Page 271

Section 5A 9/440 Resolver- based CNC/Drive System

The remote I/O circuitry and connector are integral parts of the wiring board in the 9/440 resolver--based system module. Figure 5A.11 shows the remote I/O connector mounted on the 9/440 resolver--based control wiring board. Wire connections for the remote I/O communications are made through the TB4 NODE ADAPT connector. Connect the wires for remote I/O as shown in the following figure. Refer to your 1771 I/O documentation for details on making remote I/O connections. Figure 5A.11 Remote I/O Connector in System Module

9/440 Resolver--based System Module

Remote I/O Plug RIO2

RIO1

SHLD

TB4

Blue Shield Clear

5A.4.2 9/440 Resolver- based Control Remote I/O Connection

Open Cover

9/440 Resolver- based Control Remote I/O LED Assuming you have: made all necessary remote I/O communication connections on your 1771 I/O network configured your remote I/O port for the remote I/O network in AMP written PAL to set $RMON true during the first PAL foreground execution, and to handle input and output words ($RMI1 -- $RMI8 inputs to PAL and $RMO1 -- $RMO8 outputs from PAL.)

5A-25

Page 272

Section 5A 9/440 Resolver- based CNC/Drive System

CNC Processor Board

Front of System Module

Serial Port A

R--I/O LED

You are ready to start receiving and transmitting remote I/O information. An LED is provided on the 9/440 resolver--based CNC processor board and is visible from the bottom of the system module. As remote I/O responds to commands, you should see this LED pattern: LED

Status

Description

Green R- I/O LED

ON

Active Link to PLC. This is the normal state when the RIO link is active.

FLASHING

The remote I/O link is active but the PLC is currently in program mode.

OFF

Remote I/O link is offline. The port is not being used, not configured in AMP correctly, not turned on with $RMON, or not attached to a 1771 device.

Video

5A.4.3 9/440 Resolver- based Analog Out (TB2 and TB3)

Two auxiliary analog outputs are provided through the connectors labeled TB2 and TB3 of the 9/440 resolver--based wiring board. These connectors are typically used to command external analog spindle drive systems but can also be configured in AMP to control additional analog servo systems. Figure 5A.12 shows the location of ANALOG OUT connector and lists terminal assignments of this connector. Important: If positioning feedback is required for the spindle or analog servo system, its corresponding encoder feedback should be wired through one of the encoder feedback connectors and indicated as such in AMP. Figure 5A.12 Terminal Block TB2 and TB3, Plug-type Terminal Block Connections. P1 +

Wiring Board

J5 J14

-WATCHDOG

TB2

TB3

SHLD ANLGOUT2 RET SHLD ANLGOUT1 RET

XILINX

TB2 TB3

TB4

5A-26

Analog Out 1 (spindle 1)

Analog Out 2 (spindle 2)

Page 273

Section 5A 9/440 Resolver- based CNC/Drive System

Connector

5A.4.4 Battery Backup

Description

Signal Destination

Analog Out

±10V Analog with no feedback

(typically spindle drive)

RET

Signal Return

(typically spindle drive)

SHLD shield connect at wiring board only

The memory for part programs, tool offset/compensation data, work coordinate offset data, etc... is stored on the processor board. In the case of a power failure, there is a super capacitor on the processor board that backs up this data for up to 5 days (at 40°C) on systems without extended program storage. This super capacitor re-charges within 1 hour of power turn on if completely discharged. If you want to extend this backup time install the lithium battery pack that supports the data for: 9/440 Resolver- based Memory Option:

Time (at 40°C Discharge):

standard

3 years with extended program storage

1 year

This battery pack is connected to the lithium battery connector (P1) on the wiring board as shown in Figure 5A.13. Batteries and the battery cable are included with the battery replacement kit. Figure 5A.13 Lithium Battery 9/440 Resolver- based System Module Connect the battery pack to P1 on the wiring board. Wiring Board

Mount the battery pack to the inside of the module cover.

P1 +

-

Press cover release to open

The lithium battery contains heavy metals and must be collected separately from other waste.

5A-27

Page 274

Section 5A 9/440 Resolver- based CNC/Drive System

5A.5 Power Terminal Block Connection

All external power connections to the 9/440 Resolver--based CNC/Drive are wired through the system modules power strip, located behind the front cover in the lower right corner. Input power is wired to this strip in two different voltages: 24 V Logic Power -- this is 24 volt AC or 24 volt DC. The logic power is used to operate the processors in the system module, axis module logic boards, and power the resolvers/encoders. Drive Power -- this is 324-528 V AC, three phase, 50/60 Hz. The drive power is used to supply the drive portion of the 9/440 resolver--based control the voltages necessary to power the axis modules and the servo motors. To this Power Strip Connector

Connect:

W1

+24 V Logic Power

W2

24 V Logic Power common

U, V, W

380/460V AC, three phase power (not phase sensitive)

PE

System Ground Bar

DC+, INT, COL

Shunt resistor connection. When the jumper exists between INT and COL the internal 200 W shunt is used. When using the optionally purchased 1000 W shunt the jumper is removed and the new shunt is installed between DC+ and COL.

All connectors on the power strip support a maximum of AWG 12 gauge solid wire.

5A-28

Page 275

Section 5A 9/440 Resolver- based CNC/Drive System

9/440 Resolver--based System Module

Wiring Board

Power Terminal Block

E- Stop Connections (TB1)

DC+

INT

COL

W1

W2

U

V

W

PE

3rd Encoder Port (J11)

5A.5.1 On/Off Control and 24V Logic Power

24 Volt logic power is supplied to the 9/440 resolver--based control to run the processor board and axis module logic boards. The 24 volts are provided from a customer supplied transformer. Specifications for this supply are:

Transformer Input Voltage

9/440 Resolver- based Input Voltage Range (Transformer Output)

125/240 V AC (85-265 V AC @50/60 Hz)

24V ac (19 - 28V ac, single phase @50/60 Hz) or 24V dc (18.75 - 31.25V)

Number of Axis Modules 1

2

3

4

3.5 A

4.4 A

5.2 A

6.0 A

On/Off connections are made through the Allen-Bradley On/Off Control assembly (8520-OFC). This assembly allows connection to the standard MTB panel on/off switch and should be used to supply power to your 24 V transformer.

5A-29

Page 276

Section 5A 9/440 Resolver- based CNC/Drive System

Figure 5A.14 On/Off Control Assembly

ALLEN- BRADLEY AC POWER

FUSE 8A/250V

L1 AC IN L2

Incoming AC Power 85--265 Volts AC

PE L1 AUX AC

Switched AC Out 85--265 Volts AC 8 amp max

L2 ON SW

COMMON

To MTB panel ON/OFF switch

OFF SW

Logic power should be wired so that if the 24 V is not available to the system module, it will open the drive contactors and disable 3 phase drive power (see Figure 5A.18).

5A-30

Page 277

Section 5A 9/440 Resolver- based CNC/Drive System

Figure 5A.15 Connecting On/Off Power Control Assembly and 24V Transformer

ALLEN- BRADLEY AC POWER FUSE 8A/250V

AC IN

AUX AC

Incoming Power 85- 265 V ac

9/440 Resolver- based Power Strip

Low High

To local cabinet ground bus

BT02 Monochrome or Color operator panel power supply

PE L1

DC+

L2 PE L1 4 amp max draw

L2 ON SW

COMMON OFF SW

U

COL

W1

W2

V

W

PE

Input 85-265 V ac ON COM

ON/OFF Control Assembly

INT

OFF

Customer supplied 24V transformer Output 24 V ac or 24 V dc non-polarized

E- Stop

15 AMP Customer Supplied Fuses

COM RESET

Noise suppressor

MTB Panel

ATTENTION: You must make sure logic power (24V) is applied to the system module and the system module is out of E--Stop before you allow 3 phase power to be enabled.

5A-31

Page 278

Section 5A 9/440 Resolver- based CNC/Drive System

If 24 V power is required for other devices in your machine system, you can use a 24 V power supply in place of the 24 V transformer as shown in Figure 5A.16. Figure 5A.16 Connecting On/Off Power Control Assembly and 24V Power Supply

ALLEN- BRADLEY AC POWER

To local cabinet ground bus

Incoming Power 85- 265 V ac

FUSE 8A/250V

9/440 Resolver- based Power Strip

Low High

BT02 Monochrome or Color operator panel power supply

PE L1

AC IN

DC+

L2 PE

Customer supplied 24V Power Supply

ON COM

Output 24 V ac or 24 V dc non-polarized

OFF

ON/OFF Control Assembly

U

COL W1

L1 AUX AC L2 ON SW COMMON OFF SW

INT

W2

V

W

PE

Noise suppressor 199-ISMAxx On Off Relay Bulletin 100 A30--Nxx

C C1

15 AMP Customer Supplied Fuses

E- Stop COM RESET

MTB Panel

5A.5.2 Drive Power 3 Phase

Three--phase power to the 9/440 resolver--based control must be 324-528 V AC, 50/60 Hz. The drive power is used to supply the drive portion of the 9/440 resolver--based control the voltages necessary to power the axis modules and the servo motors. All power connectors on the 9/440 Resolver--based power strip accept AWG 12 gauge solid wire. Refer to local codes for required wire type and gauge.

5A-32

Page 279

Section 5A 9/440 Resolver- based CNC/Drive System

Grounded vs Ungrounded Three Phase The 9/440 Resolver--based CNC/Drive comes from the factory set for three phase grounded systems. If your facility uses an ungrounded three phase 360/480 volt system, you must move a jumper in the 9/440 Resolver--based system module. This jumper will connect an internal resistor that helps keep high voltage static, that can be typical of ungrounded three phase systems, from building up in the system module. Jumper Setting

Three Phase Power

J27 to J26 (factory setting)

Grounded system

J27 to GND3

Ungrounded systems

GND3

J26

Wire Jumper

J27

Figure 5A.17 Three- phase Jumper

Open cover

9/440 Resolver--based System Module

5A-33

Page 280

Section 5A 9/440 Resolver- based CNC/Drive System

Figure 5A.18 Recommended Connection of 3- phase Drive Power 9/440 Resolver- based Power Strip

Bussman FRS- R- 20A (class RK-5) 600 V AC (qty 3)

DC+

INT

COL

W1

W2

U

V m3

PE m2

Three-phase input 360 or 480V AC m1 m

Bulletin 100 Contactor Power

AC Bulletin 100- A30N x 3 (surge protector required) or DC Bulletin 100- A30NZ x 3 Noise suppressor c1 c

Customer supplied 24V Power Supply Output 24 V ac or 24 V dc

Customer Supplied E--Stop Control Relay

E- Stop Connector TB1 7

Noise suppressor Customer Supplied Fuse

5A-34

W

Other Customer Controlled E--Stop Status Relays

E- Stop status contact (30V dc 1.4A)

1