Page 236

Chapter

7

Inspection Tools: Gages

7-46 -

Selecting Range/Reference Popup Menu and Parameters (continued)

Assigning Range Limits and Output Lines Range Limits - The term range limit, as it applies to a gage, refers to the upper and lower tolerance limits for a gage measurement or counting operation. In general, range limits specify the upper and lower boundaries of acceptable inspection “results” values. Thus, the “result” value could be a pixel count, object count, or other value from the gage inspection operation. The CVIM system provides two sets of range limits: Warning range limits, and fault range limits. Warning range limits always lie at or within fault range limits. The two sets of range limits have this relationship:

LF<=LW<=REFERENCE<=UWc=UF The REFERENCE value could be the “nominal”value from a Learn operation, or a “mean”value from a trial inspection series. For example, if the REFERENCE value were 1.50 inches, l The LW value (lower warning limit) could be set to 1.48 inches. l The UW value (upper warning limit) could be set to 1.52 inches. l The

LF value (lower fault limit) could be set to 1.46 inches. a The UF value (upper fault limit) could be set to 1.54 inches. If an inspection result value goes outside either warning limit, the CVIM system will generate a warning signal. If the value goes outside both a warning limit and a fault limit, the CVIM system will generate both a warning signal and a fault signal. In a practical application, the warning range limits can be used to indicate a deteriorating condition, such as a cutting tool starting to wear out, and the fault limits can be used to indicate a “hard” failure, such as a broken cutting tool. Output Lines -The term output lines refers to the 14 discrete output lines assigned to carry various signals to your production equipment. Of these signals, the “results” signals indicate whether or not any of the warning and/or fault range limits have been exceeded. Here are a couple of examples of using the warning and fault range limits and their corresponding output lines:

Example 1: If the dimensions of stamped-out parts change as the die wears, and one of the dimensions drifts outside the specified warning limit, the CVIM system will issue a signal to the “results” output line that you specified for the gage’s warning signal. The inspection processing would then continue.

-

Page 237

Chapter

Selecting Range/Reference Popup Mew and Parameters (continued)

7

Inspection Tools: Gages

7-47

Assigning Range f.imits and Output Lines (continued) The warning signal could be used to inform operations personnel that the die needs to be replaced soon, but not necessarily right away. They could then plan to replace the die at a convenient time, such as a shift change, rather than being forced to shut down during a shift. Example 2: If a stamping die breaks, the dimensions of the stamped-out parts could change abruptly outside both the warning limit and the fault limit. In this case, the CVIM system will issue both a warning signal and a fault signal to the specified “results” output lines, and the inspection processing would then stop. The fault signal could be used to inform operations personnel that the tool needs to be replaced right away. NOTE: Two procedures are available for determining the appropriate range limits for your application: The shorter procedure is to use the Learn function described earlier. The longer procedure is to run a series of inspections on a representative sample of workpieces in order to accumulate a statistical basis for setting the range limits. The following steps describe the shorter procedure using the Learn function:

Your Action Position a ‘),erfect” workpiece in the screen image.

Comments The “perfect” workpiece should be one on which the dimension or other characteristic that the gage is to measure or count is in the middle of the tolerance range; that is, + 0. Before you perform the “learn” function, be sure the gage is properly positioned over the workpiece in the screen image and the edges are properly defined.

Perform a Learn function, as described earlier. Look at the result in the Learn menu box.

Pick the Learn menu box to perform the Learn function. The new result is the current count or measurement this “perfect” workpiece.

for

Record the result value. Position a minimum-tolerance workpiece-&. the screen image.

Perform a second Learn function.

The “minimum-tolerance” workpiece should be one on which the workpiece dimension or other characteristic is at the low end of the tolerance range. This the dimension or characteristic below which the workpiece is unacceptable. Pick the Learn menu box to perform the Learn function again, and record the result value.

Page 238

Chapter

7

Inspection Tools: Gages

7-48

Selecting

Range/Reference

-

Assigning Range Limits and Output Lines (continued)

Popup Menu and Parameters (continued)

Your Action Position a maximum-tolerance workpiece in the screen image.

Perform a third Learn function.

Comments The “maximum-tolerance” workpiece should be one on which the workpiece dimension or other characteristic is at the high end of the tolerance range. This the dimension or characteristic above which the workpiece is unacceptable. Pick the Learn menu box to perform the Learn function again, and record the result value. The three result values are the ones you will use to determine the fault range limits. Continue now with the procedure for configuring the range limits. The following steps describe the longer procedure using a series of inspections:

Your Action Prepare to run a series of “trial” inspections.

Comments Refer to Chapter 10, Runtime Operations for more details about the following steps. For these trial inspection series, you should have on hand a sufficiently large quantity of representative workpieces. You can either place them in front of the camera manually and use a manual trigger, or use some type of automatic positioning and triggering mechanism that simulates the actual factory-floor situation.

Pick the Exit menu box in the Main Configuration menu.

When you pick the Exit menu box, the Exit popup menu will appear.

Pick the Runtime init. menu box in the Exit menu.

When you pick the Runtime popup menu will appear.

Look at the Mode menu box in the Runtime Initmenu.

If the word “Standard” appears, pick the box once to toggle to “Learn .” This activates the “learn” mode during the trial inspection series and ensures the accumulation of gage “results” data in the statistics tables.

Pick the Runtime Display menu box in the Exit menu.

When you pick the Runtime Display menu box, the Runtime Display popup menu will appear.

Pick the Stat. Page 1 menu box in the Runtime Display menu.

The Stat. Page 1 menu box causes page one of the statistics tables to appear on the monitor screen when you activate the run mode. Page one displays “results” statistics for all ena bled gages.

Init. menu box, the Runtime

Init.

-

Page 239

Chapter

7 inspection Tools: Gages 7-49

Selecting Range/Reference Popup Menu and Parameters

Assigning Range Limits and Output Lines (continued)

(con timed)

Your Action

-

Comments

Pick the Runtime menu box in the Exit menu.

When you pick the Runtime menu box, the Runtime popup menu will appear.

Pick the Goto Runmode menu box in the Runtime menu.

When you pick the Goto Runmode menu box, the CVIM system will begin running inspections if you selected Auto/Internal as the trigger source. If not, the system will await trigger inputs from whatever trigger source you selected.

Look the statistics table.

As the inspections continue, the Stat. Page 1 table will display accumulated “results” data only for each enabled gage. No data will appear for a gage that is not enabled.

When you have enough inspections, look at the four statistics columns in the’Stat. Page 1 table.

These columns show the mean, standard deviation, minimum reading, and maximum reading statistics for the inspection series.

Pick th.e Setup menu box to stop the runmode.

Picking the Setup menu box stops the run mode and returns the CVIM system to the configuration mode.

These statistics are your basis for configuring limit values for the currently selected gage, the range

At this time, the final data appearing in the Stat. Page 1 table are recorded in the Inspection Statistics table for the currently selected gage. You will see this when you pick the Range/Outputs menu box in the Range/Reference popup menu. Pick th.e Gage menu box.

This restores the Gage popup menu.

Select the gage number.

This restores the gage number whose range limits you want to set.

Pick the Range/Reference menu box.

This restores the Range/Reference popup menu.

Page 240

Chapter

7

Inspection

Tools: Gages

7-50

Selecting Range/Reference Popup Menu and Parameters (con timed)

Assigning Range Limits and Output

Lines (continued)

Use the following steps to set range limits and assign output lines.

Your Action

Comments

Pick the Range/Outputs menu box in. the Range/Outputs popup menu.

When you pick the Range/Outputs appear on the screen, as follows:

menu box, two tables will

2

Inspection Statistics Table

-

:#;n$e$&e&e Learn:

;.i.;.:igc~ -

Nominal = 111 B.Pixels

Gage Popup Menu i Gage 1: Enabled Previous

Next

Env.

Camera A

I Ref. Line

Ref. Win

$&g~

Window

Mist

Exit

The Range/Outputs setup table is the one you will use to set the range limits and assign the output lines. The numbers appearing in it now are the limits and lines set previously. Note that each box in the table has the three dots (O-J, which indicates that you will need to pick each box, one at a time, in order to set its value. The Inspection Statistics table shows the statistical accumulation of inspection “results” data if you performed a series of inspections with the CVIM system running in the “learn” mode. These numbers can help you choose the best values for the range limits.

-

Page 241

Chapter

7

Inspection

Tools: Gages 7-51

Assigning Range f imits and Output Lines (continued)

Selecting Range/Reference Popup Menu <andParameters

The next several steps show you how to enter values for the range limits.

(continued)

NOTE: The order in which these steps are presented may not be the appropriate order in all cases. If not, a blinking message will appear in the calculator display that says: VALUE OUT OF RANGE. For example, thismessage will appear if you attempt to change the upper warning range limit to a value below the lower warning range limit. Comments

Your Action Pick the -upper box under WARNING RANGE.

This is the warning range upper (“High”) limit. When you pick this box, the calculator pad appears on the screen, as follows:

-

Inspection Statktics Table

Define Features

Learn:

Nominal = 111 B.Pixels

Gage 1:

Enabled

Env.

Camera A

Pick each digit of the upper warning limit value. Pick the Enter key.

Ref. Line

Ref. Win

,.@&e. ., :

Window

Mist

Exit

As you pick each digit, it will appear in the calculator “display.“Thus, for a value of 50, pick “5,” then pick “0.” When you pick the Enter key, the new value will appear in the upper box under WARNING RANGE.

Pick the -middle box under WARNING RANGE.

This is the warning range lower (“Low”)

limit.

Pick each digit of the lower warning limit value.

As you pick each digit, it will appear in the calculator “display.”

Page 242

Chapter

7-52

Selecting Range/Reference Popup Menu and Parameters

7

Inspection Tools: Gages

Assigning Range Limits and Output Lines (continued)

(continued)

Comments

Your Action Pick the Enter key. Pick the upper box under FAULT RANGE. Pick each digit of the upper fault limit value. Pick the Enter key.

When you pick the Enter key, the new value will appear in the middle box under WARNING RANGE. This is the fault range upper (“High”)

limit.

As you pick each digit, it will appear in the calculator “display.” When you pick the Enter key, the new value will appear in the upper box under FAULT RANGE.

Pick the middle box under FAULT RANGE.

This is the fault range lower (“Low”)

limit.

Pick each digit of the lower fault limit value.

As you pick each digit, it will appear in the calculator “display.”

Pick the Enter key.

When you pick the Enter key, the new value will appear in the middle box under FAULT RANGE.

Pick the lower box under WARNING RANGE.

When you pick this box, a variation of the Output Assignment popup menu appears on the screen, as follows:

Range/Reference Popup Menu t-

Camera A

Ref. Line

2 l/Results

0

3 l/Results

0

4 l/Results i-J

5 Z/Results q

8 Not Used

0

9 Not Used

[7

10 Not Used

0

11 Not Used

Gage

Popup Menu

Env.

0

Ref. Win

/‘&$&I’~ Window

Mist

Exit

1

Page 243

Chapter

7

Inspection Tools: Gages 7-53

Selecting Range/Reference Popup Menu (and Parameters

Assigning Range limits and Output fines (continued)

(continued)

Your Action

Comments This is the Output Line Selection popup menu. It shows the output line functions that you assigned to the Output Assignment popup menu in Chapter 4, Operating Environment. NOTE: This menu shows that only the output lines that you designated in Chapter 4 as ” 1/Resu Its” are available to this gage if it is in tool set #l (“Z/Results” if the gage is in tool set #2). These appear in light type, and all others appear in black type (meaning that you cannot pick them). Note also that the No Output box in the Output Line Selection popup menu has a shaded square (0). This indicates that no output line is currently assigned to carry WARNING RANGE signals for this gage. If you prepared an Output Line Planning Sheet in Appendix A, refer to it for the output line assignments for this gage.

Pick the output line number for the WARNING RANGE.

From the Output Line Selection popup menu, pick one of the available output lines boxes labeled ’ 1/Resu Its”. When you pick the appropriate box, the shaded square will shift to it. In addition, the output line number appears in the lower box under WARNING RANGE.

Pick the lower box under -FAULT RANGE. Pick the output line number for the FAULT RANGE.

From the Output Line Selection popup menu, pick one of the available output lines boxes labeled “1 /Resu Its”. When you pick the appropriate box, the shaded square will shift to it. In addition, the output line number appears in the lower box under FAULT RANGE.

Page 244

Chapter

7 inspection Tools: Gages

7-54

Selecting

Selecting Range/Reference Popup Menu and Parameters

Reference Popup Menu

Select the Reference popup menu, if appropriate, then assign a reference tool to provide shift and/or rotation compensation to the currently selected gage.

(continued)

You can configure CVIM so that one of the six reference tools provides shift compensation to a gage. During an inspection, if the reference tool detects shift and/or rotation in the workpiece, it shifts and/or rotates the gage a corresponding amount and direction. Use the following steps to select a reference tool for the currently selected gage. Comments

Your Action Look at the Ref menu box in. the Range/Reference popup menu. Pick the Ref menu box.

The Ref menu box shows the currently selected reference tool assigned to this gage. When you pick the Ref menu box, the Reference popup menu appears, as follows: &&L&

;i .i; p.

t::::::

Range/Reference Popuy Menu

I

I

Define Gage

10

Ref.Line

1

10

Ref.Win

1

10

Ref.Win 2

Ref. Line

Ref. Win

0.0

I

4 ..:

Env.

Camera A

Qage

Window

Mist

Exit

Note that the Fixed box in the Reference menu has a shaded square (0). This indicates that a reference tool is not currently assigned to this gage. Also note that only the available reference tools are in light type. All others are shown in black type, which indicates that you cannot pick them. Pick the appropriate reference tool from the menu.

If appropriate, pick one of the available reference tools from the Reference menu.