command received on
= 0, OFF 0 0, ON used if Debug mode is ON. Low byte first. used if Debug mode is ON. Low byte first. Low byte first. Low byte first. Low byte first Low byte first Low byte first Low byte first
5130 Cat. Nos.
10–23
For status information from these cat. nos.
See page
5130-RM1, -RM2 (PLC-5/250) controllers
10-23
5130-RM1,-RM2 (PLC-5/250) Status Bytes Bytes
Bits
Contents
Description
1
0-2
Operating status of PLC-5/250 processor
0 = Program load 1 = Not used 2 = Run mode 3 = Not used 4 = Remote program load 5 = Remote test 6 = Remote run 7 = Not used
3 4 5 6 7 2 3 4
5
0-3 4-7 all 0 1 2 3 4 5 6 7 all
Processor Type
0 = Normal 1 = Major processor fault 0 = Normal 1 = Download mode 0 = Normal 1 = Off-line 0 = Not testing edits 1 = Testing edits 0 = No edits in processor 1 = Edits in processor 0E = expansion byte D0 = PLC-5/250
ID Forces active if 1 Backup system active if 1 Partner system active if 1 Edit resource allocated if 1 Outputs reset if 1 Memory invalid if 1 SFC forces active if 1 Edit resource allocated by user if 1 Processor Station Address on Link
Publication 1770-6.5.16 - October 1996
Page 195
10–24
Diagnostic Status Information
Bytes
Bits
Contents
Description
6-7 8-9 10 - 11 all all all
Program Change Sequence Count Data Change Sequence Count User-Defined Data Change Sequence Count
1 word 1 word 1 word
Publication 1770-6.5.16 - October 1996
Page 196
Reference Data Encoding
Chapter 11
Uploading and Downloading with A-B Processors Chapter 12 PLC Addressing
Chapter 13
Line Monitor Examples ASCII Codes
Chapter 14
Chapter 15