Page 581
Section 10A I/O Interface voltages on IN+ and IN-- terminals terminals must remain within ±20 Volts with respect to ANL COM for proper input channel operation. This is true for current and voltage input channel operation. voltage outputs (OUT 0 and OUT 1) are referenced to ANL COM. Load resistance (R1) for a voltage output channel must be equal to or greater than 1K ohms. current output channels (OUT 0 and OUT 1) source current that returns to ANL COM. Load resistance (R1) for a current output channel must remain between 0 and 500 ohms. input connections for single-ended or differential inputs are the same. ATTENTION: Before wiring any analog module, disconnect power from the chassis and from any other source to the analog module.
Grounding Your Cable Belden cable #8761 has two signal wires (black and clear), one drain wire and a foil shield. The drain wire and foil shield must be grounded at one end of the cable. Do not earth ground the drain wire and foil shield at both ends of the cable. Input Channel -- Ground the drain wire and foil shield near the sourcing device. Output Channel -- Use a rack mounting tab as a ground for the drain wire and foil shield. Important: If you cannot ground the input channel at the sourcing device, ground the drain wire and foil shield at the rack mounting tab. Do not connect the foil shield or drain wire to the analog terminal block. They must be connected to an earth ground, which is not provided at the analog module.
10A-58
Page 582
Section 10A I/O Interface
Analog Module NIO4V OUTPUT INPUT POWER
ANALOG
(0) IN 0+ (1) IN 0(2) ANL COM (3) IN 1+ (4) IN 1-
+ Analog source -
(0) IN 0+ (1) IN 0-
PE
(2) ANL COM (3) IN 1+ (4) IN 1-
(5) ANL COM
(5) ANL COM
(6) NOT USED
(6) NOT USED
(7) OUT 0
(7) OUT 0
(8) ANL COM
(8) ANL COM
(9) NOT USED
(9) NOT USED
(10) OUT 1
(10) OUT 1
(11)ANL COM
(11)ANL COM
Jumper unusedinputs
+ Analog Load Do not jumper unused outputs
PE
1746- NIO4V
Reading/Writing Analog Data The analog I/O module passes values to PAL through the I/O ring. The variable used to read/write the analog I/O module data is assigned using the PAL I/O assigner (refer to your 9/Series PAL Reference Manual for details). The following table shows the values of these PAL variables: Table 10A.AN Analog Input Decimal Values (to PAL) Voltage/Current Range
Decimal Representation
Number of Significant Bits
- 10V to + 10V (1LSB)
- 32,768 to + 32,767
16 bits
0V to 10 V (1LSB)
0 to 32,767
15 bits
0V to 5V
0 to 16,384
14 bits
1V to 5V
3,277 to 16,384
13.67 bits
- 20mA to +20mA
- 16,384 to +16,384
15 bits
0 to +20mA
0 to 16,384
14 bits
4 to +20 mA
3,277 to 16,384
13.67 bits
Resolution per LSB
305.176mV
1.22070mA
10A-59
Page 583
Section 10A I/O Interface
To determine an approximate voltage that an input value represents, use one of the following equations: 10 V (input value) = input voltage (V) 32,768 or for current 20 mA ( input value) = input voltage (V) 16,384 For example, if an input value of - 16,021 is in the input image, the calculated input voltage is: 10 V (- 16,021) = - 4.889221 V 32,768
This is the calculated value. The actual value may vary within the accuracy limitations of the module.
Table 10A.AO Analog Output Decimal Values (from PAL) Voltage/Current Range
Decimal Representation
Number of Significant Bits
- 10V to + 10V (1 LSB)
- 32,768 to + 32,767
14 bits
0V to 10 V (1 LSB)
0 to 32,767
13 bits
0V to 5V
0 to 16,384
12 bits
1V to 5V
3,277 to 16,384
11.67 bits
0 to +21mA
0 to +32,764
13 bits
0 to +20mA
0 to 31,208
12.92 bits
4 to +20 mA
6,242 to 31,208
12.6 bits
Resolution per LSB 1.22070mV
2.56348mA
To determine a value for the PAL variable of an analog output to produce a desired output, use one of the following equations: 32,768 (desired voltage output V) = output decimal value 10 V dc or for current 32,768 ( desired current output mA) = output decimal value 21 mA For example, if an output voltage of +1 V dc is desired, the value to be put in the corresponding PAL variable would be: 32,768 10V dc
10A-60
(+1V dc) = 3277
Page 584
Section 10A I/O Interface
10A.8.1 Analog I/O Specifications (1746-NIO4V)
Features High resolution -- 16 bit input and 14 bit output converters provide accurate control capabilities. Backplane powered -- No external power supply required, reducing system cost. User selectable inputs -- Configurable per channel for current or voltage inputs. Input channel filtering -- Rejects high frequency noise that couples into an analog input signal. Image maps directly into the 1746I adapter. Isolation -- All analog modules are isolated from each other and from the backplane. Description
Specification
Input Channels per Module
2 differential, voltage or current selectable per channel
Output Channels per Module
2 voltage outputs, not individually isolated
Backplane Current Draw
55mA at 5V dc 115mA at 24 V dc
Communication Format
16 bit Two’s Complement Binary
Field Wiring to Backplane Isolation
500 V dc
Conversion Time
512ms for all channels in parallel
Current/Voltage Ranges NIO4V
±10 V dc or ±20 mA (input) ±10 V dc (output)
Step Response Input Output
60 ms at 95% 2.5 ms at 95%
Maximum Wire Size
#14 AWG
Terminal Block
Removable
Noise Immunity
NEMA Standard ICS 2-230
Environmental Conditions Operating temperature Storage temperature Humidity rating
0 to +60°C (+32°to +140°F) - 40°C to +85°C (- 40°to +185°F) 5 to 95% (noncondensing)
Recommended Cable
Belden #8761
Certification
UL 508 listed, CSA 22.2 142 approved
Hazardous Environment Classification
Class I, Division 2 Hazardous Environment
10A-61
Page 585
Section 10A I/O Interface
10A.9 1746 I/O Fault Status
If the 9/Series fiber optic I/O ring should fault or any other fault should occur within the 1746 I/O rack, the 1746I module will attempt to maintain all of its I/O in the same state condition. This holds all output devices in the chassis to their present state. (Outputs already ON remain ON, outputs already OFF remain OFF, and analog modules maintain their present output voltage). Wire your I/O devices accordingly considering all safety issues.
10A.9.1 Troubleshooting the 1746I Communication Module
This section provides diagnostic information for troubleshooting your 1746 I/O chassis using the LED’s on the front of the 1746I module. Also in this section is information on using test modes to diagnose any problems with the fiber-optic connections. OFF This LED Status ON Flashing
10A-62
Indicates this possible cause:
Run LED On
·The I/O ring and the 1746 I/O rack are communicating properly and the rack is functioning.
Rack LED On
·RAM or ROM failure at power turn on. ·Device in rack failed or is not seated properly. ·Internal error in the 1746I adapter.
Rack LED Flashing
·A card type was found in the rack at power turn on that is not supported by the 1746I module.
Ring LED On
·Connection or device has failed in the I/O ring for a device before the 1746I in the ring. ·Power turned off at the CNC. ·Transmitter and receiver cables are reversed.
Ring LED Flashing
·Connection or device has failed in the I/O ring for a device after the 1746I in the ring.
All LEDs Off
·Power turned off at the CNC while the ring was up and running. ·Connection of I/O ring broken before this 1746I module while the ring was up and running.
Page 586
Section 10A I/O Interface
10A.10 Fast I/O (9/260 and 9/290 only)
The Fast I/O feature provides 4 inputs to and 4 outputs from the control. This feature is used to make changes in PAL that will take effect the next iteration of the PAL program. Using the fast I/O feature, the operator can input values to the PAL program using the PAL flag $HSIN and output values using the PAL flag $HSOUT. The fast I/O connector on the motherboard provides an interface port for fast input and output to and from the control. This connector interfaces with cable C11. Refer to page 7A-26 for additional information on cable C11. Figure 10A.40 and Table 10A.AP show the connector and its pin assignments. Figure 10A.40 Fast I/O Connector (has pins)
1
2
3
4
5
6
7
8
9 11
10 12
13
14
15
16
10A-63
Page 587
Section 10A I/O Interface
Table 10A.AP Pin Assignments for the Fast I/O Connector (P3) (Not available on the 9/230 and 9/440 control) Pin No.
Signal Name
Pin No.
Signal Name
1
FAST_I1
9
FAST_O1
2
COM
10
COM
3
FAST_I2
11
FAST_O2
4
COM
12
COM
5
FAST_I3
13
FAST_O3
6
COM
14
COM
7
FAST_I4
15
FAST_O4
8
COM
16
COM
Allen-Bradley recommends that you use the terminal blocks shown in Figure 10A.41 to simplify the wiring between your control and the fast I/O. The fast I/O cable connects to the connector on the block. Use the pin assignments in Table 10A.AP to wire the terminal connections. Figure 10A.41 Recommended Terminal Blocks for Fast I/O Wiring
19203
Weidmueller RI-16 Idc R (rail-mounted) Cat. No. 914892 Weidmueller RI-16 Idc P (panel-mounted) Cat. No. 914903
10A-64
19204
Phoenix FLKM 16 Order No. 22 81 02 1
Page 588
Section 10A I/O Interface
Figure 10A.42 shows the fast I/O circuit. Figure 10A.42 Fast I/O Circuit (Not available on the 9/230 control) +5 V 1K F38
Fast I/O Output
+5 V 1.8K Fast I/O Input
PE
PE
Table 10A.AQ lists the input specifications for the fast I/O. Table 10A.AQ Fast I/O Input Specifications Item
Specification
Remark
Maximum Input Current - Low
IIL = 6mA/input
Source
Maximum Input Voltage - Low
VIL = 0.45V/input
-
Table 10A.AR lists the output specifications for the fast I/O. Table 10A.AR Fast I/O Output Specifications Not available on the 9/230 control Item
Specification
Remark
Minimum Output Voltage - High
VOH = 4.25V/output
-
Minimum Output Current - High
IOH = 300mA/output
Source
Maximum Output Voltage - Low
VOL = 0.5V/output
-
Maximum Output Current - Low
IOL = 13mA/output
Sink
10A-65
Page 589
Section 10A I/O Interface
10A.11 Wiring I/O Safely
Many safety issues present themselves to the machine tool builder when wiring I/O devices. Typically, 9/Series I/O devices attempt to maintain their current status in the event of a system failure, I/O ring fault, or E-STOP condition. Make sure that this is a safe state for your machine by following these guidelines. Make sure I/O is wired so power failure places the device in a safe condition. For example if an output point controls an axis brake, you would typically want the brake applied when the I/O device fails or loses power. Make sure I/O is wired so E-STOP condition places the device in a safe condition. Remember E-STOP conditions do not reset I/O devices. I/O devices attempt to maintain their last state when E-STOP occurred. For example if an output point controls an axis brake, you would typically want the brake applied when the E-STOP condition occurs. Brake Circuit When R1-1 is closed brake is released. If E-STOP string is broken, brake is engaged.
R1- 1
R2- 1 L2 (L)
L1 (H)
Customer supplied brake relay
R1
R2
Energizes Brake Relay E-STOP String PB2 Terminal Block COM
COM
A01
COM COM
A02 A03
B01 B02
A04
A05 A06 A07
B03 B04 B05
B06
A08 B07
A09
A10 COM
B08 B09
B10
Label
COM
Important: Notice in the above figure the E-STOP string only kills power to the terminal blocks of the I/O module which in turn de-energizes the brake relay. The actual I/O module on the I/O ring remains powered. Killing power to the I/O device itself while the fiber optic ring is still running can cause I/O ring fault errors.
END OF SECTION
10A-66
Page 590
Section
10B
9/Series Adapter Modules for 1771 and 1746 I/O Devices
10B.0 Section Overview
This section discusses using I/O adapter modules for the 9/Series I/O ring. These adapter modules allow you to use Allen-Bradley’s 1746 I/O or 1771 I/O modules in the 9/Series I/O ring. This is accomplished by placing an adapter module in the I/O chassis that will interface to the 9/Series fiber optic I/O ring. These modules always reside in the first slot of the I/O chassis and replace the logic controller CPU or ASB adapter module that would typically reside in the first slot. 1771 Series B I/O Chassis 1746 Series B I/O Chassis
1771 XIOC adapter module
10B.1 1771 I/O Ring Adapter Module
1746I adapter module
Use the 1771 I/O Ring Adapter Module to interface an Allen-Bradley 1771 series B I/O chassis with the control. The 1771 I/O ring adapter module provides the system installer with the option of using a 1771 series B I/O chassis for discrete inputs and discrete outputs to the control (only discrete I/O cards are compatible with the 1771 adapter module). Use page 10B-10 to calculate how many ASRN chips are required for each I/O chassis. The adapter module must be placed in the first slot of the 1771 series B I/O chassis. The 1771 series B I/O chassis is then interfaced with the fiber-optic I/O ring of the control using the fiber optic connectors on the adapter module. Refer to the Allen-Bradley 1771 I/O Ring Adapter Module Product Data Sheet, publication 8500-4.5.1, for additional information on this module. No more than 16 1771 I/O adapter modules can exist on the 9/Series I/O ring.
10B-1