Section 2A Planning Your System Layout

Table 2A.B Component and Module Heat Generation Wattages Component or Module

Heat Generation Wattage (W)

9/230 and Main Power Supply

130

9/260 or 9/290 and Main Power Supply

225

9/440 CNC/1394 Drive 5kw System Module (@100%)

80

9/440 CNC/1394 Drive 10kw System Module (@100%)

98

9/440 Axis Modules/1394 Drive (each module @100%)

AM03 48

AM04 63

AM07 93

9/440 CNC Power On/Off Control Module

5

Portable Operator Panel Interface Assembly

72

Monochrome Operator Panel

125

Color TFT Operator Panel (flat panel)

55

Color CRT Operator Panel

175

MTB Panel

15

HPG

1.2

3-axis Digital Servo Module

13.5

3-axis Analog Servo Module

14

4-axis Digital Servo Module (8520-ENC4)

15

4-axis Analog/1394 Servo Module (8520-SM4)

14

1746I Ring Adaptor (module only)

0.9

1771-HTE Termination Panel

0

MTB Panel I/O Module

5

Remote I/O Module (8520- RIOM)

4.2

AM75 346*

* 18 Watts in cabinet, 328 Watts out through cabinet heat sink

The temperature rise inside a metallic cabinet incorporating only an internal convection cooling fan can be roughly calculated with the following formula: T = W/6S

- T = Temperature rise in cabinet (°C) - W = Heat generation (Watts) by units and modules - S = Heat radiation surface area (sq. meter) of cabinet (total cabinet surface area minus any area in contact with the floor or building wall) The above equation assumes a closed cabinet with heat dissipated only through cabinet radiation.

2A-6

Page 52

Section 2A Planning Your System Layout

Example of Calculating Cabinet Temperature A design example of a cabinet is given below assuming a component-type frame incorporating the following: Main Power Supply (PS1)

225 watts @ 500 C

Main Power Supply (PS2A)

130 watts @ 500 C

CPU Board

33.5 watts

3-axis Digital Servo module

13.5 watts

The total heat generation (W) for this example would be 47W. 1.

Determine a minimum T value for the equation in the previous section:

a.

Estimate the maximum air temperature at the location where the cabinet will be installed.

b.

Subtract this estimate from the maximum internal cabinet temperature for your application (if you use 55°C, there is no margin for error). The difference is the allowable temperature rise in the cabinet (T). For example, assume a maximum air temperature of 35°C and a desired maximum internal cabinet temperature of 45°C, The value of T would be 45 - 35 = 10

2.

Using the W and T values just derived, calculate the minimum heat radiation surface area, S. T = W/6S S = W/6T = 47/(6 x 10) = 0.783 sq. meter (8.4 sq. feet)

This result indicates that a cabinet with a minimum of 0.783 m2 (8.4 ft2) of heat radiation surface is required. Important: Any cabinet surface in contact with the floor or building wall is not considered a heat radiation surface in this calculation. If the resulting cabinet size is prohibitively large, or if the T value calculated was 10 or more, then the use of a heat exchanger or air conditioner must be considered. Such designs require more detailed analysis, beyond that considered within scope of this manual. Important: The temperature rise value used in this calculation is a constant. Actual temperature rise will vary depending on the amount of air flow inside the cabinet.

2A-7

Page 53

Section 2A Planning Your System Layout

2A.5 Reducing Noise

For information on noise prevention measures refer to page 7C-1. We mention them here because these factors should be taken into consideration during the beginning stages of cabinet design. These noise prevention measures are covered in that section: Signal Grounding Mechanical Shielding Shielded Cables and Twisted-pair Cables Separation of Cable Routes Noise Suppressors

2A.6 Installing the Components

Install the components in the cabinet with at least 100 mm (4 inches) of clearance between the cabinet side wall and each component to allow air flow inside the cabinet. Install the components in the cabinet with 50 mm (2 inches) of clearance between them. The system installer should also consider any local regulations regarding component placement within a cabinet. ATTENTION: Do not install modules above heat generating devices (transformers, resistors, etc.)

Figure 2A.3 shows the minimum component spacing.

2A-8

Page 54

Section 2A Planning Your System Layout

Figure 2A.3 Minimum Component Spacing to Allow Air Flow in the Cabinet 100 (3.94)

100 (3.94)

100 (3.94)

mm (in)

Enclosure 100 (3.94)

50 (1.97)

50 (1.97) 100 (3.94)

100 (3.94)

50 (1.97)

50 (1.97)

100 (3.94)

9/440 CNC and digital amplifiers see page 2A-11

100 (3.94)

Follow the minimum component spacing requirements when designing the electrical system layout. You can reduce noise by placing the modules at least 50 mm apart. If this is not possible, install an electrically conductive metallic shield plate between the units. Place all devices at least 100 mm from the cabinet walls. For additional information on electrical system design requirements refer to 4D-1. ATTENTION: Do not install the control close to equipment, such as an arc welder, power transformer, or large motor, that generates high level noise.

2A-9

Page 55

Section 2A Planning Your System Layout

Installing Servo Modules Digital and analog servo modules include processors that make them very sensitive to electrical noise. These modules must be placed more than 100 mm (4 in) away from devices and cables to which any AC voltages or DC voltages greater than 50 Vdc are applied.

Installing Operator Panels You must place the Operator Panel more than 300 mm (12 inches) away from devices (transformers, main AC, electromagnetic contactors, etc.) that generate magnetic fields to protect the CRT display from any possible adverse effects. However, a strong magnetic field generated by multiple devices can have an adverse effect on the CRT display even if the operator panel is placed more than 300 mm away from these devices. If this occurs, shield the operator panel from the devices using an electromagnetic and electrostatic shield plate.

Installing Servo Amplifiers If you are installing analog servo amplifiers, refer to documentation that came with your amplifiers for specific installation instructions. If you are using digital servo amplifiers, place them vertically so that cooling air can flow upward and remove heat efficiently. Figure 2A.4 and Figure 2A.5 show the digital servo amplifier installation and spacing restrictions. If you are installing digital or analog servo amplifiers in the same cabinet as the control chassis (excluding the 9/440), then separate the amplifiers and the control chassis with a grounded, metallic plate to shield the control from electrical noise. You can use a cabinet with a center divider, where the power transformers and servo amplifiers are installed on one side, and the control, operator panel, and I/O modules installed on the other side.

2A-10

Page 56

Section 2A Planning Your System Layout

Figure 2A.4 1394 and 9/440 CNC Servo Amplifier Spacing Restrictions 50.8 (2.00) Clearance for Airflow and Installation

10.0 (0.4) Min. Along Side Allow 25.4 (1.00) Clearance at Cover Tab for Opening & Closing

Poor Instalation 10.0 (0.4) Min. along side Allow 50.8 (2.00) clearance for depth of terminator connector.

Dimensions are in millimeters and (inches) Wire Entry Area for Signal, Power and Motor Connections (min 152.4 (6.00)

Figure 2A.5 8520 Digital Servo Amplifier Spacing Restrictions mm (in) 100 (3.94) minimum

200 (7.87) minimum

Poor Installation 100 (3.94) minimum Servo Amplifier

Servo Amplifier

Servo Amplifier

Poor Installation

200 (7.87) minimum

Proper Installation

Servo Amplifier

END OF SECTION

2A-11

Page 57

Section 2A Planning Your System Layout

2A-12

Page 58

Section

2B

Mounting Dimensions 2B.0 Processor Dimensions

9/230 Component Enclosure

This section covers the dimensions and weight of the component for the 9/230. The dimensions outside of the brackets are given in millimeters and inside the brackets in inches. For additional information on this component refer to page 3A-1. Figure 2B.1 9/230 Analog Component Enclosure Dimensions mm (in.) 143 (5.60)

37.3 (1.47)

482.6 (19.0)

465.1 (18.31 )

8.8 (.34 5)

138.9 (5.47 )

6.5 (.26) INPUT 115/230V 8A/5.5A 47 - 63 Hz

TB1 354.0 (13.94 )

215.1 (8.47 )

TB2

TB3

J3

J2

J1

316.7 (12.47)

19415

The 9/230 enclosure weighs 6.2 kg (13.7 lb).

2B-1

Page 59

Section 2B Mounting Dimensions

Figure 2B.2 9/230 Digital Component Enclosure Dimensions 12.5 (.5)

125 (5) 87 (3.48)

mm (in.)

16.27 (.64)

125 (5)

375.0 (14.8)

400.0 (16) 226.16 (9.05)

Front View

The 9/230 enclosure weighs 6.75 kg (15 lb).

2B-2

Top View

Page 60

Section 2B Mounting Dimensions

9/260 and 9/290 Component Enclosures This section covers the dimensions and weight of the component for the 9/260 and the 9/290. The dimensions outside of the brackets are given in millimeters and inside the brackets in inches. For additional information on this component refer to page 4A-1. Figure 2B.3 9/260 and 9/290 Component Enclosure Dimensions mm (in.)

112.0 (4.41) 198.0 (7.80)

37.3 (1.47) 13.5 (.53) 138.9 (5.47)

354.0 (13.94)

6.5 (.26)

215.1 (8.47)

316.7 (12.47)

72.0 (2.84) 19101

465.1 (18.31)

324.3 (12.77) 482.6 (19.0)

The 9/260 and 9/290 component enclosure weighs 9.25 kg (20.41 lb).

2B-3