The text of a spec sheet · part 11 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 101 to 110
Pages 101 to 110 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 101
General Purpose Electronic Timers and Counters
Special Function Flasher Timing Relay Description t2 Setting Up Switch Down
Supply Voltages (A1/A2)
Z12 12V DC U23 24…48V DC, 24…240V AC, 50/60 Hz
Seperate Range Settings
1 Range Setting t1 Setting
700-FSH3U
700-FSH3V Function Diagram / Connection Diagram(1)
(H) Flasher (Repeat Cycle Starting with Pulse or Pause)
The repeat cycle timer permits different settings for on and off times. The following operating modes are possible: • Oscillating mode; repeat cycle starts with voltage that is applied at A1 and B1, and continues to repeat until voltage is off. • One cycle mode; started by energizing B1 with voltage on A1 and A2. • Output starts with pulse or pause (switch ⊗ Up or Down). • 700-FSH3U provides (1) range setting for t1 and t2 700-FSH3V provides (2) range settings for t1 and t2 Supply Voltage Controlled, Oscillating Mode Starting with Pause, Switch ⊗ Is up U S Output LED t2 t1 t2 t1
A1/A2 A1/B1 18 15 16
A1 B1
A2
Supply Voltage Controlled, Oscillating Mode Starting with Pulse, Switch ⊗ is Down 15
18 16
U S
A1/A2 A1
A1/B1 t2 t1
S B1
15 t1 t2 t2 15 18 16
A2
18 16
U S
A1/A2 A1/B1
Output LED t2
LED Operation Chart Ñ Green LED
100
15
A2
18 16
Output at Shelf State, No Timing - LED OFF Output at Shelf State, Time is Running - LED Flashing Output NO Contact is Closed, No Timing - LED On Output NO Contact is Closed, Time is Running - LED Long Flashing
Rockwell Automation Publication 700-TD552B-EN-P - August 2018 s A1 B1
15
A2
18 16 t1 t2 1518 16
If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.
LED LED LED LED
A1 B1
Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms, DC 30 ms), Switch ⊗ is Down One Cycle Mode, Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.
t1 t1 t2 1518 16
LED (1)
t1
A1/A2 A1/B1
LED
Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms, DC 30 ms), Switch ⊗ is Up One Cycle Mode, Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.
Output
U S Output
Page 102
General Purpose Electronic Timers and Counters
Function Diagram / Connection Diagram(1) (Q) Off-Delay without Supply Voltage (True Off-Delay)
• When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the time delay. U tp
Output
A1/A2 t
18 15 16
LED
A2 tp
U
15
A1
A1/A2
Output 1 t
18 15 16
Output 2 t
25
18 16
28 26
A1
15
A2
18 16 28 26
25
LED
(Y) Star-Delta Timing Relay
• When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns to shelf state. After the fixed time (50… 60 ms), the output contact 17/28Δ changes state. Both output contacts return to shelf state whenever the power is removed.
A1/A2
U t
A1
17
A2
18
17/18 17/28 tu = 50...65 ms
28
LED (1) Min. pulse (tp) required: 800 ms
Specifications - 700-FS Relays(1) Attribute
Input Current
1 mA
Max. Leakage Current
Value
Setting Accuracy
±5% of full scale
Repeatability
±0.2% of the setting values
Tolerance
Voltage: ±0.001%/%ΔU Temperature: ±0.025%/°C
Cable Length
400 micro Amps Max. 250 m (800 ft) without parallel load between B1 and A2, Max.50m(160ft)withload(<3 kΩ) between B1 and A2
Outputs Contact Type Dielectric Coil to Contact
Supply
Relay as changeover switch 5000 V Voltage: 440V AC
Attribute Supply Voltages
Current Ith (AC-1): 8 A (5 A for 700- FSQ)
Value
Power: 2000 VA
24…48V DC and 24…240V AC, 50/60 Hz (multi voltage)
Voltage Tolerance
–20…+20% (DC), –15…+10% (AC)
Power Consumption
0.5 W at 24V DC, 5 VA at 240V AC
According to IEC 947-5-1: Switching Capacity
3 A/440V AC (inductive load, AC 14) 3 A/250V AC (inductive load, AC 15)
Time Energized
100%
Reset Time
50 ms
According to UL 508:
Voltage Interruption
≥20 ms without reset (supply voltage)
1.5 A/250V AC (B300)
Input Impedance
Relay ON: 3K-13K ohms, Relay OFF: 0.7K-4K ohms
1 A/24V DC (inductive load, DC 13)
3 A/120V AC (B300) Short-Circuit Resistance
Cable Length (Supply Voltage Control)
10 A gL
Max. 250 m (800 ft)
Pulse Control (B1) Attribute
Value
Pulse Duration
≥50 ms (AC), ≥30 ms (DC)
Input Voltage
Supply voltage range
(1) Time Characteristics (according to VDE 0435, Part 2021)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
101
Page 103
General Purpose Electronic Timers and Counters
Mechanical: 30 million operations Electrical operations: 4 mil at 1 A/250V AC, cos φ = 1 0.2 mil at 6 A/250V AC, cos φ = 1 1.5 mil at 1 A/250V AC, cos φ = 0.3 0.3 mil at 3 A/250V AC, cos φ = 0.3
Life
0.5 mil at 6 A/24V DC, resistive 2 mil at 4 A/24V DC, resistive 2 mil at 0.2 A/230V DC, resistive 1 mil at 0.4 A/24V DC, L/R = 20 ms 1 mil at 0.2 A/110V DC, L/R = 20 ms 1 mil at 0.1 A/230V DC, L/R = 20 ms State Indicator
1 LED, combination signal
General Data- 700-FS Relays Insulation Characteristics
2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 μs surge voltage according to IEC 947-1 between all inputs and outputs
EMC/Interference Immunity
Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 μs Burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD discharge according to IEC 1000- 4-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3
EMC/Emission
Electromagnetic fields according to EN 55 022: class B
Safe Isolation
According to VDE 106, part 101
Climatic Withstand
56 Cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3
Vibration Resistance
4 g in three axes at 10…500 Hz, test FC according to IEC 68-2-6
Shock Resistance
50 g according to IEC 68-2-27
Protection Class
Enclosure: IP 40 IP 30 (Single-function) Terminal: IP 20 according to IEC 947-1
Weight Approval Ambient Temperature
100 g
UL, C-UL Open: –25…+60 °C Enclosed: –25…+45 °C Storage: –40…+85 °C
Terminals
Screw terminal M3.5 for Number 2 Posidriv, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 N•m, max. 1.2 N•m). Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106.
Mounting
Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type)
Disposal
Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
Standards
EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
Temp. Code T4A 2A 32VDC MAX. Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.
102
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 104
General Purpose Electronic Timers and Counters
700-HNC Miniature Timing Relay • Miniature timer, perfect for converting 700-HC "Ice Cube" relays into timing relays • 4 operating modes • 4PDT contact output • Timing range from 0.1 s…10 hr • Socket mounted Model
Timing Mode
Contact Output
Input Voltages 12V DC 24V DC 48V DC
On-Delay One Shot Repeat cycle, OFF-start Repeat cycle, ON-start
100…110V DC 4PDT 125V DC 24V AC 100…120V AC 200…230V AC
Cat. No. 700-HNC
Timing Range 0.1 s…10 min .1 min…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr 0.1 s…10 min 0.1 min.…10 hr
Socket Type
700-HN103 700-HN128
Cat. No. 700-HNC44AZ12 700-HNC44BZ12 700-HNC44AZ24 700-HNC44BZ24 700-HNC44AZ48 700-HNC44BZ48 700-HNC44AZ11 700-HNC44BZ11 700-HNC44AZ25 700-HNC44BZ25 700-HNC44AA24 700-HNC44BA24 700-HNC44AA12 700-HNC44BA12 700-HNC44AA23 700-HNC44BA23
Accessories - 700-HNC Relays Photo
Description
Pkg. Quantity
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting. Guarded Terminal Construction 14-Blade miniature socket for use with 700-HNC timers.
10
700-HN103
Screw Terminal Base Sockets, Panel or DIN Rail Mounting. Open Style Construction 14-blade miniature socket for use with 700-HNC timers.
10
700-HN128
Screw Terminal Socket – Panel or DIN Rail Mounting. Guarded Terminal Construction 14-blade miniature socket for use with 700-HNC timers. This socket has coil and contact separation.
10
700-HN104
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HNC Timers. Secures Timer in Socket.
10
700-HN263
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
103
Page 105
General Purpose Electronic Timers and Counters
Specifications - 700-HNC Relays Attribute
700-HNC
Pilot Duty Rating
NEMA B300
Pin type
Plug-in 85%…110% of rated supply voltage (12V DC: 90%…110% of rated supply voltage) (1)
Operating voltage range Reset voltage
10% min. of rated supply voltage 24V AC:
Relay ON: Relay OFF:
1.5 VA (1.1 W) (at 24V AC, 60 Hz) 0.2 VA (0.1 W) (at 24V AC, 60 Hz)
100…120V AC:
Relay ON: Relay OFF:
1.5 VA (1.3 W) (at 120V AC, 60 Hz) 0.8 VA (0.5 W) (at 120V AC, 60 Hz)
200…230V AC:
Relay ON: Relay OFF:
1.8 VA (1.5 W) (at 230V AC, 60 Hz) 1.2 VA (0.9 W) (at 230V AC, 60 Hz)
12V DC:
Relay ON: Relay OFF:
0.9 W (at 12V DC) 0.07 W (at 12V DC)
24V DC:
Relay ON: Relay OFF:
0.9 W (at 24V DC) 0.07 W (at 24V DC)
48V DC:
Relay ON: Relay OFF:
1.0 W (at 48V DC) 0.2 W (at 48V DC)
100…110V DC:
Relay ON: Relay OFF:
1.3 W (at 110V DC) 0.3 W (at 110V DC)
125V DC:
Relay ON: Relay OFF:
1.3 W (at 125V DC) 0.3 W (at 125V DC)
Power consumption
Control outputs
4PDT: 5 A at 250V AC, resistive load (cos φ = 1)
Characteristics Make
Break
120V AC
30 A
240V AC
15 A
120V AC
3A
240V AC
1.5 A
Hp at 120V AC
1/6 Hp
Hp at 240V AC
1/6 Hp
Accuracy of operating time
±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error
±10%±50 ms FS max.
Reset time
Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage
±2% FS max.
Influence of temperature
±2% FS max.
Insulation resistance
100 mΩ min. (at 500V DC) 2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts) (2)
2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output) Dielectric strength
2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) 1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Malfunction: 10…55 Hz, 0.5 mm single amplitude
Shock resistance
Malfunction: 100 m/s2 (approx. 10G)
Ambient temperature 104
Operating: -10 °C…50 °C (with no icing) Storage: -25 °C…65 °C (with no icing) Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 106
General Purpose Electronic Timers and Counters
Attribute Ambient humidity Life expectancy
700-HNC Operating: 35%…85% Mechanical: 10 000 000 operations min. (under no load at 1800 operations/hr) Electrical: 4PDT: 200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
Noise immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns / 1 μs, 1- ns rise)
Static immunity
Destruction:8 kV Malfunction:4 kV IP40
Enclosure rating Weight
Approx. 50 g Emission Enclosure:EN55011 Group 1 class A Emission AC Mains:EN55011 Group 1 class A Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3)
EMC
Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst:EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
Standards
UL 508, CSA 22.2 No. 14, EN/IEC 61812-1
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CSA Certified (File 224268), CE Marked, C- Tick Marked
(1) Single-phase, full-wave-rectified power supplies can be used. (2) When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C…50 °C, supply 90%…110% of the rated supply voltages supply 95%…110% with 12V DC type).
General Timer Functions
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
105
Page 107
General Purpose Electronic Timers and Counters
Timing Charts - 700-HNC Relays IMPORTANT t: Set time, Rt:Reset time
Operating Mode
Timing Charts / Wiring Diagram Rt t
ON-Delay t
Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Power
Time limit contact NO (9-5, 10-6, 11-7, 12-8)
t Output
Run / Power Indicator (PW) Output Indicator (UP)
One shot
Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Power
Time limit contact NO (9-5, 10-6, 11-7, 12-8)
Output Run / Power Indicator (PW) Output Indicator (UP)
t
Repeat Cycle OFF-Start t t t
Timer Circuit
Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Power t t t
Output
Time limit contact NO (9-5, 10-6, 11-7, 12-8)
UP
PW
Run / Power Indicator (PW) Output Indicator (UP)
t t t t
Power (13-14)
Repeat Cycle ON-Start
Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Power t t
Output t
Time limit contact NO (9-5, 10-6, 11-7, 12-8) Run / Power Indicator (PW) Output Indicator (UP)
General Timer Functions
Pulse Operation A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNC timing relay in interval mode as shown in the following timing charts.
Output Indicator (Orange) (Lit: Output ON)
Run/Power Indicator (Green) (Lit: Power ON)
1
2
3
4
5
6
7
8
Power (9-14)
Main Dial Set the desired time according to time range selectable by DIP switch.
External short circuit (5-13) External input (9-13)
11
9
10
13
Timer
14
( - ) Circuit (~)
(+) (~)
~ (
106
Time limit contact NO (10-6, 11-7, 12-8) Time limit contact NC (10-2, 11-3, 12-4) Run/Power indicator (PW) Output indicator (UP)
12
UP FW External Input
50 ms min.
)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Note:
t: Set time Rt: Reset time
Page 108
General Purpose Electronic Timers and Counters
DIP Switch Settings - 700-HNC Relays Time Ranges Cat. No.
Time Range
Time Setting Range
700-HNC44AZ12 700-HNC44AZ24 700-HNC44AZ48 700-HNC44AZ11 700-HNC44AZ25 700-HNC44AA24 700-HNC44AA12 700-HNC44AA23
1s
0.1 s…1 s
Yes
10 s
1 s…10 s
No
1 min
0.1 s…1 min
No
10 min
1…10 min
No
1 min
0.1…1 min
Yes
10 min
1…10 min
No
1 hr
0.1…1 hr
No
1 hr
1…10 hr
No
700-HNC44BZ12 700-HNC44BZ24 700-HNC44BZ48 700-HNC44BZ11 700-HNC44BZ25 700-HNC44BA24 700-HNC44BA12 700-HNC44BA23
Setting
Factory-Set
Note: The top two DIP switch pins are used to select the time ranges.
Operating Mode
Setting
Factory-set
ON-delay
Yes
One Shot
No
Repeat Cycle OFF-start
No
Repeat Cycle ON-start
No
Note: The top two DIP switch pins are used to select the time ranges.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
107
Page 109
General Purpose Electronic Timers and Counters
Dimensions - 700-HNC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
30.0 (1-3/16) 6.1 (15/64)
Fourteen 3 x 1.2 mm Elliptic Holes
8
7
6
5
4
3
2
1
24.9 (57/64) 21.1 (53/64)
4.2 (5/32)
28 (1.10) 4.0 (0.15)
6.3 (.024)
6.4 (0.25)
52.6 (2.07) 63.0 (2.48)
14 12
21.5 max (084)
13 11
10
62.0 (2-15/64)
65.0 (2-9/16)
9
26.0 (1-1/64)
Cat. No. 700-HN128 (1) Wire Size: 2 x 1.5 mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) - Torque: 0.8 N•m (7 lb•in)
Cat. No. 700-HNC…
27.0 (1.06)
Panel Mounting
24.5 (31/32)
60.9 (2.40) 21.5 (0.85)
28.9 (1-9/64)
76.0 (2.99)
67.0 (2-5/8)
35.6 (1.40) 3.2 (0.13) 18.9 (0.74) 34.9 (1.37)
30.0 (1-11/64)
2.5 (0.10)
Cat. No. 700-HN103 Single wire: 0.2…2.5 mm2 (#24 AWG…14 AWG) Double wire: 2 x 0.2 mm2…2 x 1.5 mm2 (2 x 24 AWG…2 x 16 AWG) Wire type: solid or stranded, copper only Strip length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)
Cat. No. 700-HN104 Single Wire: 0.2…2.5 mm2 ( #24 AWG…14 AWG) Double Wire: 2 x 0.2 mm2…2 x2.5 mm2 (2 x 24 AWG…2 x 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
(1) Total height of 700-HN128 + 700-HNC is 82.5 mm.
108
32.0 (1.26) 35.5 (1.40)
#4-40 M3
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 110
General Purpose Electronic Timers and Counters
700-HNK Ultra-Slim Timing Relay • The ultra-slim timing relay is the smallest relay available • It is perfect for converting 700-HK relays into a timing relay • SPDT and DPST-NO contact output • Socket-mounted • Timing range From 0.1 s…10 hr Photo
Timing Mode
Socket Type
Contact Output
Timing Range
0.1 s…10 min 700-HN121
SPDT (1) 0.1 min…10 hr
On-Delay One Shot Repeat Cycle, OFF-start Repeat Cycle, ON-start 0.1 s…10 min 700-HN122
DPST-NO(2) 0.1 min…10 hr
Input Voltage
Cat. No.
12V DC
700-HNK41AZ12
24V DC
700-HNK41AZ24
24V AC
700-HNK41AA24
12V DC
700-HNK41BZ12
24V DC
700-HNK41BZ24
24V AC
700-HNK41BA24
12V DC
700-HNK42AZ12
24V DC
700-HNK42AZ24
24V AC
700-HNK42AA24
12V DC
700-HNK42BZ12
24V DC
700-HNK42BZ24
24V AC
700-HNK42BA24
(1) 5-blade terminal type only. (2) 8-blade terminal type only.
Accessories - 700-HNK Relays Pkg. Quantity
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniatue socket. For use with 1-pole type 700-HNK41 timers. Socket includes a retainer clip.
10
700-HN121
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole, 700-HNK42 timers. This socket includes a retainer clip.
10
700-HN122
Description
Sockets and Retainer Clip Reference Timer Type 700-HNK
Socket Cat. No. 700-HN121 700-HN122
Retainer Clip Cat. No. Provided Provided
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
109