For the Allen-Bradley 8500-1746I

Page 321

Section 5B 9/440HR CNC/Drive System

Logic power should be wired so that if the 24 V is not available to the system module, it will open the drive contactors and disable 3 phase drive power (see Figure 5B.20). Figure 5B.17 Connecting On/Off Power Control Assembly and 24V Transformer

ALLEN- BRADLEY AC POWER FUSE 8A/250V

AC IN

AUX AC

To local cabinet ground bus

Incoming Power 85- 265 V ac

9/440HR Power Strip

Low High

BT02 Monochrome or Color operator panel power supply

PE L1

DC+

L2 PE L1 4 amp max draw

L2 ON SW

COMMON OFF SW

U

INT

W1

W2

V

W

PE

Input 85-265 V ac ON COM

ON/OFF Control Assembly

COL

OFF

Customer supplied 24V transformer Output 24 V ac or 24 V dc non-polarized

E-STOP

15 AMP Customer Supplied Fuses

COM RESET

Noise suppressor

MTB Panel

ATTENTION: You must make sure logic power (24V) is applied to the system module and the system module is out of E-STOP before you allow 3 phase power to be enabled.

5B-31

Page 322

Section 5B 9/440HR CNC/Drive System

If 24 V power is required for other devices in your machine system, you can use a 24 V power supply in place of the 24 V transformer as shown in Figure 5B.18. Figure 5B.18 Connecting On/Off Power Control Assembly and 24V Power Supply

ALLEN- BRADLEY AC POWER

To local cabinet ground bus

Incoming Power 85- 265 V ac

9/440HR Power Strip

Low High

BT02

FUSE 8A/250V

PE

Monochrome or Color operator panel power supply

U

COL INT DC+

L1 AC IN

L2 PE

W1

L1 AUX AC L2 ON SW COMMON OFF SW

Customer- supplied 24V Power Supply

ON COM OFF

ON/OFF Control Assembly

Output 24 V ac or 24 V dc non-polarized

W2

V

W

PE

Noise suppressor 199-ISMAxx On Off Relay Bulletin 100 A30--Nxx

C C1

15 AMP Customer- supplied Fuses

E-STOP COM RESET

MTB Panel

5B.5.2 Drive Power Three- phase

Three--phase power to the 9/440HR must be 324-528 V AC, 50/60 Hz. The drive power is used to supply the drive portion of the 9/440HR the voltages necessary to power the axis modules and the servo motors. All power connectors on the 9/440HR power strip accept AWG 12 gauge solid wire. Refer to local codes for required wire type and gauge.

5B-32

Page 323

Section 5B 9/440HR CNC/Drive System

Grounded vs Ungrounded Three- phase The 9/440HR CNC/Drive comes from the factory set for three--phase grounded systems. If your facility uses an ungrounded three--phase 360/480 volt system, you must move a jumper in the 9/440HR system module. This jumper will connect an internal resistor that helps keep high voltage static, that can be typical of ungrounded three phase systems, from building up in the system module. Jumper Setting

Three Phase Power

J27 to J26 (factory setting)

Grounded system

J27 to GND3

Ungrounded systems

GND3

J26

Wire Jumper

J27

Figure 5B.19 Three- phase Jumper

Open cover

9/440HR System Module

5B-33

Page 324

Section 5B 9/440HR CNC/Drive System

Figure 5B.20 Recommended Connection of Three- phase Drive Power 9/440HR Power Strip

Bussman FRS- R- 20A (class RK-5) 600 V AC (qty 3)

COL W1 DC+ INT W2

U

V m3

W PE m2

Three-phase input 360 or 480V AC m1 m

Bulletin 100 Contactor Power

AC Bulletin 100- A30N x 3 (surge protector required) or DC Bulletin 100- A30NZ x 3 Noise suppressor c1 c

Customer supplied 24V Power Supply Output 24 V ac or 24 V dc

Customer Supplied E-STOP Control Relay

E-STOP Connector TB1 7

Noise suppressor Customer Supplied Fuse

Other Customer Controlled E-STOP Status Relays

E-STOP status contact (30V dc 1.4A)

1

ATTENTION: Brake control should not be directly released by the E-STOP status relay (or your customer supplied E-STOP control relay). Brakes should only be released by the PAL logic when it has determined that the 9/440HR is in full control of the servo motors and the control is out of E-STOP. See the description of the PAL flag $PFLT.15 for detail on how to test drive status.

5B-34

Page 325

Section 5B 9/440HR CNC/Drive System

5B.6 Connecting Axis Modules

The Axis Module provides terminating points for the motor power, thermal sensor and brake. Axis module wiring is identical for all module ratings. Refer to Figure 5B.21 and the paragraphs that follow for detailed information. Figure 5B.21 Axis Module Connections

U1

V1

W1 PE2 PE1 PE3

TB1 and TB2 (Located on Bottom of Module)

Motor Wiring Allen-Bradley 1326-CPB1xxx cables must be used for connection to the motor. The motor wiring size is determined by the continuous and overload current requirements (RMS Duty Cycle), NEC and local codes. In general, motors operated with the 1394 should not require wire sizes larger than those accepted by the motor terminal blocks. In addition, the motor leads must be twisted throughout their entire length to minimize radiated electrical noise. The maximum motor wire sizes that the 1394 Axis Module terminal block will accept are dependent upon axis module selection (see your 1394 users manual).

5B-35

Page 326

Section 5B 9/440HR CNC/Drive System

See page 5B-12 for details on high--resolution feedback device cables (1326-CECU--x). 1326AB servo motors have integral thermal protection. This contact must be connected in the E-STOP string for motor overload protection. Connections are performed through the front panel terminal block as shown in Figure 5B.21. Refer to the information below and the Interconnect Drawings on page 5B-40 for further information. Table 5B.B Motor Power Terminations Terminal

Description

Wire/Pin Number

U1

Motor Power A

1

V1

Motor Power B

2

W1

Motor Power C

3

PE1

Axis Ground

Ground Bar

PE2

Motor Ground

8

PE3

Overall Shield

7

Thermal and Brake Leads The motor thermal sensor and brake leads (if used) are connected to the Axis Module at TB1 & TB2. See Figure 5B.21 for location and Table 5B.C for terminations.

5B-36

Page 327

Section 5B 9/440HR CNC/Drive System

Table 5B.C Thermal Sensor and Brake Terminations Terminal

Description

Wire/Pin Number

TB1-1, 2

Thermal Sensor Input from Motor Cable string axis modules

TB1-3, 4

Brake 24V DC Input from Motor Cable user brake

TB2-1, 2

Brake 24V DC To Brake Control

5, 9

TB2-3, 4

Thermal Sensor Output to Fault System

4, 6

TB1 All Axis modules

Axis Module

6

(applying 24V DC releases brake)

TB2 Axis module 1

Brake

TB2 Axis module 2

User Brake Control Thermal String (connect to E-STOP String)

4 5

9

Motor

Thermostat

TB2 Axis module 3

User Brake Control

TB2 Axis module 4

User Brake Control

User Brake Control

ATTENTION: Brake control should not be directly released by the E-STOP status relay (or your customer supplied E-STOP control relay). Brakes should only be released by the PAL logic when it has determined that the 9/440HR is in full control of the servo motors and the control is out of E-STOP. See the description of the PAL flag $PFLT.15 for detail on how to test drive status.

5B-37

Page 328

Section 5B 9/440HR CNC/Drive System

5B.7 9/440HR LEDs

9/440HR CNC/Drive has 4 LEDs on the system module and one LED on each axis module in the system. The LEDs operate as follows. System Module LEDs The system module has 4 LEDs. They are: LED

Indicates

XILINX

Under normal operation this LED is on. If it turns off while the system module is under power it indicates a XILINX hardware fault. Contact your local Allen- Bradley Service.

WATCHDOG

Under normal operation this LED is on. If it turns off while the system module is under power it indicates the watchdog has timed out and a processor failure has occurred. Contact your local Allen-Bradley Service.

R- I/O

Only available on systems with remote I/O. This LED illuminates when the remote I/O link is communicating. See page 5B-27.

STATUS

This is identical to the Watchdog LED but is visible through the system modules front cover.

9/440HR System Module

Wiring Board

XILINX

Press Cover Release to Open Open Cover

WATCHDOG

Status LED

R-I/O LED (visible from under system module in front of serial port B)

Check your 9/Series CRT for any drive faults that may have occurred and are displayed as an error. 5B-38

Page 329

Section 5B 9/440HR CNC/Drive System

Axis Module LEDs The Axis module has a Status LED visible thru the front cover. It is: LED

Indicates

STATUS

Steady Green Flashing Green Flashing Red/Green Flashing Red Steady Red bus up, axis enabled bus up, axis not enabled ready, bus not up fault present hardware malfunction

For more details on how to diagnose and troubleshoot your axis module refer to the 1394 Digital AC Multi-Axis Motion Control System Users Manual (publication 1394-5.0)

5B.8 General Wiring Overview

The following figure shows a typical interconnect diagram for a 9/440HR CNC to 1326AB motors. Note this figure illustrates only one servo motor with optional feedback encoder. The 9/440HR CNC can support up to four servo’s and two spindle drives.

5B-39

Page 330

Section 5B 9/440HR CNC/Drive System

Figure 5B.22 Wiring Overview For 9/440HR CNC Processor Board

Fiber Optic I/O Ring

TB1

Video Port

J8

Serial Port B

J7

Serial Port A

J6

1 2 3 4 5 6 7

MTB E-Stop Connections External Customer E-Stop String

M1

E-STOP Status String

1394 Axis Module

Analog Out 1

Analog Out 2

Remote I/O

1 2 3 4 5 6

TB2 Wiring Board

1 2 3

RIO1 TB4

Thermostat and Brake Feedthru

TB1 TB3

U1 V1 W1 PE1 PE2 PE3 4 3 2 1 TB5

SHLD

1 2 3 4

1

Touch Probe

M1 M1 M1 Three-phase input 360-480V AC

DC+ COL INT W1 W2 U V W PE

To Cabinet Ground Bar Ground Stud

5B-40

3

8

T1 T2 T3

7

GND

6

4

5

9

B2 B1 K2 K1

4 3 2 1 To next axis and User Brake Control Input

Brake

9/440HR System Module

User- supplied 24V AC or 24V DC (non-polarized), 15A

2

RIO2

9/440HR Power Supply

TB2

Feedback Board Encoder Inputs J1, J2, J3, or J4

Encoder Inputs J9, J10, J11, or J12

Servo Motor 3 2 11 12 10 8 9 7 6 5 4 1 1 12 11 9 78 6 5 3 2 15 16

A B C D

Thermostat

Ground Bar

Encoder

E F G H I J G A H I B C J D F

1326AB Motor

AB 845H Encoder