Page 872

Index 9/Series Integration and Maintenance Manual ii

Page 873

Section

17

Installing 9/Series Hardware for CE Compliance

17.0 Complying with European Union Directives

If your system is installed within the European Union, EEA regions, or has the CE mark, the following regulations apply:

EMC Directive This device is tested to meet Council Directive 89/336 Electromagnetic Compatibility (EMC) using a technical construction file and the following standards, in whole or in part: EN 50081--2 EMC -- Generic Emission Standard, Part 2 -- Industrial Environment EN 50082--2 EMC -- Generic Immunity Standard, Part 2 -- Industrial Environment The products described in this manual are intended for industrial use in an industrial environment. Use this table as a guide to determine what you need to know about your CE compliant Allen-Bradley product.

Low- voltage Directive This device is tested to meet Council Directive 73/23/EEC Low--voltage, by applying the safety requirements of EN 61131--2 Programmable Controllers, Part 2 -- Equipment Requirements of Tests. For specific information required by EN--61131--2, refer to the following Allen--Bradley publications: Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770--4.1 Guidelines for Handling Lithium Batteries, publication AG--5.4 Automation Systems Catalog, publication B111

17-1

Page 874

Section 17 Installing 9/Series for CE Compliance

17.1 Wiring AC Power for a CE Compliant System

If you are integrating a 9/Series that has a final destination within Europe you must attach a metal oxide varistor (MOV) to all connections that carry AC power to the system. If you have this control:

then you need to connect a varistor to:

9/230, 9/260 or 9/290 the incoming AC connection on the power supply

9/440 the incoming AC connection on the ON/OFF module

The types of MOV that you need are: AC Power Voltage 90-130 V AC

Manufacturer Harris

Part Number V130LA20B

130-265V AC

V275LA40B

These devices are available through several vendors, including Newark Electronics. They can be contacted at: Country

Phone Number

United Kingdom

(0420) 5433333

France

(1) 30-90-59-90

Germany

02 15 4-9 59 60

USA

312-784-5100

Here is an example of a typical MOV varistor connector on the 9/440 ON/OFF Control Module: ON/OFF Power Control Module

AC IN

L1

AC power source

C02

High

Low AC power source

L2 PE L1 AUX AC

L2 ON SW

COMMON OFF SW

17-2

Ground

Page 875

Section 17 Installing 9/Series Hardware for CE Compliance

Filtering Power for a 9/440 System To comply with CE guidelines you need to connect a power line filter to cable C55. The type of filter you need is: Product

Part Number

Manufacturer

Phone Number

Power Line Filter

MIF323-GS

Roxburgh Electronics LTD Foxhills Industrial Park Scuntharpe South Humberside, DN158Q5 United Kingdom

011-44-017-242-81770

Connect the power line filter to C55 as shown: Cable No.

Control

From Module and Connector

Cable Name

To Module and Connector

Cat. No.

C55

9/440

External 380/460V Three Phase

Drive Power

9/440 System Module Power Terminal Block

Prepared by Customer

9/440 Power Strip

Bussman FRS- R- 20A (min) 600 V AC FRS-R-30A (max) 600V AC or equivalent (qty 3)

Three-phase input 380-460V AC

DC+

INT

COL

W1

W2

U

V

W

C55

PE

LOAD

LINE

Power Line Filter AC Bulletin 100- A30N x 3 (surge protector required) or DC Bulletin 100- A30NZ x 3

Bulletin 100 Contactor Power

Noise suppressor

E-STOP Status Contactor (customer supplied or internal 9/440 TB1 status)

Connector On End of Cable

Cable Type

Connector On End of Cable

Max. Cable Length

Miscellaneous

See Local Codes (12Awg max)

Clamped by terminal screws

Line Drop Limitation

17-3

Page 876

Section 17 Installing 9/Series for CE Compliance

17.2 Wiring a High-Density I/O Module for CE Compliance

If you are using a High Density I/O module, you must wire all inputs and all outputs on the module with MOV varistors for surge protection. Here’s the type of MOV you need: DC Power Voltage

Manufacturer

24 V DC

Part Number

Harris

V392A6

This device is available through several vendors, including Newark Electronics. They can be contacted at: Country

Phone Number

United Kingdom

(0420) 5433333

France

(1) 30-90-59-90

Germany

02 15 4-9 59 60

USA

312-784-5100

Here is an example of a typical input and output connection on the high density I/O module that uses MOV varistors: CN61M or CN62M

Typical Input or Output

Terminal Board

1

1

2 3 4

G 2 G 3 G 4 G

33 34

Share current between the four “common”pins

17-4

35 36 37

C

MOV varistor

I/O Device

Page 877

Section 17 Installing 9/Series Hardware for CE Compliance

17.3 Wiring E-stop for CE Compliance

A CE compliant system must have noise-reducing components as part of its emergency stop wiring. When connecting E-stop to a 9/Series, place the ferrite suppressor core as close to the control as possible, as shown in these drawings: Figure 17.1 E-STOP Component Connection

E-STOP status relay

CR

E-STOP reset button

E-STOP button

Note: To meet CE compliance, the E- stop wire must pass through the suppressor core twice.

Pluggable E-STOP Connector

1 E-STOP 2 Common

On MTB panel

3 Reset 4

Customer E-STOP string E-STOP status relay contact connection

5 6

CR

+

7 8* customer supplied fuse (size to protect K1b contact and your E-Stop status relay) Ferrite Suppressor Core

*Important: If your control has terminal 8, then connect it to chassis ground. If terminal 8 is not present on your control, then this type of grounding is not necessary.

17-5

Page 878

Section 17 Installing 9/Series for CE Compliance

Figure 17.2 Typical Emergency Stop Circuit MTB PANEL

Reset button

Motherboard/Processor Board

E-STOP button

1

250mA 15 V dc from main power supply

Reduced to 12 V dc filter

2 K1A

3

MACHINE Extreme overtravel switches

Remote E-STOP button

4

Drive System Ready

5

Software

CR controlled Motor thermal switches may be connected directly

DRIVES ENCLOSURE

-

E-STOP status relay

Customer-supplied dc power

+

7 customer supplied fuse (size to protect K1b contact and your E-Stop status relay)

E-STOP

6

CR

Ferrite Suppressor Core

8

Contactors for E-STOP status controlled devices (servo amp contactor, indicators, brakes, coolant pumps, etc.)

circuit

K1B E-STOP relay K1 12 V dc coil Contact ratings: 30 V dc 1.4 A common

Important: If your control has terminal 8, then connect it to chassis ground. If terminal 8 is not present on your control, then this type of grounding is not necessary.

SYSTEM INSTALLER OPTIONS

Ferrite suppression cores can be aquired through several vendors, including Dexter Magnetic Materials Division (DMMD): Country

Phone

Germany

089-857-3071

United Kingdom

0753-680011

United States

1-800-345-4082

Ferrite Suppression Core Specification 250W @ 100 MHz

17-6

Manufacturer

Part Number

Fair- Rite Corporation

0443164151

Newark

95F 762

Page 879

Section 17 Installing 9/Series Hardware for CE Compliance

17.4 Modifying the Video Cable for CE Compliance

To meet CE compliance, a ferrite suppression core has to be installed around the video cable. Place the ferrite suppression core as close to the monitor as possible, as shown in this drawing:

Cable No.

Control

From Module and Connector

Cable Name

To Module and Connector

Cat. No.

C09

9/260 or 9/290

Motherboard J8

Video Signal Cable

Prepared by Customer

9/260 or 9/290

Processor Board J8

CN19M on Operator Panel or on Portable Operator Panel Interface Assembly

9/440

System Module J8 1 2 3 4 5 6 7 8

9 10 11 12 13 14

N.C. N.C.

N.C. N.C.

N.C. N.C. N.C. N.C. N.C. N.C.

N.C. N.C. N.C. N.C. N.C. N.C.

15

1 9 2 10 3 11 4 12 5 13 6 14 7 15 8

Monochrome monitor

1 9 2 10 3 11 4 12 5 13 6 14 7 15 8

Color monitor

Ferrite Suppressor Core 1 2 3 4 5 6 7 8

9 10 11 12 13 14

N.C. N.C. N.C. N.C.

N.C. N.C. N.C. N.C.

15

Ferrite Suppressor Core Connector On End of Cable

Cable Type

Connector On End of Cable

Max. Cable Length

15 Pin D-Shell (has pins) 8520-D15M

Belden 9503 (monochrome) Belden 9505 (color)

15 Pin D-Shell (has sockets) 8520-D15F

15m (50 ft)

17-7

Page 880

Section 17 Installing 9/Series for CE Compliance

Ferrite suppression cores can be aquired through several vendors, including Dexter Magnetic Materials Division (DMMD): Country

Phone

Germany

089-857-3071

United Kingdom

0753-680011

United States

1-800-345-4082

Ferrite Suppression Core 250W @ 100 MHz

17-8

Manufacturer

Part Number

Fair- Rite Corporation

0443164151

Newark

95F 762

Page 881

Section 17 Installing 9/Series Hardware for CE Compliance

17.5 1394 and 9/440 CE Requirements Enclosure

Ground Conduit to Enclosure Three- Phase Mains with Ground

Schaffner (or equivalent) E Filter

Conduit Clamp User- Supplied 24V Power Source Three- Phase Contactor

System PE Bus Enclosure

Note 1

360°shield termination at Enclosure by user. If you are using a 9/440 with optional feedback capability, 360° shielding is needed.

Resolver Feedback Cables

END OF APPENDIX

17-9