Page 591

Section 10B

9/Series Adapter Modules for 1771 and 1746 I/O Devices

Figure 10B.1 shows the 1771 I/O ring adapter module. Figure 10B.1 1771 I/O Ring Adapter

ACTIVE

ADAPTER FAULT I/O RING FAULT I/O RING ADAPTER

ALLEN-BRADLEY RECEIVER

TRANSMITTER

REMOTE RESET

11086-I

10B.1.1 1771 I/O Ring Adapter Fiber Optic Connection

The connectors used to make the fiber optic connections to the I/O ring are listed in Table 10B.A. Each module connected to the system I/O ring has an optical transmitter and receiver. Fiber optic cables connect transmitters to receivers to form the I/O ring. Refer to Appendix A for additional information on fiber optic cables and connectors. Table 10B.A 1771 I/O Ring Adapter Fiber Optic Connectors Connector on Digital I/O

10B-2

Remark

Connected To

I/O (RED)

Output

Receiver on next module in I/O ring

I/O (BLACK)

Input

Transmitter on previous module in I/O ring

Page 592

Section 10B 9/Series Adapter Modules for 1771 and 1746 I/O Devices

10B.1.2 1771 I/O Ring Adapter Node Address Setting

Different types of I/O devices can have the same node address, but devices of the same type must each have a unique node address. Each 1771 I/O ring adapter is assigned a unique node address in the I/O assignment file of ODS. This address corresponds to a switch setting on the device itself. Up to 16 addresses are available. Figure 10B.2 shows the location of the node address switch assembly on the 1771 I/O ring module. Figure 10B.2 1771 I/O Ring Adapter Switch Assembly Locations

S1

S2

S3

OPEN

1 2 3 4 5 6 7 8

OFF

ON

11343-I

Important: Switch assemblies S1 and S2 indicate which slots in the I/O chassis have modules installed and operating. Refer to the Allen-Bradley 1771 I/O Ring Adapter Module Product Data Sheet, publication 8500-4.5.1, for additional information on this module. Set switch assembly S3 to correspond to the node address as shown in Table 10B.B. Important: Switch numbers 7 and 8 of switch assembly S3 are not used. Their position should not be altered.

10B-3

Page 593

Section 10B

9/Series Adapter Modules for 1771 and 1746 I/O Devices

Table 10B.B 1771 I/O Ring Adapter Node Address Setting Node Address

Switch Assembly Position

Hexadecimal

Binary

6

5

4

3

2

1

00

00 0000

OFF

OFF

OFF

OFF

OFF

OFF

01

00 0001

OFF

OFF

OFF

OFF

OFF

ON

02

00 0010

OFF

OFF

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0F

00 1111

OFF

OFF

ON

ON

ON

ON

Important: The 3D, 3E, and 3F node addresses are used for diagnostics purposes only.

10B-4

Page 594

Section 10B 9/Series Adapter Modules for 1771 and 1746 I/O Devices

10B.2 1746 I/O Ring Adapter Module

Use the 1746 I/O Ring Adapter Module to interface Allen-Bradley 1746 I/O devices with your 9/Series control. The 1746 I/O ring adapter module provides the system installer with the option of using 1746 I/O devices in the 9/Series fiber--optic I/O ring. The adapter module must be placed in the first slot (slot 0) of the 1746 series B I/O chassis. The 1746 I/O ring adapter module provides the interface between the 1746 I/O chassis and the fiber-optic I/O ring of the control using the fiber--optic connectors on the adapter module. Figure 10B.3 1746I I/O Ring Adapter

You can place several 1746I modules with 1746 I/O chassis in the 9/Series fiber-optic ring. Each 1746 I/O chassis must contain its own 1746I module (daisy chaining racks together using one 1746I module is not allowed). The number of I/O points/chassis is limited to the number of ASRN chips supported by the 9/Series fiber--optic ring. Use page 10B-10 to calculate how many ASRN chips are required for each I/O chassis. A maximum of 16 chassis are allowed on the 9/Series fiber-optic I/O ring.

10B.2.1 1746I I/O Ring Adapter Node Address Setting

To install the 1746I module in the 9/Series I/O ring you must first assign the module an address on the 9/Series I/O ring. If the module is already installed in your 1746 I/O chassis, you must remove the module to set the module address. Remove the module by pressing in on the locking tabs on the top and bottom of the 1746I module and sliding the module out of the chassis.

10B-5

Page 595

Section 10B

9/Series Adapter Modules for 1771 and 1746 I/O Devices

Assign an address to the module using the dip switch S1 found on the side of the 1746I module. Figure 10B.4 shows the location of the node address switch assembly on the 1746I module. Figure 10B.4 1746 I/O Ring Adapter Switch Assembly Locations

ON

S1 1 2 3 4 5 6

Other 9/Series I/O devices (such as an HPG or MTB panel) on the 9/Series fiber-optic ring can have the same node address as the 1746I module. However, devices of the same type (multiple 1746I modules) must each have a unique node address. Each 1746 I/O ring adapter is assigned a unique node address in the I/O assignment file of ODS (refer to your PAL reference manual). This address corresponds to switch assembly S1 on the 1746I module. Set switch assembly S1 to correspond to the node address as shown in Table 10B.C.

10B-6

Page 596

Section 10B 9/Series Adapter Modules for 1771 and 1746 I/O Devices

Table 10B.C 1746I I/O Ring Adapter Node Address Setting Node Address

Switch Assembly Position

Hexadecimal

Binary

1

2

3

4

00

0000

OFF

OFF

OFF

OFF

01

0001

OFF

OFF

OFF

ON

02

0010

OFF

OFF

ON

OFF

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0F

1111

ON

ON

ON

ON

Important: Switch 5 and 6 of S1 must remain in the OFF position for normal operation.

10B.2.2 1746 I/O Fault Status

If the 9/Series fiber optic I/O ring should fault or any other fault should occur within the 1746 I/O rack, the 1746I module will attempt to maintain all of its I/O in the same state condition. This holds all output devices in the chassis to their present state. (Outputs already ON remain ON, outputs already OFF remain OFF, and analog modules maintain their present output voltage). This does not necessarily apply if the 1746I module is the cause of the fault. Wire your I/O devices accordingly considering all safety issues.

10B.2.3 9/Series 1746 I/O Catalogs

Three different fully equipped 1746 I/O chassis are available for the 9/Series I/O ring. See page 10A-49 for details on these I/O devices.

Catalog Number 8500-S115

Catalog Number 8500-S24

Catalog Number 8500-SANL

(1) 1746-A4

4 Slot Chassis

(1) 1746-A4

4 Slot Chassis

(1) 1746-A4

4 Slot Chassis

(1) 1746-P1

115/230V ac Power Supply

(1) 1746-P1

115/230V ac Power Supply

(1) 1746-P1

115/230V ac Power Supply

(1) 8500-1746I

I/O Ring Interface Adapter Module

(1) 8500-1746I

I/O Ring Interface Adapter Module

(1) 8500-1746I

I/O Ring Interface Adapter Module

(2) 1746-IA16

16 point 115V ac Input Module

(2) 1746-IB16

16 point 24V dc Input Module

(1) 1746-NIO4V

Analog Module

(1) 1746-OA16

16 point 115V ac Output Module

(1) 1746-OW16

16 point 24V dc Output Module

(1) 1746-N2

2 Empty Slot Covers

(1) set fiber optic connectors

For connection to I/O ring.

(1) set fiber optic connectors

For connection to I/O ring.

(1) set fiber optic connectors

For connection to I/O ring.

Total I/O

32 115V ac Inputs 16 115V ac Outputs 3 ASRN chips

Total I/O

32 24V dc Inputs 16 24V dc Outputs 3 ASRN chips

Total I/O

2 analog input chnls. 2 analog output chnls 6 ASRN chips

10B-7

Page 597

Section 10B

9/Series Adapter Modules for 1771 and 1746 I/O Devices

10B.2.4 Other Compatible 1746 I/O Modules

Catalog Number:

The following 1746 chassis and I/O modules are compatible when used with a 1746I module on the 9/Series fiber-optic I/O ring. Other modules not listed here may also be compatible. Call your Allen-Bradley sales office for details on compatibility with any 1746 I/O modules not listed here.

Description:

Chassis 1746- A4

4- Slot Chassis

1746- A7

7- Slot Chassis

1746- A10

10- Slot Chassis

1746- A13

13- Slot Chassis Power Supplies

1746- P1

Power Supply (120/240V ac)(2amp @ 5V dc)(.46amp @ 24V dc)

1746- P2

Power Supply (120/240V ac)(5amp @ 5V dc)(.96amp @ 24V dc)

1746- P3

Power Supply (24V dc)(3.6amp @ 5V dc)(.87amp @ 24V dc)

120V ac Input Modules 1746- IA4

120V ac 4 Input Module

1746- IA8

120V ac 8 Input Module

1746- IA16

120V ac 16 Input Module

240V ac Input Modules 1746- IM4

240V ac 4 Input Module

1746- IM8

240V ac 8 Input Module

1746- IM16

240V ac 16 Input Module

24V dc Input Modules 1746- IB8

24V dc 8 Input module (sink)

1746- IB16

24V dc 16 Input Module (sink)

1746- IB32

24V dc 32 Input Module (sink)

1746- IV8

24V dc 8 Input Module (source)

1746- IV16

24V dc 16 Input Module (source)

1746- IV32

24V dc 32 Input Module (source)

120V ac Output Modules 1746- OA8

120V ac 8 Output Module

1746- OAP12

120V ac 12 Output Module

1746- OA16

120V ac 16 Output Module

24V dc Output Modules

10B-8

1746- OB8

24V dc 8 Output Module (source)

1746- OB16

24V dc 16 Output Module (source)

1746- OB32

24V dc 32 Output Module (source)

1746- OV8

24V dc 8 Output (sink)

Page 598

Section 10B 9/Series Adapter Modules for 1771 and 1746 I/O Devices

Catalog Number:

Description:

1746- OV16

24V dc 16 Output Module (sink)

1746- OV32

24V dc 32 Output Module (sink)

V ac/V dc Relay Output Modules 1746- OW4

V ac/V dc Relay 4 Output Module

1746- OW8

V ac/V dc Relay 8 Output Module

1746- OW16

V ac/V dc Relay 16 Output Module

1746- IO4

120V ac 2 Inputs & ac/dc Relay 2 Outputs

1746- IO8

120V ac 4 Inputs & ac/dc Relay 4 Outputs

1746- IO12

120V ac 6 Inputs & ac/dc Relay 6 Outputs

Analog I/O Modules 1746- NI4

Analog 4 Input Module (- 20ma to +20ma) or (- 10V dc to +10V dc)

1746- NIO4I

Analog 2 Inputs (- 20ma to +20ma) or (- 10V dc to +10V dc) & 2 Outputs (0 to 20ma)

1746- NIO4V

Analog 2 Inputs (- 20ma to +20ma) or (- 10V dc to +10V dc) & 2 Outputs (- 10V dc to + 10V dc)

1746- NO4I

Analog 4 Output Module (0 to 20ma)

1746- NO4V

Analog 4 Output Module (- 10V dc to +10V dc)

Specialty I/O Modules 1746- IG16

5V dc/TTL 16 Input Module (source)

1746- OG16

5V dc/TTL 16 Output Module (sink)

1746- OBP16

24V dc 16 Output Module (enhanced source)

1746- IN16

24V ac/V dc 16 Input Module (source)

1746- OX8 ac/dc Isolated Relay 8 Output Module

Important: To configure a 12--bit I/O module using the I/O assignments application, you must select a 16--bit device, while only assigning the first 12 I/O points.

10B-9

Page 599

Section 10B

9/Series Adapter Modules for 1771 and 1746 I/O Devices

10B.2.5 Troubleshooting the 1746I Communication Module

This section provides diagnostic information for troubleshooting your 1746 I/O chassis using the LEDs on the front of the 1746I module. Also in this section is information on using test modes to diagnose any problems with the fiber-optic connections. OFF This LED Status ON Flashing

10B.3 1771 and 1746 I/O adapter ASRN Use

Indicates this possible cause:

Run LED On

·The I/O ring and the 1746 I/O rack are communicating properly and the rack is functioning.

Rack LED On

·RAM or ROM failure at power turn on. ·Device in rack failed or is not seated properly. ·Internal error in the 1746I adapter.

Rack LED Flashing

·A card type was found in the rack at power turn on that is not supported by the 1746I module.

Ring LED On

·Connection or device has failed in the I/O ring for a device before the 1746I in the ring. ·Power turned off at the CNC. ·Transmitter and receiver cables are reversed.

Ring LED Flashing

·Connection or device has failed in the I/O ring for a device after the 1746I in the ring.

All LEDs Off

·Power turned off at the CNC while the ring was up and running. ·Connection of I/O ring broken before this 1746I module while the ring was up and running.

Use this section to calculate the number of ASRN chips used by the 1771 or 1746 I/O chassis in your system. Each chassis uses a different number of ASRN chips depending on the size of the chassis and the number and types of I/O devices in the chassis. Each different 9/Series control supports a limited number of ASRN chips on its I/O ring. Refer to Table 10A.B for the number of ASRN chips supported on the ring for your specific 9/Series processor.

10B-10

Page 600

Section 10B 9/Series Adapter Modules for 1771 and 1746 I/O Devices

The following section describes how to calculate how many ASRN chips are used by either the 1771 or 1746 I/O devices. Refer to page 10A-2 for information on the number of ASRN chips used by other 9/Series I/O ring devices.

ASRN Chip Used by 1771 and 1746 I/O Chassis The number of ASRN chips used by a 1746 or 1771 I/O chassis will vary depending on the chassis size and the number and type of I/O cards installed in the chassis. Different size chassis have a minimum number of ASRN chips required (regardless of the number of I/O points) and different I/O devices in the chassis require different numbers of ASRN. To determine the number of ASRN “chips” used by the I/O chassis in a specific I/O ring application, use the following procedure: 1.

Determine “A”, the minimum chassis ASRN requirements: 1771 I/O Chassis

1746 I/O Chassis Chassis Size:

Minimum number of ASRN chips:

Chassis Size:

Minimum number of ASRN chips:

4 slot (1746-B4)

A=3

4 slot

A=3

7 slot (1746-B7)

A=4

8 slot

A=5

10 slot (1746-B10)

A=6

12 slot

A=7

13 slot (1746-B13)

A=7

16 slot

A=8

2.

Calculate “B” chassis input requirements:

(discrete inputs) + (16)(number of analog input channels) 11

3.

=B (round up)

Calculate “C” chassis output requirements:

(discrete outputs) + (16)(number of analog output channels) 6

=C (round up)

10B-11