Page 541
Section 10A I/O Interface
10A.3 Digital I/O
The Digital I/O provides for an additional 20 inputs and 12 outputs to the system I/O ring. The digital I/O interface circuits are designed to interface this I/O device with the fiber optic I/O ring. These circuits use a fiber optic transmitter and receiver to provide communication with the fiber optic I/O ring. The digital I/O receives input signals from external devices assigned to its input terminals. These signals are sent to PAL, through the I/O ring, to be used in the ladder logic process. PAL generates signals that are then sent through the I/O ring to the digital I/O. The digital I/O outputs these signals to external devices assigned to its output terminals. This section covers the specifications, connection and the settings for the digital I/O. Figure 10A.12 shows the digital I/O. Figure 10A.12 Digital I/O Fuse
Color code location
Optical connector OUT (OP21) Optical connector IN (OP22)
11317-I
There are four types of digital I/O. The four types have different combinations of power supply and I/O specifications.
10A-18
Page 542
Section 10A I/O Interface
Table 10A.K list the four types of digital I/O that can be selected according to individual machine applications. Table 10A.K Digital I/O Types Type
Power Required 3
Input Points 4
E151
115/230 V ac
20@ 100/115 V ac 50-60HZ
2 10 Triacs: 85-265V ac
RED
E152
115/230 V ac
20@ 200/230 V ac 50-60 Hz
2 10 Triacs: 85-265V ac
BLacK
E153
115/230 V ac
20@ 24V dc
12 Relays: 10-250 V ac/ 10-125V dc
BLUE
E154
24 V dc
20@ 24V dc
10 Transistors: 10-50 V dc 2 Relays: 10-250 V ac/ 10-125V dc
GREEN
1 2
1 Color Code
2 Relays: 10-250 V ac/ 10-125V dc 2 Relays: 10-250 V ac/ 10-125V dc
The color code appears in the upper right corner on the front of the unit. 10 Triac Outputs of sufficient capacity to energize size 0 - 3 contactors. Two Isolated Relay Outputs. Refer to table 10. M Refer to table 10.N Refer to tables 10.O-10.S
3 4 5
10A.3.1 Digital I/O Connection
Output Points 5
Power Connection Figure 10A.13 and Figure 10A.14 show the power connection diagram for the digital I/O. Figure 10A.13 Power Connection (E151, E152, E153) 115V ac L
230V ac H
L
H To frame
To frame
Terminal Block
CHASSIS GND 230V ac NEUT
115V ac NEUT
NOT USED 115/230 V ac
Terminal Block
CHASSIS GND Label
230V ac NEUT
115V ac NEUT
NOT USED 115/230 V ac
Label 11318-I
10A-19
Page 543
Section 10A I/O Interface
Figure 10A.14 Power Connection (E154) 24 V dc
To frame
Terminal Block
CHASSIS GND NOT USED
NOT USED
24V dc NEUT
+24 V dc
Label 11319-I
ATTENTION: Incorrect wiring can cause damage to the digital I/O power supply. Do not jumper the 115V ac NEUT and the 230 V ac NEUT together. Do not jumper the 115V ac NEUT or the unused 230V ac to the Chassis GND terminal.
Input Device Connection Table 10A.L lists the terminals of the digital I/O input terminal strips. You can assign an input device to each terminal. Use the blank space beside each terminal number to indicate any terminal assignments that are made. The terminal assignments will have to correspond to the terminal assignments of the digital I/O in the PAL I/O Assignment file. The I/O assignment file will have to be edited if the terminal assignments do not correspond. Refer to the 9/Series CNC 9/230, 9/260, and 9/290 PAL Reference Manual, publication 8520-4.3, for more information.
10A-20
Page 544
Section 10A I/O Interface
Table 10A.L Digital I/O Input Terminals Terminal No.
Digital Input Functions
Terminal No.
A01
B01
A02
B02
A03
B03
A04
B04
A05
B05
A06
B06
A07
B07
A08
B08
A09
B09
A10
B10
Digital Input Functions
Figure 10A.15 and Figure 10A.16 show the input device connection diagrams for the digital I/O. Figure 10A.15 ac Input Device Connection (E151, E152) Customer supplied ac voltage Proximity switch
L1 (H)
L2 (L)
LS1 PB2 Terminal Block COM
COM
A01
COM COM
A02 A03
B01 B02
A04
A05 A06 A07
B03 B04 B05
B06
A08 B07
All six COM terminals are connected internally
A09
A10 COM
B08 B09
B10
COM
Label 11320-I
10A-21
Page 545
Section 10A I/O Interface
Figure 10A.16 dc Input Device Connection (E153, E154) Customer supplied dc voltage Proximity switch
LS1 PB2 Terminal Block COM COM
A01 A02
COM COM
A03 A04
B01 B02
B03
A05 A06 A07 B04
A08
B05 B06 B07
A09 A10
B08
COM
B09 B10 COM
Label
All six COM terminals are connected internally
11321-I
Output Device Connection Table 10A.M lists the terminal of the digital I/O output terminal strip. Each terminal may have an output device connected to it. Use the blank space beside each terminal number to indicate any terminal assignments that are made. Table 10A.M Digital I/O Output Terminals Terminal No.
Digital Output Functions
Terminal No.
A11
B11
A12
B12
A13
B13
A14
B14
A15
B15
A16
B16
Digital Output Functions
The terminal assignments will have to correspond to the terminal assignments of the digital I/O in the PAL I/O Assignment file. The I/O assignment file will have to be edited if the terminal assignments do not correspond. Refer to the 9/Series CNC 9/230, 9/260, and 9/290 PAL Reference Manual, publication 8520-4.3, for more information. 10A-22
Page 546
Section 10A I/O Interface
Figure 10A.17 shows a triac output connection diagram. Figure 10A.17 Triac Output Connection (E151, E152) Relay type output
Relay type output Triac output - Group 1 V ac Common
A11
V ac
A12
A13
Solenoid
Noise suppressor dc dc + dc Customer supplied
A14
Triac output - Group 2 V ac Common A15
A16
NOT USED
B11
V ac
B12
B13
B14
B15
M
M
Noise suppressor 115 V ac L1 (H)
Noise suppressor 230 V ac L1 (H)
Customer supplied
L2 (L)
B16
Customer supplied
NOT USED
L2 (L) 11322-I
Important: Triac outputs are isolated by means of a photocoupler. They are also protected from transient current by a varistor. To reduce leakage current, it may be necessary to connect a load resistor or additional noise suppressor. When a triac output is connected with a hard contact to control an inductive load, it is recommended that a varistor be used. Do not use suppressors having RC networks, since damage to triacs could occur. Important: A noise suppressor is not incorporated in the relay type output circuit (terminals A11, B11). Connection of an external surge suppressor is recommended to protect the relay contact from a transient voltage spike, which occurs when an inductive device is turned off.
10A-23
Page 547
Section 10A I/O Interface
Figure 10A.18 shows a relay type output connection diagram. Figure 10A.18 Relay Type Output Connection (E153) Relay type output
Relay type output Relay output - Group 1 V ac/V dc Common
A11
V ac V dc
A12
A13
A14
A15
Relay output - Group 2 V ac/V dc Common A16
NOT USED
B13
B14
Incorporated noise suppressor
L1 (H)
B16
NOT USED
230 V ac L2 (L)
Customer supplied
B15
Noise suppressor or load resistor
115 V ac dc -
Customer supplied
B12
M
Noise suppressor or load resistor dc dc +
V ac V dc
M
Solenoid
Noise suppressor
B11
L1 (H)
L2 (L) Customer supplied
11323-I
Important: The relay type output circuits of Group 1 (A12 - A16) and Group 2 (B12 - B16) incorporate a noise suppressor. Important: Surge suppression reduces arcing of an output contact and is recommended for most applications, particularly when switching an inductive load off. Relay contacts A11 and B11 do not have built-in suppression and may exhibit 50% of the relay life of contacts A12-A16 and B12-B16. The contact life of relays used in the output circuits of the E153 module can be significantly reduced if surge suppression is not connected across the load. Performance testing indicates that contact life may be reduced by as much as 30% without surge suppression across the load.
10A-24
Page 548
Section 10A I/O Interface
The relay life of output contacts used in the E153 depends on the load being controlled. The following shows contact performance for a load that has surge suppression applied across it: Load
Switching Voltage
Allen-Bradley Bulletin 500 Size 1 ac Contactor
120V ac
Relay Life 2,500,000 (operations)
Figure 10A.19 showing the output device connection diagram, shows a transistor output connection. Figure 10A.19 Transistor Output Connection (E154) Relay type output
Relay type output
Transistor output - Group 1 V ac/V dc Common A11
V dc1 A12
A13
A14
A15
Transistor output - Group 2 V ac/V dc Common A16
COM 1
B11
Solenoid
M
Noise suppressor
Noise suppressor 115 V ac dc (+) Customer supplied
B13
B14
B15
B16
COM 2
Solenoid
Noise suppressor
24 V dc
L1 (H) L2 (L) Customer supplied
V dc2 B12
48 V dc dc (-)
dc (+) Customer supplied dc (-) 11324-I
Important: Transistor output is a source type output, which is isolated by means of a photocoupler. An external surge suppressor should be connected to protect transistors from a transient voltage spike, which occurs when an inductive device is turned off. Important: A noise suppressor is not incorporated in the relay type output circuits (terminals A11 and B11). Connection of an external surge suppressor is recommended to protect the relay contact from a transient voltage spike, which occurs when an inductive device is turned off.
10A-25
Page 549
Section 10A I/O Interface
10A.3.2 Digital I/O Specifications
Table 10A.N lists the power requirements for the 4 types of digital I/O. Table 10A.N Digital I/O Power Requirements Item
Digital I/O Types E151, E152, E153
E154
Rated Input Voltage
115/230 V ac 50/60 Hz
24 V dc
Input Voltage Range
85-132/170-265 V ac 47-63 Hz
10-30 V dc
Power Consumption
Less than 15 VA
Less than 9 VA
Fuse Rating
315mA/250V
1.6A/250V
Fuse Type
Glass-tube-filled (f6.35 ´31.8 mm)
Power ON Indicating LED
Lights up when +5V is supplied to the internal circuit
Connection
Terminal Block
Table 10A.O lists the input specifications for the 4 types of digital I/O. All input circuits include optical isolation as well as filtering to guard against high voltage transients from external input devices. Table 10A.O Digital I/O Input Specifications Item
Digital I/O Types E151
E152
E153
Number of Inputs
20 Input Terminals (pins: A01-A10, B01-B10)
Rated Input Voltage
85-132 V ac 50/60 Hz
170-265 V ac 50/60 Hz
10-30 V dc
ON
85-132 V ac
170-265 V ac
10-30 V dc
OFF
Less than 30 V ac
Less than 50 V ac
Less than 4 V dc
Operating Voltage
E154
Leakage Current at OFF
Less than 2mA
Less than 1mA
Input Current
Approximately 8mA
Approx. 4mA at 12 V dc
Maximum Inrush Current
Less than 0.8A
Response
ON to OFF
3-13 msec 1
4-8 msec 1
OFF to ON
9-18 msec 1
4-8 msec 1
Approx. 8mA at 24 V dc
Operation Indication
LED ON when power is ON
Connection
Terminal Block
Number of Common Points
6 points per 20 input points 2
Dielectric Strength
Higher than 1500V 3
1 Excluding digital filter time. 2 All common lines are internally connected to each other. 3 Across input terminal - control logic circuit.
10A-26
Page 550
Section 10A I/O Interface
Figure 10A.20 and Figure 10A.21 show the digital I/O input circuit diagrams for ac and dc applications. Figure 10A.20 Digital I/O ac Input Circuit Diagram (E151, E152)
Signal source L1
Digital I/O Module ac power supply
L2
Photocoupler Com. PE
11325-I
Figure 10A.21 Digital I/O dc Input Circuit Diagram (E153, E154) Signal source
Digital I/O Module dc power supply
Photocoupler Com. PE
11326-I
Table 10A.P through Table 10A.T list the output specifications for the 4 types of digital I/O. It is recommended that some type of surge suppressor be used when switching inductive load devices with hard contact outputs.
10A-27