Page 331
Section 5B 9/440HR CNC/Drive System
System Grounding Figure 5B.23 illustrates the recommended 9/440HR grounding scheme. All grounds terminate on a single point. Note there are two separate ground wires going to the system module. One ground connects to PE of the system module power terminal block, the other connects to the ground stud found just beneath the wiring board on the mounting bracket for the 9/440HR CNC assembly.
9/440HR System Module
Power Terminal Block 9/440HR CNC Assembly PE Stud
Open cover
DC+
COL
INT
W1
W2
U
V
W
PE
PE Power Terminal Block Ground
5B-41
Page 332
Section 5B 9/440HR CNC/Drive System
Figure 5B.23 System Grounding Diagram for 9/440HR Control Encoders
Machine Tool
Earth GND (typically AWG 8)*
Analog I/O
Chassis GND (typically AWG 10)*
Encoder input output
Chassis GND (typically AWG 12)* Signal GND
Servo Motor
Digital I/O (dc)
GND through mounting
Servo Motor
Spindle Motor
Potential Earth (PE) (typically AWG 8)* * Refer to local standards and codes for wire sizing.
Operator Cabinet
Drives Cabinet
PE
Operator Panel (see below)
9/440HR CNC/Drive
Chassis GRND Stud
System Module
PE MTB Panel
Ground Stud on 9/440HR CNC Assembly
Chassis GRND Stud
Axis Modules (PE1)
PE on Power Supply
MTB Panel I/O Module Spindle Drive HPG
Component Enclosure High Density I/O
Single point GND
Transformer
Digital I/O (ac) PE
RS-422 or RS-232 Terminal PE
PE Chassis GRND Stud
Color Operator Panel Color CRT
Keyboard Interface
Operator Panel Power Supply
Monochrome CRT
Keyboard Interface
Operator Panel Power Supply
END OF SECTION 5B-42
Chassis GRND Stud
Monochrome Operator Panel
PE
Portable Operator Panel Interface Assembly Operator Panel Interface Module
Keyboard interface
Operator Panel Power Supply
Chassis GRND Stud
Page 333
Publication 8520-6.2.5 - August 1998
Page 334
I--2
Index
9/Series, PAL, PLC, SLC 5/03, SLC 5/04, DH+, and INTERCHANGE are trademarks of Allen-Bradley Company, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation. Argentina ·Australia ·Austria ·Bahrain ·Belgium ·Brazil ·Bulgaria ·Canada ·Chile ·China, PRC ·Colombia ·Costa Rica ·Croatia ·Cyprus ·Czech Republic · Denmark ·Ecuador ·Egypt ·El Salvador ·Finland ·France ·Germany ·Greece ·Guatemala ·Honduras ·Hong Kong ·Hungary ·Iceland ·India ·Indonesia · Ireland ·Israel ·Italy ·Jamaica ·Japan ·Jordan ·Korea ·Kuwait ·Lebanon ·Malaysia ·Mexico ·Netherlands ·New Zealand ·Norway ·Pakistan ·Peru · Philippines ·Poland ·Portugal ·Puerto Rico ·Qatar ·Romania ·Russia- CIS ·Saudi Arabia ·Singapore ·Slovakia ·Slovenia ·South Africa, Republic ·Spain · Sweden ·Switzerland ·Taiwan ·Thailand ·Turkey ·United Arab Emirates ·United Kingdom ·United States ·Uruguay ·Venezuela ·Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 8520-6.2.5 - August 1998 Publication 8520-6.2.5 - August 1998
PN176439 Copyright 1998 Allen-Bradley Company, Inc. Printed in USA
Page 335
O® Rockwell Automation
Allen-Bradley
9/Series Hardware TAB 6
Emergency STOP Design
8520-6.2.6 - August 1997 PN-176274
Page 336
4
Page 337
Section
6
Emergency Stop Design
6.0 Section Overview
Emergency stop (E-Stop) is a function of the control that disables all axis and spindle drives if a major anomaly is detected. To guard against damage to the machine and injury to personnel, the system installer must make the necessary E-Stop connections to the proper terminals on the control components. E-Stop is required to safely de-energize the axes and spindle drives and place all I/O in a safe state (including motor brakes) when an Emergency Stop condition occurs. ATTENTION: All axis and spindle drives must be disabled by the emergency stop. Otherwise uncontrolled axis motion may cause injury to personnel and/or damage to the machine tool.
This section describes connections that must be made to help the control detects emergency situations and responds appropriately. Topics covered include: E-Stop Connections E-Stop String Events when E-Stop occurs
6-1
Page 338
Section 6 Emergency STOP Design
6.1 E-Stop Connections
Connect the emergency stop circuit to the pluggable E-Stop connector on as illustrated in Figure 6.1. Figure 6.1 E-Stop Component Connection Pluggable E-Stop Connector (TB1 ) E-Stop reset button
E-Stop status relay
E-Stop button
CR
1 E-Stop On MTB panel
2 Common 3 Reset 4
Customer E-Stop string E-Stop status relay contact connection
5 CR
+ customer supplied fuse (size to protect K1b contact and your E-Stop status relay)
6 7 8
If your control has, terminal 8, then connect it to chassis ground. If terminal 8 is not present on your control, then this type of grounding is not necessary.
Figure 6.2 shows a typical emergency stop circuit. This varies depending on machine tool configuration, and the devices implemented by the system installer.
6-2
Page 339
Section 6 Emergency STOP Design
Figure 6.2 Typical Emergency Stop Circuit Reset button
MTB PANEL
Motherboard/Processor Board
E-Stop button
1
250mA 15 V dc from main power supply
Reduced to 12 V dc filter
2 K1A
3
MACHINE Remote E-Stop button
Extreme overtravel switches
4
Drive System Ready
5
Software
CR controlled Motor thermal switches may be connected directly
DRIVES ENCLOSURE
-
E-Stop status relay
CR
Customer-supplied dc power
+
SYSTEM INSTALLER OPTIONS
E-Stop
6
7 circuit
K1B common
E-Stop relay K1 12 V dc coil Contact ratings: 30 V dc 1.4 A customer supplied fuse (size to protect K1b contact and your E-Stop status relay)
Contactors for E-Stop status controlled devices (servo amp contactor, indicators, brakes, coolant pumps, etc.)
8
Important: Connections to all pins on the 9/Series E- Stop terminal are DC only. AC connection to any of these terminals can cause damage to your 9/Series CNC.
If your control has terminal 8, connect it to chassis ground. If terminal 8 is not present on your control, then this type of grounding is not necessary.
Important: We recommend that all contactors used on the 12V E-Stop string are rated for use at low level operation (dry circuit contactors). This may increase initial expense of the circuit but will provide more reliable E-Stop string operation over time. Use of non-dry E-Stop devices may result in nuisance E-Stop faults or failure to establish a closed circuit when the E-Stop reset push button is closed. Corrosion build-up on non-dry contactors are not cleaned by the control’s operation. Dry contactors are more immune to corrosive effects. If non-dry contactor devices are used as elements of the E-Stop string, we recommend the use of a pilot relay in conjunction with a customer-supplied power supply operating independent of the control’s 12 Vdc string. Select a pilot relay with a dry contact rated for use in the E-Stop string.
6-3
Page 340
Section 6 Emergency STOP Design
Important: You may need to add a pilot relay if your E-Stop has one of these characteristics: the E-Stop string is very long devices on the string cause a such a large line drop in the string that the E-Stop relay will not latch. In these cases, the control may: not come out of E-Stop enter E-Stop at different times during operation when the E-Stop string voltage varies slightly If your application requires a separate E-Stop pilot relay, you must provide an external power supply to power the E-Stop string. The contactors of this pilot relay are used to break the controls 12V E-Stop string. A typical layout for this E-Stop string is shown in Figure 6.3. ATTENTION: E-Stop wiring with a pilot relay requires circuit continuity for normal operation (a customer’s E-Stop string should be a normally closed circuit). Loss of power to the external power supply should constitute an E-Stop condition. Failing to do this may cause injury to personnel or damage to the machine tool.
ATTENTION: Contact ratings on the control are DC only.
Figure 6.3 Typical Customer E-Stop String with Pilot Relay E-Stop connector (TB1) on Motherboard for 9/260 or 9/290 and on the processor board for the 9/230
MACHINE Extreme overtravel switches
Remote E-Stop button
4
CR Motor thermal switches may be connected directly
DRIVES ENCLOSURE
6-4
Drive System Ready, (DROK TB1 on 1394) (internally Connected on 9/440)
Customer Supplied External Power Supply for E-Stop String
Pilot Relay
5
6
11250-I