Page 421

Section 7C Power Distribution and Wiring Guidlines

Figure 7C.1 Shielded Twisted-pair Cables Exposure of the signal cables must be minimal

C

A

Twisted pair

B

Cable shielding

Signal source

Signal destination C

PE

A

C

C

B

B Connect the cable shielding through a terminal block

A

C

Differential input

B DO NOT connect the cable shielding to ground at the signal destination

11237-I

When parallel wires are used for carrying control signals, if distances between the noise source and the individual cables differs, one of these two wires will be subject to stronger radiation noise than the other. However, when a twisted--pair cable is used, both wires will be subject to equal radiation noise regardless of the position of the noise source. This means that equal noise voltage is applied to both of the differential input terminals. Thus, the noise applied to the two terminals will cancel each other and reduce the drive circuit noise. Usually, twisted-pair shielded cables as illustrated in Figure 7C.1 are used to transmit weak signals such as drive signals and feedback signals.

Separation of Cable Routes Route cables with high power and low power levels (voltages and/or currents) separately. Run cables along opposite sides of the cabinet to minimize the influence of magnetic and electromagnetic induction noises. Install steel sheet metal wireways between machine application cabinets. Do not use aluminum or other non-ferrous wireways as they do not provide magnetic shielding for the cables. Do not use dissimilar metals as this may lead to noise buildup. In wireways, bundle wires loosely into groups according to similar power levels and functions. Do not run cables carrying weak signals such as drive signals and feedback signals in parallel with the ac power cables and I/O cables. If they must be run in parallel with each other, pass the weak signal carrying cables in metallic conduit to protect them from the influence of magnetic and 7C-3

Page 422

Section 7C Power Distribution and Wiring Guidelines electromagnetic noise. If there is no electric conductivity between the metallic conduit and the frame or the cabinet, connect them using a conductor. Important: Run cables carrying weak signals inside metallic conduit whenever possible. Do not use the metallic conduit as the grounding connection for the frame or the cabinet. Use an exclusive conductor for grounding. Figure 7C.2 Cable Routing AC power

AC power

Discrete I/O

Machine connections panel

Feedback

Machine cable conduits

Application power distribution panel

Customer AC power

Motor power

Axis signals

9/230, 9/260, or 9/290 controller cabinet

Recommended steel dividers

Drive command

Axis drive cabinet 11238-I

Noise Suppressors To prevent noise in the ac power line on the power receiving side (controller side), connect a filter or transformer as shown in Figure 7C.3.

7C-4

Page 423

Section 7C Power Distribution and Wiring Guidlines

Figure 7C.3 Non-Isolated Conductive Type Noise Suppressing LC Filter

L

L C C

L

PE L

RC Noise Suppressor

C R R

PE

C 11239-I

Figure 7C.4 Isolated Insulation Type Noise Suppressing

Isolation Transformer

Noise Cutting Transformer

Shielded Transformer

11240-I

These noise filters and isolation transformers have different effects depending on noise characteristics (common mode noise, normal mode noise, high frequency noise, low band width noise, high band width noise, etc.). Therefore, select the appropriate noise suppression parts meeting the noise characteristics. Install these parts as close to the controller as possible for them to be most effective.

7C-5

Page 424

Section 7C Power Distribution and Wiring Guidelines

Figure 7C.5 Location of Noise Suppressors +V

Noise Source

YES

Noise Filter PE

Suppressor close to source, transient current does not circulate through the cables

+V

Noise Source

NO

Noise Filter PE

Transient current circulates through the cables and generates interference

11241-I

Spike Voltage Noise Suppression Spike voltage is generated when contacts in an inductive circuit open. To reduce spike voltage, connect a noise suppressor in parallel with the load. This suppresses spike voltage as shown in Figure 7C.6. This also prevents arcing between the contacts due to spike voltage, thereby protecting both the contacts and the internal circuit of the solid state output. Figure 7C.6 Spike Voltage Noise Suppressing Noise Suppressor 100V ac

SW

100 mH Inductive Load switch opened 141v p

Voltage waveform

4.5A p Current waveform 11242-I

-4.5A

7C-6

Page 425

Section 7C Power Distribution and Wiring Guidlines

Inductive Load Noise Suppression Select the noise suppressor according to load size and applied voltage. Connect the noise suppressor as close to the load as possible. For a small ac inductive load, such as a solenoid operated by a pushbutton switch or a limit switch, connect the RC circuit as shown in Figure 7C.7. Figure 7C.7 Small AC Inductive Load

Small AC inductive load voltage Load

C

R

11243-I

For a large ac inductive load, such as a motor operated by a contactor, connect a varistor in parallel with the RC circuit as shown in Figure 7C.8. Figure 7C.8 Large AC Inductive Load

Large AC inductive load voltage Load

C

Varistor

R

11244-I

7C-7

Page 426

Section 7C Power Distribution and Wiring Guidelines

For a three-phase ac inductive load, connect noise suppressors across the individual phases as shown in Figure 7C.9. Figure 7C.9 Three-phase AC Inductive Load

C C

R

C

R

3-phase AC inductive load

R

11245-I

For a small DC inductive load, such as a miniature relay operated by a switch, connect the diode as shown in Figure 7C.10. The diode must have a peak voltage rating higher than two times that of the applied voltage. Figure 7C.10 Small DC Inductive Load

Small DC inductive load voltage Load

Diode 11246-I

Devices used for surge protection should be connected as close to the load device as possible. When Allen-Bradley relays, contactors, and motor starters are used, refer to Table 7C.A. 7C-8

Page 427

Section 7C Power Distribution and Wiring Guidlines

Table 7C.A Allen-Bradley Surge Suppressors Device

Coil Voltage

Surge Suppressor Catalog No.

Bulletin 509 Motor Starter Bulletin 509 Motor Starter

120V ac 240V ac

599- K04 5990KA04

Bulletin 100 Contactor Bulletin 100 Contactor

120V ac 240V ac

199- FSMA1 199- FSMA2

Bulletin 709 Motor Starter

120V ac

1401- N10

Bulletin 700 R, RM Type Relay ac coil

(surge suppressor not required)

Bulletin 700 R Type Relay Bulletin 700 RM Type Relay

12V dc 12V dc

700- N22 700- N28

Bulletin 700 R Type Relay Bulletin 700 RM Type Relay

24V dc 24V dc

700- N10 700- N13

Bulletin 700 R Type Relay Bulletin 700 RM Type Relay

48V dc 48V dc

700- N16 700- N17

Bulletin 700 R Type Relay Bulletin 700 RM Type Relay

115- 125V dc 115- 125V dc

700- N11 700- N14

Bulletin 700 R Type Relay Bulletin 700 RM Type Relay

230- 250V dc 230- 250V dc

700- N12 700- N15

Bulletin 700 N, P Type Relay

150V MAX. ac

700- N24

Electromagnetic device whose sealed power is limited to 35 VA.

150V max. ac or dc

Typical surge protection circuit examples are shown in Figure 7C.11. Figure 7C.11 Surge Protection Circuits for Inductive Load Inductive output device

Inductive output device

Varistor

RC circuit

DC inductive load

AC inductive load

Diode

Surge suppressor

11247-I

7C-9

Page 428

Section 7C Power Distribution and Wiring Guidelines

7C.2 Reducing Noise

The following sections explain different types of noise and measures to reduce them.

Electrical Noise Electrical noise can be considered to be unwanted electrical signals, which produce undesirable effects in the circuits of the control systems in which they occur. High intensity noise can interfere with system functioning. The following sections explain electrical noise and the measures to reduce them. Electrical noise is transmitted in two ways. One means of transmission is through cables (conducted noise). The other is transmission through the air (radiated noise). Figure 7C.12 Noise Transmission Routes

Radiated noise

Source

Conducted noise

Destination

Wire or cable 11233-I

Conducted Noise Conducted noise is transmitted to the control through conductors such as power source cables, signal cables, and grounding cables. Conducted noise is further divided into two modes; normal mode and common mode. As shown in Figure 7C.13, normal mode noise reaches the control by passing through the two lines. Common mode noise reaches the control by passing through each line and the conductor that functions as the common potential for the two lines.

7C-10

Page 429

Section 7C Power Distribution and Wiring Guidlines

Figure 7C.13 Types of Line Noise

9/Series control

Noise source

Power source 9/Series control Noise source

Power source

PE

PE

A. Normal mode noise

B. Common mode noise

11234-I

Electrical noise varies in waveforms and magnitude over the entire frequency width. Typical examples of abnormal phenomenon and waveforms observed in the power source line are shown in Figure 7C.14. Figure 7C.14 Abnormal Voltage Waveform

Slow voltage fluctuation

Sharp voltage fluctuation

Flicker

Higher harmonic

Voltage spike

High frequency noise

One of the sources of electrical noise is a sharp current variation in inductive circuits, as shown in the circuit of Figure 7C.15. In this circuit, voltage VL applied to the inductive load L (a relay coil, for example) is equivalent to the voltage applied to the circuit while the switch SW is closed. If this switch is opened, the inductive load that prevents current variation, generates a momentary high voltage called a “spike”. 7C-11

Page 430

Section 7C Power Distribution and Wiring Guidelines

Figure 7C.15 Spike Voltage 100V ac (rms) Arc Inductive Load (528V) 100V ac

L

100mH SW

141 V peak

VL

0 Volts

90°

IL dt = 0.7ms

3.71A peak 0 Amps di = +3.71A -3.71 A

11236-I

Radiated Noise Radiated noise reaches the control through the air. The cables and the metallic frames, of the control, function as antennas that receive electrical noise from a variety of sources such as ac power lines, welding arcs, transformers, motors, and radio wave transmission devices. If a number of electronic components are arranged near the control, the surrounding air will be filled with radiated noise. The control must be shielded to protect it from radiated noise. Radiated noise is composed of three types of noise: electrostatic induction noise magnetic induction noise electromagnetic induction noise END OF SECTION

7C-12