For the Allen-Bradley 8500-1746I

Page 451

Section 8 Communication Interface

The switch assemblies on the side and rear of the tape reader must be set as shown below: SIDE VIEW ____________________ | | | 12345678 | | SW3 ****|||| | | ||||**** | | | | | | | 12 - * | 11 - * | 10 - * | 9 * | 8 * | SW2 7 * | 6 * | 5 * | 4 - * | 3 - * | 2 - * | 1 * *

REAR VIEW ___________________ | | | | | |

SW1

4 3 2 1

ON OFF * * - * * -

11359-I

Denotes switch lever location

The Decitek AB 8000-XPDR tape reader is connected to the control using a standard RS-232 with hardware handshake interface cable (see Figure 8.2).

5. DSI SP75 Connection The recommended configuration of the DSI SP75 tape punch is shown below: Configuration Parameter

Setting

DEVICE:

DSI SP75

PORT TYPE:

RS232C

BAUD RATE:

600

PROTOCOL:

RAW

PARITY:

EVEN

STOP BITS:

1

DATA LENGTH:

8

TIMEOUT:

15 SEC

OUTPUT CODE

ASCII

The DSI SP75 tape punch is connected to the control using a standard RS-232 with hardware handshake interface cable (see Figure 8.2).

8-18

Page 452

Section 8 Communication Interface

6. Epson LX-810 Printer Connection The recommended configuration of the Epson LX-810 printer is shown below:

8.9 Remote I/O Modules

Configuration Parameter

Setting

DEVICE:

Epson LX- 810

PORT TYPE:

RS232C

BAUD RATE:

2400

PROTOCOL:

LEVEL_2*

PARITY:

EVEN

STOP BITS:

1

DATA LENGTH:

8

TIMEOUT:

15 SEC

OUTPUT CODE

N/A

The remote I/O modules allow the 9/Series control to appear as a remote I/O rack to the I/O scanner of a PLC processor. There are two separate remote I/O modules, one for 9/260 controls, and one for 9/290 controls. 9/230 and 9/440 controls, equipped with remote I/O, have the remote I/O circuitry and connections mounted directly on the processor or wiring board respectively. Though the remote I/O link performs the same functions and is configured in the same manner for all the 9/Series controls, the installation and appearance is significantly different between processors. Remote I/O is a feature of Allen-Bradley’s 1771 I/O and is beyond the scope of any 9/Series documentation. For details on the operation, configuration, and capabilities of a remote I/O device on the 1771 I/O network refer to documentation that came with your 1771 I/O system. This document only discusses what is necessary to install and troubleshoot the 9/Series remote I/O modules.

Implementing Remote I/O on the 9/Series control Important: PAL must set the $RMON flag TRUE, during the first foreground execution, to enable the remote I/O connection. Also several remote I/O operating parameters must be setup in AMP to configure the remote I/O communications for your specific network. Refer to your 9/Series AMP and PAL reference manuals for details. When remote I/O information is sent to the control, it is transmitted as values from eight output words in the PLC processors output image table 8-19

Page 453

Section 8 Communication Interface into the 9/Series remote I/O connection. These values are then stored on the control where they are assigned to the remote I/O input PAL flags ($RMI1-$RMI8). When sending data from the control to a PLC processor, PAL must first assign values to the remote output flags ($RMO1-$RMO8). The control passes these output flag values to the PLC processor where they are loaded into eight input words in the PLC input image table.

8.9.1 9/290 Remote I/O Module

Figure 8.14 shows the remote I/O module as it comes mounted to the component enclosure for 9/290 controls. Figure 8.14 Remote I/O Module Mounted to the Component Enclosure

Remote I/O Module (9/290 only)

Mounting the Remote I/O Module to the Component Enclosure If you ordered the remote I/O module with your 9/290 control, it comes already assembled and mounted to the component enclosure. If you have ordered the remote I/O module separately, use this procedure to mount the remote I/O module to the component enclosure: 1.

8-20

Remove the parts from the bag

Page 454

Section 8 Communication Interface

2.

Lay the metal support on a flat surface so that the brackets stand out. Align the plastic track with the full set of brackets and slide it into the metal support. Align metal brace and assemble as shown:

3.

Repeat step 2 with the second plastic track. The card guide assembly is complete. Slide the remote I/O module into the assembly.

4.

Attach the assembly to the chassis as shown:

19207

Important: Refer to the information provided with your PLC processor or scanner for additional information on connecting the remote I/O module to your PLC processor or PLC scanner. Only port A may be used for remote I/O connection to this module. Port B is not used.

9/290 Remote I/O LEDs The 9/290 remote I/O module uses only one of its two status indicators to help you troubleshoot remote I/O communications. The second status indicator is not used. Figure 8.15 shows the location of these status indicators. Table 8.G lists these status indicators.

8-21

Page 455

Section 8 Communication Interface

Figure 8.15 Location of Status Indicators in the Remote I/O Port

A

B

Table 8.G Remote I/O Module Status Indicators Indicator

Color/State

Description

Probable Cause

Recommended Action active link normal operation none required red/steady hardware fault at processor hardware error

Recycle power. Replace the processor. Refer to your processor documentation.

red/blinking communication break

AMP is not set correctly reset AMP parameters to communicate with scanner program off remote I/O port is offline port is not being used bring remote I/O port on line

A green/steady (B is not used)

8-22

Page 456

Section 8 Communication Interface

8.9.2 9/260 Remote I/O Module

Figure 8.16 shows the remote I/O module as it comes mounted in the component enclosure for 9/260 controls. Figure 8.16 Remote I/O Module Mounted in the Component Enclosure CPU Module

Remote I/O Communication Module

Enclosure 19441

Mounting the Remote I/O Module in the Component Enclosure If you ordered the remote I/O module with your 9/260 control, it comes already mounted in the component enclosure. If you have ordered the remote I/O module separately, use this procedure to mount the remote I/O module in the component enclosure. Important: You can not use the remote I/O module in a 9/260 system that contains either a 9/Series Data Highway Plus communication module or a 9/Series MMS/Ethernet communication module. A 9/260 system can contain only one Remote I/O, DH+, or MMS/Ethernet module. ATTENTION: To prevent damage to the module, wear an ESD wristband while you unpack and install the module. Connect the wristband to the ground screw on the control’s component enclosure.

8-23

Page 457

Section 8 Communication Interface

To install the remote I/O module, follow this procedure: 1.

Turn off power to the control by pressing the <OFF> pushbutton.

ON OFF

2.

Unpack the module from the box. Make sure you are wearing an ESD wristband.

3.

Install the module as shown in Figure 8.17.

Figure 8.17 Installing the Module

Component Enclosure

Clear Shield Blue RIO Port LED Important: Only port A is available on this module.

Status LEDs RS232/422 port (Not Used)

Can be installed in the first slot or second

8-24

Remote I/O Communication Module 19439

Page 458

Section 8 Communication Interface

9/260 Remote I/O LEDs Assuming you have: made all necessary remote I/O communication connections on your 1771 I/O network configured your module for the network in AMP written PAL to set $RMON true and to handle input and output words you are ready to start receiving and transmitting remote I/O information. As the remote I/O module responds to commands, you should see this LED pattern: Figure 8.18 LED Pattern You See When You Send a Command LED for port B is not used.

A solid green - port is configured and connected to network blinking red - port is configured, but not connected to the network

FLT1 FLT2 ACT solid green - module is actively linked to 9/Series CPU

8-25

Page 459

Section 8 Communication Interface

Use this table if you see a different LED pattern than shown above. Indicator

Color/State

Description

Probable Cause

Recommended Action active link normal operation none required red/steady hardware fault at processor hardware error cycle power. Replace the processor. Refer to your processor documentation.

red/blinking communication break

AMP is not set correctly reset AMP parameters to communicate with scanner program off remote I/O port is offline port is not being used bring remote I/O port on line green/steady active link to 9/Series CPU normal operation none required off remote I/O module is not communicating with 9/Series control remote I/O module is offline

AMP or PAL is not properly configured or your remote I/O network is not configured to communicate with the module.

on major hardware fault device has failed if LED remains on after cycling power, contact your Allen-Bradley sales representative

A green/steady (B is not used)

ACT

FLT1 FLT1

8-26

Page 460

Section 8 Communication Interface

8.9.3 9/230 Remote I/O Connection

On 9/230 controls the remote I/O circuitry and plug are integral parts of the main board. No external module exists. Figure 8.19 shows the remote I/O connector and LED mounted on the 9/230 mother board. Wire connections for the remote I/O communications are made through the TB4 NODE ADAPT connector. Connect the wires for remote I/O as shown in the following figure. Refer to your 1771 I/O documentation for details on making remote I/O connections. Figure 8.19 Remote I/O Module Mounted in the Component Enclosure DS4 NA COMM ACTIVE LED for Remote I/O

TB4

Clear Shield Blue

NODE ADAPT INPUT 115/230V 8A/5.5A 47 - 63 Hz

TB1 TB2

TB3

J3

J2

J1

The analog 9/230 enclosure

9/230 Remote I/O LED Assuming you have: made all necessary remote I/O communication connections on your 1771 I/O network configured your remote I/O port for the remote I/O network in AMP written PAL to set $RMON true during the first PAL foreground execution, and to handle input and output words ($RMI1 -- $RMI8 inputs to PAL and $RMO1 -- $RMO8 outputs from PAL.)

8-27