9/Series CNC Hardware Integration and Maintenance Manual, pages 411 to 420

Pages 411 to 420 of 898

The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 8500-1746I

Page 411

Section 7A Connecting Components

Table 7A.A Cable and Connector List (continued) Cable No.

Control

From Module and Connector

Cable Name

To Module and Connector

Cat. No.

C56

9/440HR

9/440HR System Module Feedback Board (J9 - J12)

A quad B Optional Feedback Device

AB 845H Encoder

Prepared by Customer

Cat. No. 8520- MS16F Connector

Shield CHA_HI CHA_LO CHB_HI CHB_LO CHZ_HI CHZ_LO +5V_PWR GND +SENSE

Channel B is inverted for AB- 845H encoder - SENSE

1 12 11 8 9 6 5

G A H I B C J D F

3 2 15 16

AB 845H Encoder

All 22 AWG wire

Ferrite Suppressor Core

Connector On End of Cable

Cable Type

Connector On End of Cable

Max. Cable Length

Molex 43025- 1600

Belden 830

MS Type

25 m (82 ft)

7A-63

Page 412

Section 7A Connecting Components

Table 7A.A Cable and Connector List (continued) Cable No.

Control

From Module and Connector

Cable Name

To Module and Connector

Cat. No.

C56

9/440HR

9/440HR System Module Feedback Board (J9 - J12)

A quad B Optional Feedback Device generic AqB Feedback Device

Prepared by Customer

Cat. No. 8520- MS16F Connector

Shield CHA_HI CHA_LO pair shield CHB_HI CHB_LO pair shield CHZ_HI CHZ_LO pair shield +5V_PWR GND +SENSE - SENSE

1 12 11 10 9 8

Optional AqB

7 6 5 4 3 2 15 16

Pair Shields are optiona. l Not used with Belden # 830 feedback device

All 22 AWG wire Ferrite Suppressor Core

Connector On End of Cable

Cable Type

Connector On End of Cable

Max. Cable Length

Molex 43025- 1600

Belden 830

MS Type

25 m (82 ft)

END OF SECTION

7A-64

Page 413

Section

7B

Fiber Optic Connections

7B.0 Section Overview

Page 1B-1 begins illustrations of typical small and large system configurations and the modules that can be used. Most inter-module communication is accomplished through fiber optics. Most I/O devices, including handwheels, the standard MTB panel, and the operator panel, are connected to the control through an “I/O ring”. Ring devices each have an optical transmitter and receiver. Optical transmitters are connected to optical receivers using fiber optic cable to form the I/O ring. The I/O ring must be complete; each transmitter must be connected to a receiver or an I/O ring communications error will occur. Each module using the I/O ring must be included in the I/O Assignment file. The I/O Assignment file is edited using the I/O Assignments utility of the Offline Development System (ODS).

7B.1 Fiber Optic Cable Specifications

Fiber optic cables can be damaged by excessive bend radii, excessive pulling forces, or crushing forces. If the transmissive core is scratched or nicked, transmission characteristics may deteriorate noticeably and mechanical failure (breakage) of the core will be accelerated. The following fiber optic cable installation recommendations should be taken into account: Avoid pulling cable over sharp edges. Do not install cable in areas where it is likely to suffer impact damage (from such things as dropped tools). Avoid installing cable in areas where it will experience repeated flexing, particularly with small radii. Support cable in long vertical runs.

7B-1

Page 414

Section 7B Fiber Optic Connections

Cable suspended in the air should be supported to withstand the load produced by its own weight. DOP, a plasticizer, commonly used with polyvinyl chloride insulated wire (80% of wires) tends to degrade the acrylic core of fiber optic cable. If fiber optic cable is tightly bundled with wire cables and these cables are subjected to high temperature and humidity, the DOP in the wire cable’s insulation may leech into the fiber optic cable and degrade the core. Fiber transmittivity may also be degraded if exposed to organic solvents including, but not limited to: Common Solvents Degrading Transmittivity acetone methyl ethyl ketone benzene toluene ethyl acetate trichloroethane gasoline trichloroetholene methanol

Fiber optic cable can be exposed to the following liquids for long terms without transmittivity being degraded: Cable Resistant to these Solvents NaOH (10%) at 60°C

H2SO4 (10%) at 60°C

NH4 (5%) at 60°C

NaCl (5%) at 60°C chlorinated hydrocarbon cutting oil 1 distilled water mineral oil based dielectric fluid 1 1 The PVC jacket of the cable will be affected but fiber attenuation will not be affected.

Fiber optic cable can be exposed to the following liquids for short terms without transmittivity being degraded: Cable Resistant to these Solvents for Short Term only

7B-2 isopropyl alcohol soap suds (0.5%) at 60°C sodium phosphate based flux cleaners (0.5% sodium phosphate synthetic detergent)

Ammonium hydroxide based flux cleaners

Page 415

Section 7B Fiber Optic Connections

Table 7B.A shows the specifications for the fiber optic cable used to connect optical transmitters to optical receivers. Table 7B.B shows the fiber optic thermal Specifications and Table 7B.C shows the cable attenuation specifications. Table 7B.A Fiber Optic Cable Mechanical Specifications Fiber Optic Mechanical Specifications

Min

Max

Units

Cable Length

-

27 m

Tensile Load During Installation

-

30

Kg/Cable

Tensile Load in Continuous Use

-

30

Kg/Cable

Bend Radius

50

- mm

Impact (10mm R 1/2 cyl. of 1Kg mass)

-

5 cm

Twisting

-

5

Twists/m

Table 7B.B Fiber Optic Cable Thermal Specifications Fiber Optic Thermal Specifications

Min

Max

Units

Storage Temperature

-40

+85

°C

Application Temperature

0

+70

°C

Table 7B.C Fiber Optic Cable Attenuation Specifications Fiber Optic Attenuation Specifications

Min

Max

Units

30 meter (conditions: 660 nm, 25°C)

.21

.30 dB/meter

10 meter (conditions: 660 nm, 25°C)

.23

.34 dB/meter

7B-3

Page 416

Section 7B Fiber Optic Connections

7B.2 Fiber Optic Cable Construction

1. Fiber Optic Cable Stripping Before a fiber optic plug can be connected to the end of a fiber optic cable, the end of the cable must be stripped. Use a Thomas & Bettst wire stripper no. 007--8990--95 or equivalent to strip away approximately 25 mm (1 in.) of the outer jacket of the fiber optic cable. Set the stripper to strip the outer jacket without damaging the inner jacket. Figure 7B.1 Fiber Optic Cable Stripping Outer jacket

25.4 mm (1.00 in) Inner jacket Fiber

11362-I

2. Fiber Optic Plug Assembly Insert the stripped fiber optic cable into the fiber clamp of the fiber optic plug along the fiber clamp guide groove. Leave approximately .8 mm (.032 in) of space between the back of the fiber clamp and the unstripped area of the outer jacket. Allow the stripped portion of the fiber optic cable to protrude several millimeters from the front of the fiber optic plug. Figure 7B.2 Inserting the Cable into the Clamp Fiber clamp

.8 mm (.032 in)

Cable

Plug housing

11363-I

7B-4

Page 417

Section 7B Fiber Optic Connections

Squeeze the fiber clamp and the plug together with pliers until the fiber clamp reaches the bottom of the plug. Important: The lower jaw of the pliers must be seated on the recessed step of the plug housing as shown in Figure 7B.3. Figure 7B.3 Assembling the Fiber Clamp and the Plug Housing

Connector

Pliers Fiber clamp and fiber are trimmed as pieces are clamped together

11364-I

Important: Once the plug has been clamped it cannot be reclamped or reused. The cable clamp slides over the fiber optic plug housing to secure the fiber optic cable. Figure 7B.4 Cable Clamp Mounting

Plug Cable clamp

11365-I

7B-5

Page 418

Section 7B Fiber Optic Connections

3. Inserting a Fiber Optic Plug into a Receptacle Insert the polarized positive-snap retention fiber optic plug into the color coded receptacle. The red receptacles are transmitters, the black receptacles are receivers. Figure 7B.5 Inserting a Fiber Optic Plug into a Receptacle Receptacle Plug

11366-I

4. Removing a Fiber Optic Plug To remove a fiber optic plug from a receptacle, press the quick release tab on the top of the plug and slide the plug out of the receptacle. Figure 7B.6 Removing a Fiber Optic Plug Quick-release tab

11369-I

END OF SECTION

7B-6

Page 419

Section

7C

Noise Prevention

7C.0 Section Overview

This section discusses wiring guide lines and techniques that should be followed to help lower system noise susceptibly. Of these guide lines are followed, noise should not be a factor in most 9/Series system applications.

7C.1 Preventing Noise

The first measures to take to protect the electrical system from electrical noise is to provide a protective ground. Proper grounding helps reduce the effects of electrical noise by isolating induced noise voltages to individual ground wires and shunting them to ground. This allows the noise to be directed to the earth instead of being transmitted through the cables. See page 3B-9 (9/230 systems), page 4D-10 (9/260 and 9/290 systems), or page 5A-42 (9/440 systems) for details on proper protective grounding. In addition to protective grounding, the following noise prevention measures may also be used: Signal Grounding Mechanical Shielding Shielded Cables and Twisted-pair Cables Separation of Cable Routes Noise Suppressors To prevent noise related problems, first find the noise transmission route and then take the appropriate noise prevention measures.

Signal Grounding Signal grounding is used to direct any electrical noise, caused by shorted or leaking high frequency electrical currents, to earth ground. Protective ground, which has a high impedance path for high frequency noise, cannot effectively lead electrical noise from high frequency current to the earth ground. Signal grounding must be made separately from other protective electronic component grounding. Protective ground and signal ground methods differ from each other in that the type of grounding wire used is different. Signal noise, which is caused by high frequency current, has strong skin effect and flows only on the surface layer of the grounding wire. Therefore, the wire used for signal grounding should be as thick as possible and as short as possible to minimize resistance and inductance. 7C-1

Page 420

Section 7C Power Distribution and Wiring Guidelines

Important: When grounding more than one electronic device, do not serially connect their grounding wires. If connected in series, even low level noises can cause interference, as they accumulate additively. Grounding must be made to a single point.

Mechanical Shielding Radiated noise generates high frequency noise on high-impedance control inputs. For effective noise prevention, install a low-impedance grounded conductor in the radiated noise transmission route. Normally, installing the control inside a metallic cabinet and providing protective ground to this cabinet will produce satisfactory results.

Shielded Cables and Twisted-pair Cables Shielded cables are very effective for protecting weak signals such as control signals from electrical noise. These cables are effective for protecting the signals from full frequency band electrostatic inductive noises and radio frequency band electromagnetic noises. However, they are not as effective for low frequency magnetic inductive noises and electromagnetic inductive noise of frequencies lower than radio frequency band. Generally, signal cables carrying signals of similar voltage or current levels are run along the same route. This sometimes causes electrostatic coupling between the signal cables. To prevent such a problem, use shielded cables to carry weak signals, drive signals, and feedback signals, for example. Exposure of signal cables must be kept to a minimum to provide common mode noise rejection and protection. Ground the shielded cable only at one end (usually, the controller or signal source end). The other end of the shield cable should be insulated with tape or shrink tubing. Important: If both ends of the shielded cable are connected to ground, a ground loop will be formed. This may conduct the noise current through the cabinet frame and the chassis ground, generating noise problems instead of eliminating them. To carry NC control signals, use twisted--pair cables, as shown in Figure 7C.1, to prevent transmission of noise to the differential input signals.

7C-2