Page 541

Section 10A I/O Interface

10A.3 Digital I/O

The Digital I/O provides for an additional 20 inputs and 12 outputs to the system I/O ring. The digital I/O interface circuits are designed to interface this I/O device with the fiber optic I/O ring. These circuits use a fiber optic transmitter and receiver to provide communication with the fiber optic I/O ring. The digital I/O receives input signals from external devices assigned to its input terminals. These signals are sent to PAL, through the I/O ring, to be used in the ladder logic process. PAL generates signals that are then sent through the I/O ring to the digital I/O. The digital I/O outputs these signals to external devices assigned to its output terminals. This section covers the specifications, connection and the settings for the digital I/O. Figure 10A.12 shows the digital I/O. Figure 10A.12 Digital I/O Fuse

Color code location

Optical connector OUT (OP21) Optical connector IN (OP22)

11317-I

There are four types of digital I/O. The four types have different combinations of power supply and I/O specifications.

10A-18

Page 542

Section 10A I/O Interface

Table 10A.K list the four types of digital I/O that can be selected according to individual machine applications. Table 10A.K Digital I/O Types Type

Power Required 3

Input Points 4

E151

115/230 V ac

20@ 100/115 V ac 50-60HZ

2 10 Triacs: 85-265V ac

RED

E152

115/230 V ac

20@ 200/230 V ac 50-60 Hz

2 10 Triacs: 85-265V ac

BLacK

E153

115/230 V ac

20@ 24V dc

12 Relays: 10-250 V ac/ 10-125V dc

BLUE

E154

24 V dc

20@ 24V dc

10 Transistors: 10-50 V dc 2 Relays: 10-250 V ac/ 10-125V dc

GREEN

1 2

1 Color Code

2 Relays: 10-250 V ac/ 10-125V dc 2 Relays: 10-250 V ac/ 10-125V dc

The color code appears in the upper right corner on the front of the unit. 10 Triac Outputs of sufficient capacity to energize size 0 - 3 contactors. Two Isolated Relay Outputs. Refer to table 10. M Refer to table 10.N Refer to tables 10.O-10.S

3 4 5

10A.3.1 Digital I/O Connection

Output Points 5

Power Connection Figure 10A.13 and Figure 10A.14 show the power connection diagram for the digital I/O. Figure 10A.13 Power Connection (E151, E152, E153) 115V ac L

230V ac H

L

H To frame

To frame

Terminal Block

CHASSIS GND 230V ac NEUT

115V ac NEUT

NOT USED 115/230 V ac

Terminal Block

CHASSIS GND Label

230V ac NEUT

115V ac NEUT

NOT USED 115/230 V ac

Label 11318-I

10A-19

Page 543

Section 10A I/O Interface

Figure 10A.14 Power Connection (E154) 24 V dc

To frame

Terminal Block

CHASSIS GND NOT USED

NOT USED

24V dc NEUT

+24 V dc

Label 11319-I

ATTENTION: Incorrect wiring can cause damage to the digital I/O power supply. Do not jumper the 115V ac NEUT and the 230 V ac NEUT together. Do not jumper the 115V ac NEUT or the unused 230V ac to the Chassis GND terminal.

Input Device Connection Table 10A.L lists the terminals of the digital I/O input terminal strips. You can assign an input device to each terminal. Use the blank space beside each terminal number to indicate any terminal assignments that are made. The terminal assignments will have to correspond to the terminal assignments of the digital I/O in the PAL I/O Assignment file. The I/O assignment file will have to be edited if the terminal assignments do not correspond. Refer to the 9/Series CNC 9/230, 9/260, and 9/290 PAL Reference Manual, publication 8520-4.3, for more information.

10A-20

Page 544

Section 10A I/O Interface

Table 10A.L Digital I/O Input Terminals Terminal No.

Digital Input Functions

Terminal No.

A01

B01

A02

B02

A03

B03

A04

B04

A05

B05

A06

B06

A07

B07

A08

B08

A09

B09

A10

B10

Digital Input Functions

Figure 10A.15 and Figure 10A.16 show the input device connection diagrams for the digital I/O. Figure 10A.15 ac Input Device Connection (E151, E152) Customer supplied ac voltage Proximity switch

L1 (H)

L2 (L)

LS1 PB2 Terminal Block COM

COM

A01

COM COM

A02 A03

B01 B02

A04

A05 A06 A07

B03 B04 B05

B06

A08 B07

All six COM terminals are connected internally

A09

A10 COM

B08 B09

B10

COM

Label 11320-I

10A-21

Page 545

Section 10A I/O Interface

Figure 10A.16 dc Input Device Connection (E153, E154) Customer supplied dc voltage Proximity switch

LS1 PB2 Terminal Block COM COM

A01 A02

COM COM

A03 A04

B01 B02

B03

A05 A06 A07 B04

A08

B05 B06 B07

A09 A10

B08

COM

B09 B10 COM

Label

All six COM terminals are connected internally

11321-I

Output Device Connection Table 10A.M lists the terminal of the digital I/O output terminal strip. Each terminal may have an output device connected to it. Use the blank space beside each terminal number to indicate any terminal assignments that are made. Table 10A.M Digital I/O Output Terminals Terminal No.

Digital Output Functions

Terminal No.

A11

B11

A12

B12

A13

B13

A14

B14

A15

B15

A16

B16

Digital Output Functions

The terminal assignments will have to correspond to the terminal assignments of the digital I/O in the PAL I/O Assignment file. The I/O assignment file will have to be edited if the terminal assignments do not correspond. Refer to the 9/Series CNC 9/230, 9/260, and 9/290 PAL Reference Manual, publication 8520-4.3, for more information. 10A-22

Page 546

Section 10A I/O Interface

Figure 10A.17 shows a triac output connection diagram. Figure 10A.17 Triac Output Connection (E151, E152) Relay type output

Relay type output Triac output - Group 1 V ac Common

A11

V ac

A12

A13

Solenoid

Noise suppressor dc dc + dc Customer supplied

A14

Triac output - Group 2 V ac Common A15

A16

NOT USED

B11

V ac

B12

B13

B14

B15

M

M

Noise suppressor 115 V ac L1 (H)

Noise suppressor 230 V ac L1 (H)

Customer supplied

L2 (L)

B16

Customer supplied

NOT USED

L2 (L) 11322-I

Important: Triac outputs are isolated by means of a photocoupler. They are also protected from transient current by a varistor. To reduce leakage current, it may be necessary to connect a load resistor or additional noise suppressor. When a triac output is connected with a hard contact to control an inductive load, it is recommended that a varistor be used. Do not use suppressors having RC networks, since damage to triacs could occur. Important: A noise suppressor is not incorporated in the relay type output circuit (terminals A11, B11). Connection of an external surge suppressor is recommended to protect the relay contact from a transient voltage spike, which occurs when an inductive device is turned off.

10A-23

Page 547

Section 10A I/O Interface

Figure 10A.18 shows a relay type output connection diagram. Figure 10A.18 Relay Type Output Connection (E153) Relay type output

Relay type output Relay output - Group 1 V ac/V dc Common

A11

V ac V dc

A12

A13

A14

A15

Relay output - Group 2 V ac/V dc Common A16

NOT USED

B13

B14

Incorporated noise suppressor

L1 (H)

B16

NOT USED

230 V ac L2 (L)

Customer supplied

B15

Noise suppressor or load resistor

115 V ac dc -

Customer supplied

B12

M

Noise suppressor or load resistor dc dc +

V ac V dc

M

Solenoid

Noise suppressor

B11

L1 (H)

L2 (L) Customer supplied

11323-I

Important: The relay type output circuits of Group 1 (A12 - A16) and Group 2 (B12 - B16) incorporate a noise suppressor. Important: Surge suppression reduces arcing of an output contact and is recommended for most applications, particularly when switching an inductive load off. Relay contacts A11 and B11 do not have built-in suppression and may exhibit 50% of the relay life of contacts A12-A16 and B12-B16. The contact life of relays used in the output circuits of the E153 module can be significantly reduced if surge suppression is not connected across the load. Performance testing indicates that contact life may be reduced by as much as 30% without surge suppression across the load.

10A-24

Page 548

Section 10A I/O Interface

The relay life of output contacts used in the E153 depends on the load being controlled. The following shows contact performance for a load that has surge suppression applied across it: Load

Switching Voltage

Allen-Bradley Bulletin 500 Size 1 ac Contactor

120V ac

Relay Life 2,500,000 (operations)

Figure 10A.19 showing the output device connection diagram, shows a transistor output connection. Figure 10A.19 Transistor Output Connection (E154) Relay type output

Relay type output

Transistor output - Group 1 V ac/V dc Common A11

V dc1 A12

A13

A14

A15

Transistor output - Group 2 V ac/V dc Common A16

COM 1

B11

Solenoid

M

Noise suppressor

Noise suppressor 115 V ac dc (+) Customer supplied

B13

B14

B15

B16

COM 2

Solenoid

Noise suppressor

24 V dc

L1 (H) L2 (L) Customer supplied

V dc2 B12

48 V dc dc (-)

dc (+) Customer supplied dc (-) 11324-I

Important: Transistor output is a source type output, which is isolated by means of a photocoupler. An external surge suppressor should be connected to protect transistors from a transient voltage spike, which occurs when an inductive device is turned off. Important: A noise suppressor is not incorporated in the relay type output circuits (terminals A11 and B11). Connection of an external surge suppressor is recommended to protect the relay contact from a transient voltage spike, which occurs when an inductive device is turned off.

10A-25

Page 549

Section 10A I/O Interface

10A.3.2 Digital I/O Specifications

Table 10A.N lists the power requirements for the 4 types of digital I/O. Table 10A.N Digital I/O Power Requirements Item

Digital I/O Types E151, E152, E153

E154

Rated Input Voltage

115/230 V ac 50/60 Hz

24 V dc

Input Voltage Range

85-132/170-265 V ac 47-63 Hz

10-30 V dc

Power Consumption

Less than 15 VA

Less than 9 VA

Fuse Rating

315mA/250V

1.6A/250V

Fuse Type

Glass-tube-filled (f6.35 ´31.8 mm)

Power ON Indicating LED

Lights up when +5V is supplied to the internal circuit

Connection

Terminal Block

Table 10A.O lists the input specifications for the 4 types of digital I/O. All input circuits include optical isolation as well as filtering to guard against high voltage transients from external input devices. Table 10A.O Digital I/O Input Specifications Item

Digital I/O Types E151

E152

E153

Number of Inputs

20 Input Terminals (pins: A01-A10, B01-B10)

Rated Input Voltage

85-132 V ac 50/60 Hz

170-265 V ac 50/60 Hz

10-30 V dc

ON

85-132 V ac

170-265 V ac

10-30 V dc

OFF

Less than 30 V ac

Less than 50 V ac

Less than 4 V dc

Operating Voltage

E154

Leakage Current at OFF

Less than 2mA

Less than 1mA

Input Current

Approximately 8mA

Approx. 4mA at 12 V dc

Maximum Inrush Current

Less than 0.8A

Response

ON to OFF

3-13 msec 1

4-8 msec 1

OFF to ON

9-18 msec 1

4-8 msec 1

Approx. 8mA at 24 V dc

Operation Indication

LED ON when power is ON

Connection

Terminal Block

Number of Common Points

6 points per 20 input points 2

Dielectric Strength

Higher than 1500V 3

1 Excluding digital filter time. 2 All common lines are internally connected to each other. 3 Across input terminal - control logic circuit.

10A-26

Page 550

Section 10A I/O Interface

Figure 10A.20 and Figure 10A.21 show the digital I/O input circuit diagrams for ac and dc applications. Figure 10A.20 Digital I/O ac Input Circuit Diagram (E151, E152)

Signal source L1

Digital I/O Module ac power supply

L2

Photocoupler Com. PE

11325-I

Figure 10A.21 Digital I/O dc Input Circuit Diagram (E153, E154) Signal source

Digital I/O Module dc power supply

Photocoupler Com. PE

11326-I

Table 10A.P through Table 10A.T list the output specifications for the 4 types of digital I/O. It is recommended that some type of surge suppressor be used when switching inductive load devices with hard contact outputs.

10A-27