Page 341
Section 6 Emergency STOP Design
6.2 E-Stop String
The E-Stop string begins at the E-Stop connector, then may contain: remote E-Stop pushbutton(s) whose contacts open when the button is pushed to cause E-Stop. axes overtravel limit switches whose contacts open when an axis travels over the switch. auxiliary machine fault detection equipment whose contacts open when an auxiliary device fails. contacts associated with the servo drives that open when a fault condition occurs in the drive. contacts associated with the spindle that open when a fault condition occurs. motor over temperature (thermal) sensors that cause the E-Stop string to open when they sense an over temperature condition. The E-Stop string terminates on one side of the 12 V dc relay coil. The opposite side of the coil connects to the supply common through a software-controlled E-Stop request transistor. This permits the coil to be energized when there is series continuity through the E-Stop string. ATTENTION: The E-Stop button is designed to be used in emergency situations to protect equipment or personnel. Make sure that it performs properly by wiring the E-Stop string with the following considerations: 1.
The E-Stop string must be hardwired and working before enabling drives. This provides a safe and reliable way of de-energizing the drives if an E-Stop condition should occur when the drives are enabled.
2.
Current always flows through the string when there is no E-Stop condition. This makes sure that the control will go into E-Stop should a wire be broken.
3.
Triggering the E-Stop string should be exclusively a hardware function that can be monitored or induced by software, but never dependant on software. This makes sure that a software failure or loss of logic power does not prevent an E-Stop condition.
4.
Do not use devices on the fiber optic ring to trigger E-Stop.
6-5
Page 342
Section 6 Emergency STOP Design
6.3 E-Stop Status
Use the contact on TB1-6,7 in the E-Stop string for status control of peripheral machine tool devices, such as: alarms emergency braking devices (9/440 systems refer to page 5B-34) axes drive equipment coolant pumps remote status indicators spindle drive Table 6.A Contact Ratings, 9/230, 9/440, 9/260, and 9/290 E-Stop Relay (K1)
6.4 Events When E-Stop Occurs
Item
Rating
Max. Allowable Power (resistive load)
30W
Max. Allowable Voltage
30 Vdc
Max. Allowable Current
1.4A
When E-Stop occurs: the position loop is disabled and issues no motion commands the following error is cleared part program execution stops it is the OEM’s responsibility to assure that the axes decelerate appropriately Important: Note that E--Stop condition is not the same as a power loss condition or a hardware failure.
Controlled Stop on E-Stop The controlled stop on E--Stop feature is used for servo systems that use the 9/Series to close the velocity loop on these servo hardware platforms: 9/440 systems 9/260 and9/290s that use the 8520-ENC4 or 8520-SM4 9/230’s connected to the 8520 or 1394 digital drive interface. Important: The controlled stop feature, as described in this section, is only available on standard systems using a system executive of 10.02 or higher (some custom executives may not support controlled stop on E--Stop) and have the appropriate servo hardware. The controlled-stop feature can be used in conjunction with your own machine-braking system to help decelerate or hold axes in position when an E--Stop event occurs.
6-6
Page 343
Section 6 Emergency STOP Design
On systems that support the controlled-stop feature, the velocity loop remains enabled and the velocity command is reduced exponentially to zero after an E-Stop occurs. This results in the velocity loop attempting to bring the motor to a stop and/or hold it steady. After 2 seconds, the controls software disables the velocity loop. The control will also maintain the axis/drive enable signal to 1394 and 8520 digital servo amplifiers for this 2 second interval after E--Stop. The commands sent to the drive (torque commands) are limited by the torque limits defined for the axis in AMP (“MAXIMUM PERCENT RATED TORQUE...”). Important: If problems (such as amplifier faults) occur from overcurrent conditions caused during a worst case E-Stop (E--Stop during rapid move), you must reduce the AMP configured maximum percent rated torque limits. ATTENTION: We strongly recommend that the high-voltage input to the amplifiers be disconnected by a contactor when the E-Stop string opens. As a result of this power loss to the drive, the only current available to the drive to bring the motor to a stop and hold it is the residual bus energy stored in the drives. The velocity loop from the control will attempt to stop and hold the axes for 2 seconds after an E-Stop occurs. The amount of time the drive system can actually pull current from the motor to bring the axis to a stop and hold it in position varies depending on machine factors (e.g., the size of the motor, the speed at which it is traveling or its static load, and the amplifier size)
Resetting E-Stop Once the cause of the error has been corrected, press E-Stop reset. the E-Stop string will reset and return system control to system software. depending on the value of the AMP parameter Control Reset on E-Stop Reset, the control will either execute a control reset, which returns the part program pointer to the top of the program, or leaves the pointer at the block being executed when the E-Stop occurred. END OF SECTION
6-7
Page 344
Section 6 Emergency STOP Design
6-8
Page 345
Publication 8520-6.2.6 - August 1997
Page 346
I--2
Index
9/Series, PAL, PLC, SLC 5/03, SLC 5/04, DH+, and INTERCHANGE are trademarks of Allen-Bradley Company, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation. Argentina ·Australia ·Austria ·Bahrain ·Belgium ·Brazil ·Bulgaria ·Canada ·Chile ·China, PRC ·Colombia ·Costa Rica ·Croatia ·Cyprus ·Czech Republic · Denmark ·Ecuador ·Egypt ·El Salvador ·Finland ·France ·Germany ·Greece ·Guatemala ·Honduras ·Hong Kong ·Hungary ·Iceland ·India ·Indonesia · Ireland ·Israel ·Italy ·Jamaica ·Japan ·Jordan ·Korea ·Kuwait ·Lebanon ·Malaysia ·Mexico ·Netherlands ·New Zealand ·Norway ·Pakistan ·Peru · Philippines ·Poland ·Portugal ·Puerto Rico ·Qatar ·Romania ·Russia- CIS ·Saudi Arabia ·Singapore ·Slovakia ·Slovenia ·South Africa, Republic ·Spain · Sweden ·Switzerland ·Taiwan ·Thailand ·Turkey ·United Arab Emirates ·United Kingdom ·United States ·Uruguay ·Venezuela ·Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 8520-6.2.6 - August 1997 Publication 8520-6.2.6 - August 1997
PN176274 Copyright 1998 Allen-Bradley Company, Inc. Printed in USA
Page 347
9/Series Hardware TAB 7
Making Cables and Noise Prevention Techniques
1
1
3
3
10
15
2
2
9
14
5
5
12
17
4
4
11
16
6
6
13
18
8
20
14
19
7
7
N.C.
N.C. 8
Shield RDA RDB SDA SDB CSA CSB RSA RSB DMA DMB TRA TRB GND RRA
Belden 9507 - 24 Gauge
852062--RM007A--EN--P -- November 2000
PN--176960
Page 348
Page 349
Section
7A
Cable Diagrams
7A.0 Connecting the Components and Modules
The following sections contain information to be used when connecting the modules and components. Included is information on intermodule connections, maximum cable lengths, cable types, and connector types. For detailed information on a specific connector, refer to the section that covers the module on which the connector is located. ATTENTION: Electrostatic discharge can degrade performance or damage the system components. Observe the following precautions to guard against such damage: Touch a grounded object to eliminate static discharge from your body before handling any of the components. It is also recommended practice to wear a wrist strap (such as Allen--Bradley cat. no. 8000-ESD) that provides a low resistance path to ground. Do not touch the connectors or the connector pins. Do not touch other circuit components when you are setting switches or jumpers. If available, use a static-safe workstation. Keep the components that are packaged in static-shield bags in their bags when they are not used. For more information about electrostatic discharge and how to guard against it, refer to publication 8000-4.5.2, Guarding Against Electrostatic Damage: Using the ESD Kit.
7A.1 System Cabling Diagrams
The internal system connection diagram is shown in the following figures. The intermodule and intercomponent connections and their corresponding cables and connectors are covered in the following section.
7A-1
Page 350
Section 7A Connecting Components
Figure 7A.1 9/260 & 9/290 CNC’s System Connection Diagram External E-Stop 1
Main Power Supply
2 ac power source 25
3 6 4
28
Port A (RS-232)
5
26 17 Scanner
Operator Panel or ROPI assembly
9 Remote I/O Port
10
9/260 or 9/290
Port B (RS-232/ RS-422)
MTB Panel
8
7
27
MTB I/O
10
10
10
11
29
Fast I/O
12
12
Battery
12
13 10
10
Servo Module (third) 9/290 0nly 1746 I/O
10
10
High Density I/O
HPG
Digital I/O
Analog I/O
Servo Module (first) 15
AB supplied cables
32
16 30
33
34
35
31
Customer supplied cables Optical signal cable Terminal type connection
Servo Module (second)
Machine
Machine
Machine 115/230V ac 24V dc
24V dc
115/230V ac 24V dc
115/ 230V ac
Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the system I/O ring. Refer to the 9/Series 9/230, 9/260, and 9/290 PAL Reference Manual, publication 8520-4.3, for more information.
7A-2