Page 561

Section 10A I/O Interface

10A.4.2 High Density I/O Module Specifications

Power Supply Specifications Table 10A.Z lists the power requirements for the high--density I/O module. Table 10A.Z High- density I/O Module Power Requirements Item

Specifications

Rated Input Voltage

24 V dc

Input Voltage Range

18-30 V dc

Current Consumption

Less than 1.2A (Excluding Output Power)

Connection

Phoenix Connector or Terminal Block

Important: The power requirements listed above are for the logic power of the high--density I/O module only. Important: Power supplies with excessive noise or poor voltage regulation should not be used to power the high--density I/O.

Input Specifications Table 10A.AA lists the input specifications for the high--density I/O module. Table 10A.AA High- density I/O Module Input Specifications Item

Specifications

Number of Input Points Operating Voltage

66 ON

10-30 V dc

OFF

0-5 V dc

Allowable Voltage Drop

Max. 6 V dc

Input Impedance

3 K ohms

Input Current Leakage Current

Remark Pin Number

For external device

ON

Approx. 4.0mA

With 12 V dc Inputs

OFF

Approx. 8.0mA

With 24 V dc Inputs

OFF

Less than 1mA

Response

0.1-23msec Including Digital Filter Time

OFF to ON, ON to OFF

Number of Common Points

4 per each 33 inputs

All common points are internally connected to each other

Fuse

1.25 A

1 for all inputs*

Isolation

Non-Isolated type

Input Connection

2 37-Pin, D-Shell Connectors

Male type

* Fuse is used only for inputs using 24V module power from pins 34, 35, 36, and 37 of CN61 or CN62

10A-38

Page 562

Section 10A I/O Interface

The input circuit diagram for the high--density I/O module is shown in Figure 10A.30. Figure 10A.30 High- density I/O Module Input Circuit Diagram Machine

High- density I/O Input signal +24V Input Power CN61/CN62

PE

1.25A fuse dc power supply TB1

+24V

PE

Reference voltage generation circuit

GND Ground terminal

BT33 TB1

11335-I

Output Specifications The output specifications for the high--density I/O module are listed in Table 10A.AB. Table 10A.AB High- density I/O Module Output Specifications Item

Specifications

Remark

Number of Outputs

36

PNP Transistor

Output Type

Open Collector Output

Source Type

Rated Output Voltage

24 V dc

Output Voltage Range

18-30 V dc

Output Current at ON

Less than 250mA

Per each output

Maximum Output Capacity

9A

All outputs “ON”

Voltage Drop at ON

Less than 1.5 V

Leakage Current at OFF

Less than 0.1mA

Number of Ground Points

1

Isolated

Non- Isolated Type

Output Connection

37- Pin D-Shell Connector

+24 V dc (COM), GND

10A-39

Page 563

Section 10A I/O Interface

Figure 10A.31 shows the output circuit diagram for the high--density I/O module. Figure 10A.31 High- density I/O Module Output Circuit Diagram High- density I/O Module

Signal destination +24V BT33 TB2

Customer- supplied dc power supply Load

CN63F

BT33 TB2 PE

Com.

11336-I

10A.4.3 High- density I/O Module Fiber Optic Connection

Table 10A.AC lists the connectors used to make the fiber optic connections to the I/O ring. Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the I/O ring. Refer to Appendix A for additional information on fiber optic cables and connectors. Table 10A.AC High- density I/O Module Fiber Optic Connectors Connector on Digital I/O

10A-40

Connected To

Remark

OP23 (RED)

Receiver on next module in I/O ring

Output

OP24 (BLACK)

Transmitter on previous module in I/O ring

Input

Page 564

Section 10A I/O Interface

10A.4.4 High Density I/O Module Node Address Setting

Different types of I/O devices can have the same node address, but devices of the same type must each have a unique node address. Each high--density I/O module is assigned a unique node address in the I/O assignment file of ODS. This address corresponds to a switch setting on the high--density I/O module. Figure 10A.32 shows the location of the node address switch assembly on the high--density I/O. Figure 10A.32 High- density I/O Module Switch Assembly Location

DIP switch Fuse ON

1

2

3

4

56 I/O Ring Fault Indicator

BT33

CN61M

CN62M

I/O Inputs

I/O Inputs

CN63F

I/O Outputs

Optical connector OP24 (IN)

Optical connector OP23 (OUT)

Set the switch assembly to correspond to the node address as shown in Table 10A.AD. Table 10A.AD High- density I/O Module Node Address Setting Node Address

Switch Assembly Position

Hexadecimal

Binary

1

2

3

4

5

6

00

00 0000

OFF

OFF

OFF

OFF

OFF

OFF

01

00 0001

OFF

OFF

OFF

OFF

OFF

ON

02

00 0010

OFF

OFF

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

3D

11 1101

ON

ON

ON

ON

OFF

ON

3E

11 1110

ON

ON

ON

ON

ON

OFF

3F

11 1111

ON

ON

ON

ON

ON

ON

10A-41

Page 565

Section 10A I/O Interface

10A.5 E - Series Analog I/O

This section only discusses the use of the E--Series analog I/O module. If you are using a 1746 analog I/O device, refer to page 10B-10 for installation and operation details. The Analog I/O provides analog input and output to the control through the system I/O ring. It converts analog inputs to digital inputs and digital outputs to analog outputs for transmission to and from the control via the I/O ring. Each analog I/O provides 1 input channel and 1 output channel. Figure 10A.33 E- Series Analog I/O External Appearance Fuse

Optical connector

Optical connector

11338-I

10A-42

Page 566

Section 10A I/O Interface

10A.5.1 E- Series Analog I/O Specifications

Table 10A.AE lists the power requirements for the analog I/O. Table 10A.AE E- Series Analog I/O Power Requirements Item

Specifications

Rated Input Voltage

115/230 V ac 50/60 Hz

Input Voltage Range

85-132 V ac, 170-265 V ac, 47 Hz-63Hz

Power Consumption

Less than 15 VA

Fuse Rating

315mA/250V

Power ON Indicator

Lights up when +5V and ±15V are supplied to internal circuit

Connection

Terminal Block

Figure 10A.34 shows the terminals of analog I/O terminal block used for power source connection. Figure 10A.34 E- Series Analog I/O Power Source Connection 115V ac L

230V ac L

H

H To frame

To frame

Terminal Block

CHASSIS GND 230V ac NEUT

NOT USED

115V ac NEUT

115/230 V ac

Label

Terminal Block

CHASSIS GND 230V ac NEUT

NOT USED

115V ac NEUT

115/230 V ac

Label 11339-I

ATTENTION: Incorrect wiring can cause damage to the analog I/O power supply. Do not jumper the 115V ac NEUT and the 230 V ac NEUT together. Do not jumper the 115V ac NEUT or the unused 230V ac to the Chassis GND terminal.

10A-43

Page 567

Section 10A I/O Interface

Table 10A.AF lists the input specifications for the analog I/O. Table 10A.AF E- Series Analog I/O Input Specifications Item

Specifications

Remark

Number of Input Points

1

Input Voltage Range

Bipolar: -10 to +10 V dc Unipolar: 0 to +10V dc

Resolution

12 bit binary

Input Impedance

More than 100 Kohms

-10V to +10V

Conversion Rate

Interval: Less than 100 msec Time: Less than 30 msec

Approx. 64 msec Approx. 20 msec

Maximum Input Voltage

±25 V dc

Common Mode Rejection

More than 70dB

Connection

Terminal Block

PAL Variable Values

Bipolar: 0 - 2047 (0 to +10V dc) 2048 - 4096 (- 10 to 0 V dc)

Range selected by switch next to the node address switch on the analog I/O

From dc to 60 Hz

The PAL variable name is determined in your I/O configuration using ODS.

Unipolar: 0 - 4096 (0 to +10V dc)

Figure 10A.35 shows a typical analog I/O input device connection. Figure 10A.35 E- Series Analog I/O Input Device Connection From analog device

From analog device e2 e

Single Input e1 e=e1 -e2

Differential Input Shielded cable

Shielded cable

Terminal Block

CHASSIS GND NOT USED

INPUT (-)

CHASSIS GND

COM

CHASSIS GND

INPUT (+) CHASSIS GND

CHASSIS GND

CHASSIS GND

Label

CHASSIS GND

NOT

NOT

USED

USED

INPUT (-)

CHASSIS GND

COM

CHASSIS GND

INPUT (+)

CHASSIS GND

CHASSIS GND

CHASSIS GND

NOT USED 11340-I

10A-44

Page 568

Section 10A I/O Interface

Table 10A.AG lists the output specifications for the analog I/O. Table 10A.AG E- Series Analog I/O Output Specifications Item

Specifications

Number of Output Points

1

Operating Voltage

Bipolar: -10 to +10 V dc Unipolar: 0 to +10V dc

Resolution

12 bit binary

Load Drive Capability

Maximum 10 mA

Remark

Range selected by switch next to the node address switch on the analog I/O

No Sustained Oscillation

Maximum 1 mF Maximum mF Response Rate

Less than 200 msec

Connection

Terminal Block

PAL Variable Values

Bipolar: 0 - 2047 (0 to +10V dc) 2048 - 4096 (- 10 to 0 V dc)

The PAL variable name is determined in your I/O configuration using ODS.

Unipolar: 0 - 4096 (0 to +10V dc)

Figure 10A.36 shows a typical analog I/O output device connection.

10A-45

Page 569

Section 10A I/O Interface

Figure 10A.36 E- Series Analog I/O Output Device Connection To analog device

Shielded cable

Terminal Block

CHASSIS GND NOT USED

10A.5.3 E- Series Analog I/O Fiber Optic Connection

COM

CHASSIS GND

OUTPUT

CHASSIS GND

CHASSIS GND

CHASSIS GND

NOT

Label

USED NOT

NOT

USED

USED

11341-I

Table 10A.AH lists the analog I/O connectors used to make the fiber optic connections to the I/O ring. Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the I/O ring. Refer to Appendix A for additional information on fiber optic cables and connectors. Table 10A.AH E- Series Analog I/O Fiber Optic Connectors Connector on Digital I/O

10A.5.4 E- Series Analog I/O Node Address Setting

Connected To

Remark

OP25 (RED)

Receiver on next module in I/O ring

Output

OP26 (BLacK)

Transmitter on previous module in I/O ring

Input

Different types of I/O devices can have the same node address, but devices of the same type must each have a unique node address. Each analog I/O is assigned a unique node address in the I/O assignment file of ODS. This address corresponds to a switch setting on the analog I/O device. Figure 10A.37 shows the location of the node address switch assembly on the analog I/O.

10A-46

Page 570

Section 10A I/O Interface

Figure 10A.37 E- Series Analog I/O Node Address Switch Assembly Location

O1 2 3 4 N This cover unsnaps and folds down to expose switches 11342-I

Set the node address switch assembly to correspond to the node address as shown in Table 10A.AI. Table 10A.AI E- Series Analog I/O Node Address Setting Node Address

Switch Assembly Position

Hexadecimal

Binary

1

2

3

4

00

0000

OFF

OFF

OFF

OFF

01

0001

OFF

OFF

OFF

ON

02

0010

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0D

1101

ON

ON

OFF

ON

0E

1110

ON

ON

ON

OFF

0F

1111

ON

ON

ON

ON

10A-47