Page 571

Section 10A I/O Interface

10A.5.5 E- Series Analog I/O Bipolar/Unipolar Configuration

The E--Series analog I/O module allows you to select between bipolar operation (--10V to +10V dc) and unipolar operation (0V to +10V dc). Select this using a dip switch located next to the node address switch (see Figure 10A.38). Bipolar or unipolar can be selected independently for the input and output channels. Figure 10A.38 E Series Analog I/O Node Address Switch Assembly Location

O1 2 3 4 N

Bipolar/Unipolar switches INPUT OUTPUT

This cover unsnaps and folds down to expose switches 11342-I

Switch positions are as follows: Unipolar (0 V dc to +10 V dc)

Bipolar (- 10 V dc to +10 V dc)

10A-48

Page 572

Section 10A I/O Interface

10A.6 1746 I/O

You can place several 1746I modules with 1746 I/O chassis in the 9/Series fiber-optic ring. Each 1746 I/O chassis must contain its own 1746I module (daisy chaining racks together using one 1746I module is not allowed). The number of I/O points/chassis is limited to the number of ASRN chips supported by the 9/Series fiber--optic ring. Use page 10B-10 to calculate how many ASRN chips are required for each I/O chassis. A maximum of 16 chassis are allowed on the 9/Series fiber-optic I/O ring. 1746 Series B I/O Chassis

1746I adapter module Three different fully equipped 1746 I/O chassis are available for the 9/Series I/O ring. These chassis contain the following I/O devices: Table 10A.AJ Standard 9/Series 1746 I/O Catalogs Catalog Number 8500-S115

Catalog Number 8500-S24

Catalog Number 8500-SANL

(1) 1746-A4

4 Slot Chassis

(1) 1746-A4

4 Slot Chassis

(1) 1746-A4

4 Slot Chassis

(1) 1746-P1

115/230V ac Power Supply

(1) 1746-P1

115/230V ac Power Supply

(1) 1746-P1

115/230V ac Power Supply

(1) 8500-1746I

I/O Ring Interface Adapter Module

(1) 8500-1746I

I/O Ring Interface Adapter Module

(1) 8500-1746I

I/O Ring Interface Adapter Module

(2) 1746-IA16

16 point 115V ac Input Module

(2) 1746-IB16

16 point 24V dc Input Module

(1) 1746-NIO4V

Analog Input Module

(1) 1746-OA16

16 point 115V ac Output Module

(1) 1746-OW16

16 point 24V dc Output Module

(1) 1746-N2

2 Empty Slot Covers

(1) set fiber optic connectors for connection to I/O ring

(1) set fiber optic connectors for connection to I/O ring

(1) set fiber optic connectors

For connection to I/O ring

Total I/O

32 115V ac Inputs 16 115V ac Outputs 3 ASRN chips

Total I/O

32 24V dc Inputs 16 24V dc Outputs 3 ASRN chips

Total I/O

2 analog input chnls. 2 analog output chnls 6 ASRN chips

10A-49

Page 573

Section 10A I/O Interface

10A.6.1 Removing/Installing 1746 Modules

The following procedure covers how to remove modules from your 1746 I/O chassis. In some cases it is necessary to remove a module to set or check dip switch settings. ATTENTION: Never install, remove, or wire modules with power applied to the chassis.

Removing a Module 1.

Label and remove any wiring or removable terminal blocks.

2. Gently press in on both the top and bottom latches of the module to be removed. 3. Slide the module out of the rack.

Installing a Module 1. Align the circuit board of the module with the card guide in the chassis. Important: You must install the 1746I module in the first slot of the chassis (slot immediately next to the power supply). The 1746I module takes the place of a CPU module or a ASB adapter module in this slot. Other modules should be returned to the same slot they were removed from. 2.

Gently slide the module in until both top and bottom latches are latched.

3.

Reconnect wires or removable terminal blocks.

Cover all unused slots with a Card Slot Filler, Catalog Number 1746-N2.

10A.6.2 1746I I/O Ring Adapter Node Address Setting

To install the 1746I module in the 9/Series I/O ring you must first assign the module an address on the 9/Series I/O ring. If the module is already installed in your 1746 I/O chassis, you must remove the module to set the module address. Remove the module by pressing in on the locking tabs on the top and bottom of the 1746I module and sliding the module out of the chassis. Assign an address to the module using the dip switch S1 found on the side of the 1746I module. Figure 10B.4 shows the location of the node address switch assembly on the 1746I module.

10A-50

Page 574

Section 10A I/O Interface

Figure 10A.39 1746 I/O Ring Adapter Switch Assembly Locations

ON

S1 1 2 3 4 5 6

Other 9/Series I/O devices (such as an HPG or MTB panel) on the 9/Series fiber-optic ring can have the same node address as the 1746I module. However, devices of the same type (multiple 1746I modules) must each have a unique node address. Each 1746 I/O ring adapter is assigned a unique node address in the I/O assignment file of ODS (refer to your PAL reference manual). This address corresponds to switch assembly S1 on the 1746I module. Set switch assembly S1 to correspond to the node address as shown in Table 10A.AK.

10A-51

Page 575

Section 10A I/O Interface

Table 10A.AK 1746I I/O Ring Adapter Node Address Setting Node Address

Switch Assembly Position

Hexadecimal

Binary

1

2

3

4

00

0000

OFF

OFF

OFF

OFF

01

0001

OFF

OFF

OFF

ON

02

0010

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0F

1111

ON

ON

ON

ON

Important: Switch 5 and 6 of S1 must remain in the OFF position for normal operation.

10A.6.3 1746P1 Power Supply

The following are the specifications and wiring instructions for the 1746 P1 power supply.

Set the Input Voltage Jumper 1.

Locate the input voltage jumper. If necessary, remove and reinstall the jumper to match the external voltage available. ATTENTION: Set the input jumper before applying power. Hazardous voltage is present on exposed pins when power is applied: contact with the pins may cause injury to personnel.

100/120 V

200/240 V push latch up from underneath to open the door

10A-52

Page 576

Section 10A I/O Interface

2.

Wire the power supply terminals as shown below. These terminals accept two #14AWG wires.

PWR OUT +24 V dc PWR OUT COM L1, 120/240 V L2, V ac NEUTRAL, PE

ATTENTION: Turn off power lines before connecting power; failure to do so could cause injury to personnel and/or equipment.

20151

Table 10A.AL 1746 P1 Power Supply Specifications Description:

Specification:

Line Voltage

85- 132/170- 265 V ac 50/60 Hz

Typical Line Power Requirement

135 VA

Internal Current Capacity

2 AMP at 5 V dc 0.46 AMP at 24 V dc

User Current Capacity

24 V dc - 0.2 AMP

Fuse Protection

3 AMPs

Ambient Operating Temperature Rating

0 to +55°C (Current capacity derated by 5% at +60°C)

Humidity Rating

5 - 95% (noncondensing)

Wiring

#14 AWG

10A-53

Page 577

Section 10A I/O Interface

10A.6.4 1746 I/O Ring Adapter Fiber Optic Connection

The connectors used to make the fiber optic connections to the I/O ring are listed in Table 10A.AM. Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the I/O ring. Refer to Appendix A for additional information on fiber optic cables and connectors. The fiber-optic connectors are located under the front door of the 1746I module for easy access. Run the fiber-optic cables out the bottom of the 1746I module to allow the front door of the module to close after the cables have been installed. Table 10A.AM 1746 I/O Ring Adapter Fiber Optic Connectors Connector on Digital I/O

10A.7 1746 Discrete I/O Racks

Remark

Connected To

I/O (RED)

Output

Receiver on next module in I/O ring

I/O (BLACK)

Input

Transmitter on previous module in I/O ring

The following tables give input and output specifications for the standard 1746 I/O modules available for the 9/Series fiber-optic I/O ring. Contact your Allen-Bradley sales representative for details on any modules not listed here. See page 10B-8 for details on other 9/Series compatible 1746 I/O modules.

General 1746 Discrete I/O Module Specifications Description:

NEMA-Standard ICS 2-230

Vibration (operating)

Displacement - .015 inch peak to peak at 5 - 57 Hz Acceleration - 2.5 G at 57 - 2000 Hz

Shock (operating)

30 G

Isolation

1500 V

Environmental conditions Operating temperature Storage temperature Humidity rating

0 to +60°C (+32°to +140°F) -40°to +85°C (- 40°to +185°F) 5 to 95% (noncondensing)

Certification

UL listed, CSA approved

Hazardous Environment Classification

Class I, Division 2 Hazardous Environment.À

À

10A-54

Specification

Noise Immunity

Some modules are excluded from this certification. Refer to the following tables for a complete listing.

Page 578

Section 10A I/O Interface

Discrete Input Module Specifications Backplane Current Draw 5V 24V

Signal Delay (ms. max)

Off-State Current (max)

Off-State Voltage (max)

Nominal Input Current

Inrush Current (max)

16

0.085

0 on=35 Off=45

2 mA

30 V ac

12 mA at 120 V ac

0.8 A

16

0.085

0

On=8 Off=8

1 mA

5.0 V dc

8 mA at 24 V dc n/a

Catalog Number

Voltage Category

Operating Voltage

Number of Inputs

Points Per Common

1746-IA16 (RTB)

100/120 V ac

85-132

16

1746-IB16 (RTB)

24 V dc

10-30

16

1746-IA16 0 V ac

30 V ac

85 V ac

Off- State

132 V ac

Input State Not Guaranteed

0 V dc

On- State

5 V dc

10 V dc

1746-IB16

30 V dc

Measure voltage between common terminal and input terminal.

Discrete Output Module Specifications Catalog Number

Voltage Category

Operating Voltage

Number of Outputs

Points per Common

1746-OA16 (RTB)

120/240 V ac

85-265

16

8

1746-OW16À (RTB)

V ac/V dc Relay

5-265 V ac 5-125 V dc

16

8

Backplane Current Draw 5v 24V 0.370 0.170

Signal Delay (ms. max)

Off State Leakage (max)

Load Current at 5 V dc (min.)

0

On=0.10 Off=11.0

2 mA

10 mA

0.180

On=10.0 Off=10.0

0 mA

10 mA

Continuous Current per Point (max.)

Continuous Current per Module (max.)

0.50 A at 30°C

8 A at 30°C

0.25 at 60°C

4 A at 60°C

See contact rating chart below.

16.0 A ac 8.0 A/ common

1746-OA16 0 V ac

85 V ac

265 V ac

Recommended Operating Range

Operation Not Guaranteed 0 V dc 0 V ac

5 V dc 5 V ac

If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 V ac even though the output is off.

1746-OW16

125 V dc 265 V ac

1746-OW16 Relay Contact Rating Chart Type

Relay Contact Ratings for 1746-OW16

Maximum Volts

240 V ac 120 V ac

AmpereÀ Make

Break

7.5 A 15.0 A

0.75 A 1.50 A

Amperes Continuous Â

2.5 A

Voltamperes Make

Break

1800 VA

180 VA

125 V dc

0.22 AÁ

1.0 A

28 VA

24 V dc

1.2 AÁ

2.0 A

28 VA

10A-55

Page 579

Section 10A I/O Interface

10A.7.1 Wiring 1746 Discrete I/O

L1

All modules are UL 508 listed and CSA 22.2 142 approved. These modules meet requirements for Class I division 2 hazardous location requirements of both Underwriter’s Laboratory and the Canadian Standards Association.

1746-IA16 IN 0 IN 2 IN 4 IN 6

100/120 V ac

IN 8 IN 10 IN 12 IN 14

L2

1746-IB16

+dc

IN 0

IN 1

IN 2

IN 3

IN 4

IN 5

IN 6

IN 7

24 V dc

IN 9

IN 8 IN 10

IN 11

IN 12

IN 13

IN 14

IN 15

---dc ac COM

100/240 V ac L2

OUT 3 CR

OUT 5

CR

OUT 7

OUT 11 CR CR

OUT 13 OUT 15

IN 9 IN 11 IN 13 IN 15

1746-OW16 +dc or L1

V dc or V ac 1 OUT 0

OUT 0

OUT 1

OUT 2 OUT 4 OUT 6

V dc V ac

CR

OUT 3 CR

OUT 5

CR

OUT 7

CR dc COM or L2 L1

V ac 2 OUT 9

IN 7

COMMONS CONNECTED INTERNALLY

1746-OA16

OUT 1

IN 5 ac COM

COMMONS CONNECTED INTERNALLY

V ac 1

IN 3 ac COM ac COM

L1

IN 1

OUT 8 OUT 10 OUT 12

CR

OUT 14

CR

100/240 V ac

CR CR

L2

OUT 2 OUT 4

CR

OUT 6

CR

V dc or OUT 9 V ac 2 OUT 8 OUT 11 OUT 10 OUT 13 OUT 12 OUT 15 OUT 14

+dc or L1

CR

V dc V ac

CR dc COM or L2

10A-56

Page 580

Section 10A I/O Interface

Selecting Voltage or Current Mode The NIO4V analog module has a user selectable DIP switch setting which allows you to configure the input channels as either current or voltage inputs. The switches are located on the analog module board. ATTENTION: Care should be taken to avoid connecting a voltage source to a channel configured for current input. Improper module operation or damage to the module can occur.

Voltage

1 2

ON

Switch 1 = Input Channel 0 Switch 2 = Input Channel 1

Current

10A.8 1746 Analog I/O

On - Current Mode Off - Voltage Mode

The module has two individual switches labeled 1 and 2. These switches control the input mode of input channel 0 and 1. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input. Output channels are always voltage mode and can not be configured.

Wiring 1746 Analog I/O Belden cable #8761 is recommended when wiring analog modules. Use the following guidelines in planning the system wiring for the analog modules: all analog common terminals (ANL COM) are electrically connected inside the modules. ANL COM is not connected to earth ground inside the module. 10A-57