Section 10A I/O Interface
10A.5.5 E- Series Analog I/O Bipolar/Unipolar Configuration
The E--Series analog I/O module allows you to select between bipolar operation (--10V to +10V dc) and unipolar operation (0V to +10V dc). Select this using a dip switch located next to the node address switch (see Figure 10A.38). Bipolar or unipolar can be selected independently for the input and output channels. Figure 10A.38 E Series Analog I/O Node Address Switch Assembly Location
O1 2 3 4 N
Bipolar/Unipolar switches INPUT OUTPUT
This cover unsnaps and folds down to expose switches 11342-I
Switch positions are as follows: Unipolar (0 V dc to +10 V dc)
Bipolar (- 10 V dc to +10 V dc)
10A-48
Page 572
Section 10A I/O Interface
10A.6 1746 I/O
You can place several 1746I modules with 1746 I/O chassis in the 9/Series fiber-optic ring. Each 1746 I/O chassis must contain its own 1746I module (daisy chaining racks together using one 1746I module is not allowed). The number of I/O points/chassis is limited to the number of ASRN chips supported by the 9/Series fiber--optic ring. Use page 10B-10 to calculate how many ASRN chips are required for each I/O chassis. A maximum of 16 chassis are allowed on the 9/Series fiber-optic I/O ring. 1746 Series B I/O Chassis
1746I adapter module Three different fully equipped 1746 I/O chassis are available for the 9/Series I/O ring. These chassis contain the following I/O devices: Table 10A.AJ Standard 9/Series 1746 I/O Catalogs Catalog Number 8500-S115
Catalog Number 8500-S24
Catalog Number 8500-SANL
(1) 1746-A4
4 Slot Chassis
(1) 1746-A4
4 Slot Chassis
(1) 1746-A4
4 Slot Chassis
(1) 1746-P1
115/230V ac Power Supply
(1) 1746-P1
115/230V ac Power Supply
(1) 1746-P1
115/230V ac Power Supply
(1) 8500-1746I
I/O Ring Interface Adapter Module
(1) 8500-1746I
I/O Ring Interface Adapter Module
(1) 8500-1746I
I/O Ring Interface Adapter Module
(2) 1746-IA16
16 point 115V ac Input Module
(2) 1746-IB16
16 point 24V dc Input Module
(1) 1746-NIO4V
Analog Input Module
(1) 1746-OA16
16 point 115V ac Output Module
(1) 1746-OW16
16 point 24V dc Output Module
(1) 1746-N2
2 Empty Slot Covers
(1) set fiber optic connectors for connection to I/O ring
(1) set fiber optic connectors for connection to I/O ring
(1) set fiber optic connectors
For connection to I/O ring
Total I/O
32 115V ac Inputs 16 115V ac Outputs 3 ASRN chips
Total I/O
32 24V dc Inputs 16 24V dc Outputs 3 ASRN chips
Total I/O
2 analog input chnls. 2 analog output chnls 6 ASRN chips
10A-49
Page 573
Section 10A I/O Interface
10A.6.1 Removing/Installing 1746 Modules
The following procedure covers how to remove modules from your 1746 I/O chassis. In some cases it is necessary to remove a module to set or check dip switch settings. ATTENTION: Never install, remove, or wire modules with power applied to the chassis.
Removing a Module 1.
Label and remove any wiring or removable terminal blocks.
2. Gently press in on both the top and bottom latches of the module to be removed. 3. Slide the module out of the rack.
Installing a Module 1. Align the circuit board of the module with the card guide in the chassis. Important: You must install the 1746I module in the first slot of the chassis (slot immediately next to the power supply). The 1746I module takes the place of a CPU module or a ASB adapter module in this slot. Other modules should be returned to the same slot they were removed from. 2.
Gently slide the module in until both top and bottom latches are latched.
3.
Reconnect wires or removable terminal blocks.
Cover all unused slots with a Card Slot Filler, Catalog Number 1746-N2.
10A.6.2 1746I I/O Ring Adapter Node Address Setting
To install the 1746I module in the 9/Series I/O ring you must first assign the module an address on the 9/Series I/O ring. If the module is already installed in your 1746 I/O chassis, you must remove the module to set the module address. Remove the module by pressing in on the locking tabs on the top and bottom of the 1746I module and sliding the module out of the chassis. Assign an address to the module using the dip switch S1 found on the side of the 1746I module. Figure 10B.4 shows the location of the node address switch assembly on the 1746I module.
10A-50
Page 574
Section 10A I/O Interface
Figure 10A.39 1746 I/O Ring Adapter Switch Assembly Locations
ON
S1 1 2 3 4 5 6
Other 9/Series I/O devices (such as an HPG or MTB panel) on the 9/Series fiber-optic ring can have the same node address as the 1746I module. However, devices of the same type (multiple 1746I modules) must each have a unique node address. Each 1746 I/O ring adapter is assigned a unique node address in the I/O assignment file of ODS (refer to your PAL reference manual). This address corresponds to switch assembly S1 on the 1746I module. Set switch assembly S1 to correspond to the node address as shown in Table 10A.AK.
10A-51
Page 575
Section 10A I/O Interface
Table 10A.AK 1746I I/O Ring Adapter Node Address Setting Node Address
Switch Assembly Position
Hexadecimal
Binary
1
2
3
4
00
0000
OFF
OFF
OFF
OFF
01
0001
OFF
OFF
OFF
ON
02
0010
OFF
OFF
ON
OFF
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
0F
1111
ON
ON
ON
ON
Important: Switch 5 and 6 of S1 must remain in the OFF position for normal operation.
10A.6.3 1746P1 Power Supply
The following are the specifications and wiring instructions for the 1746 P1 power supply.
Set the Input Voltage Jumper 1.
Locate the input voltage jumper. If necessary, remove and reinstall the jumper to match the external voltage available. ATTENTION: Set the input jumper before applying power. Hazardous voltage is present on exposed pins when power is applied: contact with the pins may cause injury to personnel.
100/120 V
200/240 V push latch up from underneath to open the door
10A-52
Page 576
Section 10A I/O Interface
2.
Wire the power supply terminals as shown below. These terminals accept two #14AWG wires.
PWR OUT +24 V dc PWR OUT COM L1, 120/240 V L2, V ac NEUTRAL, PE
ATTENTION: Turn off power lines before connecting power; failure to do so could cause injury to personnel and/or equipment.
20151
Table 10A.AL 1746 P1 Power Supply Specifications Description:
Specification:
Line Voltage
85- 132/170- 265 V ac 50/60 Hz
Typical Line Power Requirement
135 VA
Internal Current Capacity
2 AMP at 5 V dc 0.46 AMP at 24 V dc
User Current Capacity
24 V dc - 0.2 AMP
Fuse Protection
3 AMPs
Ambient Operating Temperature Rating
0 to +55°C (Current capacity derated by 5% at +60°C)
Humidity Rating
5 - 95% (noncondensing)
Wiring
#14 AWG
10A-53
Page 577
Section 10A I/O Interface
10A.6.4 1746 I/O Ring Adapter Fiber Optic Connection
The connectors used to make the fiber optic connections to the I/O ring are listed in Table 10A.AM. Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the I/O ring. Refer to Appendix A for additional information on fiber optic cables and connectors. The fiber-optic connectors are located under the front door of the 1746I module for easy access. Run the fiber-optic cables out the bottom of the 1746I module to allow the front door of the module to close after the cables have been installed. Table 10A.AM 1746 I/O Ring Adapter Fiber Optic Connectors Connector on Digital I/O
10A.7 1746 Discrete I/O Racks
Remark
Connected To
I/O (RED)
Output
Receiver on next module in I/O ring
I/O (BLACK)
Input
Transmitter on previous module in I/O ring
The following tables give input and output specifications for the standard 1746 I/O modules available for the 9/Series fiber-optic I/O ring. Contact your Allen-Bradley sales representative for details on any modules not listed here. See page 10B-8 for details on other 9/Series compatible 1746 I/O modules.
General 1746 Discrete I/O Module Specifications Description:
NEMA-Standard ICS 2-230
Vibration (operating)
Displacement - .015 inch peak to peak at 5 - 57 Hz Acceleration - 2.5 G at 57 - 2000 Hz
Shock (operating)
30 G
Isolation
1500 V
Environmental conditions Operating temperature Storage temperature Humidity rating
0 to +60°C (+32°to +140°F) -40°to +85°C (- 40°to +185°F) 5 to 95% (noncondensing)
Certification
UL listed, CSA approved
Hazardous Environment Classification
Class I, Division 2 Hazardous Environment.À
À
10A-54
Specification
Noise Immunity
Some modules are excluded from this certification. Refer to the following tables for a complete listing.
Page 578
Section 10A I/O Interface
Discrete Input Module Specifications Backplane Current Draw 5V 24V
Signal Delay (ms. max)
Off-State Current (max)
Off-State Voltage (max)
Nominal Input Current
Inrush Current (max)
16
0.085
0 on=35 Off=45
2 mA
30 V ac
12 mA at 120 V ac
0.8 A
16
0.085
0
On=8 Off=8
1 mA
5.0 V dc
8 mA at 24 V dc n/a
Catalog Number
Voltage Category
Operating Voltage
Number of Inputs
Points Per Common
1746-IA16 (RTB)
100/120 V ac
85-132
16
1746-IB16 (RTB)
24 V dc
10-30
16
1746-IA16 0 V ac
30 V ac
85 V ac
Off- State
132 V ac
Input State Not Guaranteed
0 V dc
On- State
5 V dc
10 V dc
1746-IB16
30 V dc
Measure voltage between common terminal and input terminal.
Discrete Output Module Specifications Catalog Number
Voltage Category
Operating Voltage
Number of Outputs
Points per Common
1746-OA16 (RTB)
120/240 V ac
85-265
16
8
1746-OW16À (RTB)
V ac/V dc Relay
5-265 V ac 5-125 V dc
16
8
Backplane Current Draw 5v 24V 0.370 0.170
Signal Delay (ms. max)
Off State Leakage (max)
Load Current at 5 V dc (min.)
0
On=0.10 Off=11.0
2 mA
10 mA
0.180
On=10.0 Off=10.0
0 mA
10 mA
Continuous Current per Point (max.)
Continuous Current per Module (max.)
0.50 A at 30°C
8 A at 30°C
0.25 at 60°C
4 A at 60°C
See contact rating chart below.
16.0 A ac 8.0 A/ common
1746-OA16 0 V ac
85 V ac
265 V ac
Recommended Operating Range
Operation Not Guaranteed 0 V dc 0 V ac
5 V dc 5 V ac
If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 V ac even though the output is off.
1746-OW16
125 V dc 265 V ac
1746-OW16 Relay Contact Rating Chart Type
Relay Contact Ratings for 1746-OW16
Maximum Volts
240 V ac 120 V ac
AmpereÀ Make
Break
7.5 A 15.0 A
0.75 A 1.50 A
Amperes Continuous Â
2.5 A
Voltamperes Make
Break
1800 VA
180 VA
125 V dc
0.22 AÁ
1.0 A
28 VA
24 V dc
1.2 AÁ
2.0 A
28 VA
10A-55
Page 579
Section 10A I/O Interface
10A.7.1 Wiring 1746 Discrete I/O
L1
All modules are UL 508 listed and CSA 22.2 142 approved. These modules meet requirements for Class I division 2 hazardous location requirements of both Underwriter’s Laboratory and the Canadian Standards Association.
1746-IA16 IN 0 IN 2 IN 4 IN 6
100/120 V ac
IN 8 IN 10 IN 12 IN 14
L2
1746-IB16
+dc
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
24 V dc
IN 9
IN 8 IN 10
IN 11
IN 12
IN 13
IN 14
IN 15
---dc ac COM
100/240 V ac L2
OUT 3 CR
OUT 5
CR
OUT 7
OUT 11 CR CR
OUT 13 OUT 15
IN 9 IN 11 IN 13 IN 15
1746-OW16 +dc or L1
V dc or V ac 1 OUT 0
OUT 0
OUT 1
OUT 2 OUT 4 OUT 6
V dc V ac
CR
OUT 3 CR
OUT 5
CR
OUT 7
CR dc COM or L2 L1
V ac 2 OUT 9
IN 7
COMMONS CONNECTED INTERNALLY
1746-OA16
OUT 1
IN 5 ac COM
COMMONS CONNECTED INTERNALLY
V ac 1
IN 3 ac COM ac COM
L1
IN 1
OUT 8 OUT 10 OUT 12
CR
OUT 14
CR
100/240 V ac
CR CR
L2
OUT 2 OUT 4
CR
OUT 6
CR
V dc or OUT 9 V ac 2 OUT 8 OUT 11 OUT 10 OUT 13 OUT 12 OUT 15 OUT 14
+dc or L1
CR
V dc V ac
CR dc COM or L2
10A-56
Page 580
Section 10A I/O Interface
Selecting Voltage or Current Mode The NIO4V analog module has a user selectable DIP switch setting which allows you to configure the input channels as either current or voltage inputs. The switches are located on the analog module board. ATTENTION: Care should be taken to avoid connecting a voltage source to a channel configured for current input. Improper module operation or damage to the module can occur.
Voltage
1 2
ON
Switch 1 = Input Channel 0 Switch 2 = Input Channel 1
Current
10A.8 1746 Analog I/O
On - Current Mode Off - Voltage Mode
The module has two individual switches labeled 1 and 2. These switches control the input mode of input channel 0 and 1. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input. Output channels are always voltage mode and can not be configured.
Wiring 1746 Analog I/O Belden cable #8761 is recommended when wiring analog modules. Use the following guidelines in planning the system wiring for the analog modules: all analog common terminals (ANL COM) are electrically connected inside the modules. ANL COM is not connected to earth ground inside the module. 10A-57