Power Distribution 4D.0 Section Overview
Once you have planned your system layout, you can begin connecting power and components to your system. In this section we discuss: how ac power is distributed through the system connecting the main power supply and operator interface power supply main and operator panel power supply input power specifications protective grounding The external ac power connections to the control and operator panel are covered in this section. For information on external ac power source connections to servo amplifiers, servo motors, and I/O modules, refer to the sections that cover these components. For details on external ac power source connections to an analog servo amplifier or analog servo motor, refer to the documentation provided by the manufacturer. Figure 4D.1 shows the power distribution from the supply to the control and its components. Figure 4D.1 Power Distribution from the Supply to the Control and its Components
Indicates fiber optic cable 1
9/260 or 9/290 CNC
Customer supplied 24V dc
115/230V ac
115/230V ac
2 E-Stop
K1A
3 4 5
24V dc Customer supplied1 P1 Low current ( < 1.0 amp) pilot relay On button
ON
Main power supply
6 7
Digital I/O E151/E152/E153
Digital I/O E154
K1
Analog I/O
I/O Ring
K1B CN07 Cable C04 8A Fuse
1746 I/O ring adapter
HPG
5V dc ac input 115/230V ac
MTB I/O 12V dc
High density I/O Customer supplied 24V dc
Auxiliary ac
COM
115/230V ac
OFF
Color monitor
Off button To power circuitry
Operator panel power supply2
12V dc
Monochrome monitor
5V dc connectors to servo modules (encoder power) (9/260 and 9/290 only)
1 May not be necessary on PS2 24V is part of the power supply. 2 May be mounted on operator panel or portable operator panel interface assembly.
11194-I
4D-1
Page 232
Section 4D Power Distribution and Wiring Guidelines
4D.1 Connecting the Main Power Supply
This section discusses the connections of the main power supply and the operator panel power supply.
Connecting the Main Power Supply to AC Power Source ATTENTION: To guard against electrical shock hazards, never make connections or disconnections at the ac distribution network unless the main ac disconnect switch is open and locked.
Important: In addition to supplying power to the operator panel power supply, the main power supply also supplies power to the motherboard, the CPU board, and the servo module(s) (9/260 and 9/290 only). As shown in Figure 4D.2, the power cables for these modules originate from the side of the main power supply (for 9/260 and 9/290). Refer to Figure 4D.2 while performing these steps: 1.
Locate AC-IN, L1, L2, and PE on terminal block BT04.
2.
Connect the ac power source cable (C02) from the external ac power source to AC-IN, L1, L2, and PE on BT04.
3.
Connect the chassis ground terminal to the cabinet’s grounding bus bar.
Important: The chassis ground terminal connects to the control chassis and designated cable shields. Power supply common is AC coupled to chassis ground. It is the users responsibility to determine if a direct connection to cabinet ground bus is required.
4D-2
Page 233
Section 4D Power Distribution and Wiring Guidlines
Figure 4D.2 Main Power Supply Connection (for the 9/260 and the 9/290)
ALLEN-BRADLEY
AC POWER
To motherboard power supply connector J1
BT04
AC
5V DC Encoder Power Use this table to connect to the servo or optional feedback modules on the 9/260 or 9/290 Module in 9/260 or 9/290
Connector
3-axis Digital Servo 3-axis Analog Servo 4-axis Digital Servo 4-axis Analog/1394 Servo Optional Feedback
CN13 P3 P3 P3 CN25M
250V 8A
IN
L1
From ac power source L2 PE
AUX AC
L1 L2 ON SW COM
Switched ac power to operator panel power supply Power-on switch
Power-off switch
OFF SW
4D-3
Page 234
Section 4D Power Distribution and Wiring Guidelines
Connecting the Main Power Supply to the Servo Module for +5V dc Encoders on 9/260 and 9/290 Systems The servo modules gets power directly from the motherboard. However, 5V dc encoder power, which runs through the servo module, must come directly from the main power supply. Important: Some applications may not require the use of the servo module’s 5V dc encoder power (i.e., servo modules 15V dc encoder power or an external power supply is used). For these applications, this connection is not necessary. The main power supply provides 3 wires (with connectors) for 5V dc encoder power supply. These wires are shown in Figure 4D.2. Connect any of the 5V dc encoder power wires to connector on your servo module that is shown here: Figure 4D.3 5V dc Encoder Power Connections to Servo Module 3-Axis Digital Servo Module
Connect to CN13 for 5V dc encoder power
3-Axis Analog Servo Module
Connect to P3 for 5V dc encoder power
4-Axis Servo Modules
Connect to P3 for 5V dc encoder power
TB2 TB1
CN1 CN11
CN8
P1 (CN1)
TB2
P3
J2
J1 J3
J2 J3
P3
CN2 CN3 CN4 CN5 CN6 CN7 CN9
J1
P2
CN12
P2
CN10 CN13
4D-4
TB1
CN1
J4
Page 235
Section 4D Power Distribution and Wiring Guidlines
4D.2 Main and Operator Panel Power Supply Input Power Specifications
The input power specifications of the main power supply, the operator panel power supply, and the portable operator panel interface module power supply are shown in Table 4D.A and Table 4D.B. For output power specifications of the main power supply (PS1) for 9/260 and 9/290, refer to page 4A-10. For output power specifications of the operator panel power supply, refer to page 9A-7. Table 4D.A Main Input Power Specifications Specifications
Item Input
Rated Input
115V/230V ac -- 50/60Hz
Input Range
90-265V ac --- 47-63Hz
Power Consumption 8520-PS1 8520-PS2A
225 Watts @ 50°C
Fuse
8A/250V
Connection
Terminal Block
130 Watts @ 50°C
Remark
168 Watts @ 60°C or 225 Watts with min. 25 CFM 96.4 Watts @ 60°C or 130 Watts with 25 CFM Protects power supply module and sub-power supply and the color CRT
4D-5
Page 236
Section 4D Power Distribution and Wiring Guidelines
Connecting the Main Power Supply to the Monochrome Operator Panel Power Supply You connect the operator panel power supply directly to the main power supply. Refer to Figure 4D.2 and Figure 4D.4 when performing these steps: 1.
Use the ac power supply cable (C03) to connect terminals AUX-AC L1 and L2 of terminal block BT04 on the main power supply to terminals L1 and L2 of terminal block BT02 on the operator panel power supply.
2.
Connect the chassis ground terminal on the operator panel power supply to the cabinet’s grounding bus bar.
Important: The chassis ground terminal connects to the operator panel chassis and designated cable shields. Power supply common is AC coupled to chassis ground. It is the users responsibility to determine if a direct connection to cabinet ground bus is required. Figure 4D.4 Power Supply Connector on Monochrome Operator Panel BT02
AC
L1
L1
L2
L2
AC
PE HPG
HPG
HPG
MTB
5V
5V
GND
GND
5V
5V
GND
GND
5V
5V
GND
GND
12V
12V
GND
GND
To HPG
To HPG
To H PG To M TB panel I /O m o d u le
19450
4D-6
Page 237
Section 4D Power Distribution and Wiring Guidlines
Connecting the Main Power Supply to the Portable Operator Panel Interface Assembly Power Supply You connect the Portable Operator Panel Interface Assembly power supply directly to the main power supply. Refer to Figure 4D.2 and Figure 4D.5 when performing these steps: 1.
Use the ac power supply cable (C03) to connect terminals AUX-AC L1 and L2 of terminal block BT04 on the main power supply to terminals L1 and L2 of terminal block BT02 on the power supply for the portable operator panel interface module.
2.
Connect the chassis ground terminal on the portable operator panel interface assembly power supply to the cabinet’s grounding bus bar.
Figure 4D.5 Power Supply Connector on Portable Operator Panel Interface Assembly
GND 12V GND 5V GND 5V GND 5V
GND
To M TB panel
12V GND 5V GND 5V GND 5V
PE
PE
L2 L1 AC
L1
To HPG
To HPG
To HPG
AC
L2
4D-7
Page 238
Section 4D Power Distribution and Wiring Guidelines
Connecting Main Power Supply to the Color Operator Panel You connect the operator panel power supply directly to the main power supply. The operator panel power supply receives power from the color CRT power supply through an internal jumper from the AC (L1 and L2) terminals. Figure 4D.6 Color Operator Panel Power Supply Connection
BT02 AC
L1
L1
L2
L2
AC
PE HPG
HPG
HPG
MTB
5V
5V
GND
GND
5V
5V
GND
GND
5V
5V
GND
GND
12V
12V
GND
GND
To HPG
To HPG
To HPG To M TB panel I/ O m o d u le
19450
Connect terminals AUX-AC L1 and L2 of terminal block BT04 on the main power supply to the color CRT power supply terminals AC L1 and AC L2, which are located on the rear of the color operator panel, using the power supply cable C03. Important: The chassis ground terminal connects to the operator panel chassis and designated cable shields. Power supply common is AC coupled to chassis ground. It is the users responsibility to determine if a direct connection to cabinet ground bus is required.
4D-8
Page 239
Section 4D Power Distribution and Wiring Guidlines
Connecting the Power Supply to the MTB Panel ON/Off Switch Terminal block BT04 terminals ON-SW, COM and the OFF-SW are connected to terminal block BT-20 terminals ON, COM and OFF on the MTB panel using the ON/OFF signal cable C01. Figure 4D.7 shows terminal block BT-20 on the MTB panel. Figure 4D.7 MTB Panel ON/OFF Switch Connection
To Main Power Supply (BT04)
To Motherboard/ Processor Board (TB1)
PWR ON PWR COM PWR OFF ESTOP
+12V GND
CN51
OP12 (in)
ESTOP COM
OP11 (out)
RESET
JPR1 JPR2
CN52 I/O ring fault indicator
BT20
MTB Panel
Table 4D.B Operator Panel or Portable Operator Panel Interface Assembly Power Supply Input Power Specifications Item Input
Specifications Rated Input
115/230V ac --- 50/60Hz
Input Range
90-265V ac --- 47-63Hz
Power Consumption
55 Watts
Fuse
2A/250V
Connection
Terminal Block
Remark
4D-9
Page 240
Section 4D Power Distribution and Wiring Guidelines
4D.3 Protective Grounding
All components and modules must be correctly grounded to protect against electrical shock hazards. Proper grounding also helps to reduce the effect of electrical noise by isolating induced noise voltages to individual ground wires and shunting them to ground. There are two types of grounds used in electrical system design, chassis and earth. Chassis ground is defined as the internal ground of a cabinet. Earth ground is defined as the central ground for all electrical equipment and ac power within any factory. For the chassis ground use a conductor such as the control cabinet or the cabinet’s grounding bus bar. To provide good conductivity when the cabinet is used as the conductor, remove rust and any coating from the area of the cabinet that will be a contact point for the ground cables. Each component installed in the cabinet will have a separate grounding cable connected to the conductor. Each electrical cabinet requires two separate connections from the cabinet to the earth ground: from the chassis ground -- each component installed in a cabinet is connected to the cabinet’s chassis ground. The cabinet chassis ground is connected to the earth ground by a single grounding cable. from the cabinet -- each cabinet is connected separately to the earth ground. ATTENTION: To guard against damage to the machine, do not interconnect chassis ground wires between the components. This would place ground wires in series and cause their noise voltages to be additive. The resulting increased noise energy can interfere with proper control and machine functions.
A general system grounding diagram, which shows both chassis ground and earth ground, is shown in Figure 5A.21.
4D-10