The text of a manual · part 15 of 46
Pico GFX-70 Controllers User Manual: 4 - Wiring with Pico GFX-70, pages 111 to 120
Pages 111 to 120 of 400, from Pico GFX-70 Controllers User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley GFX-70 1760-DUB
Page 111
Chapter
4
Wiring with Pico GFX-70
This chapter describes all the functions available with Pico GFX-70.
Pico GFX-70 Operation
Buttons for Drawing Circuit Diagrams and Function Block Usage
ALT
DEL OK ESC
*
DEL: Delete circuit connection, contact, relay or empty line in the circuit diagram. ALT: Toggle between break and make contact. Connect contacts and relays. Add circuit connections. Cursor buttons: (up, down): change values (left, right): change place Cursor buttons set as P buttons: (left): Input P1 (right): Input P3 (up): Input P2 (down): Input P4 OK: Change, add contact/relay Save setting ESC: Undo setting from previous OK Exit current display or menu *:Terminal mode on/off
1
Publication 1760-UM002B-EN-P - March 2005
Page 112
4-2
Wiring with Pico GFX-70
Operating Principles The cursor buttons in the Pico GFX-70 circuit diagram perform three functions. The current mode is indicated by the appearance of the flashing cursor. • Move • Entering • Connect In Move mode, you can the up, down, left, and right arrows buttons to move the cursor around the circuit diagram to select a circuit connection, contact or relay coil. Use OK to switch to Entry mode so that you can enter or change a value at the current cursor position. If you press ESC in Entry mode, Pico GFX-70 will undo the most recent changes. Press ALT to switch to Connect mode for wiring contacts and relays. Press ALT again to return to Move. Press ESC to leave the circuit diagram and parameter display.
IMPORTANT
Pico GFX-70 performs many of these cursor movements automatically. For example, Pico GFX-70 switches the cursor to Move mode if no further entries or connections are possible at the selected cursor position.
Opening the Parameter Display for Function Blocks with Contacts or Coils If you specify the contact or coil of a function relay type in Entry mode, the Pico GFX-70 automatically switches from the contact number to the function block parameter display when you press OK. Press the right arrow key to switch to the next contact or coil field without entering any parameters.
Publication 1760-UM002B-EN-P - March 2005
Page 113
Wiring with Pico GFX-70
4-3
Program A program is a sequence of commands which the Pico GFX-70 executes cyclically in RUN mode. A Pico GFX-70 program consists of the necessary settings for the device, the Pico-Link, Serial Interface, password, system settings, a circuit diagram and/or function blocks and/or the visualization screens. The circuit diagram is that part of the program where the contacts are connected together. In RUN mode a coil is switched on and off in accordance with the current flow and the coil function specified.
Function Blocks Function blocks are program elements with special functions. Example: timing relays, time switches, arithmetic function blocks. Function blocks are elements provided with or without contacts and coils as required. In RUN mode the function blocks are processed according to the circuit diagram and the results are updated accordingly. Examples: Timing relay = function block with contacts and coils Time switch = function block with contacts
Visualization Screens Visualization screens are the sections of programs containing the display and operator functions.
Relays Relays are switching devices which are electronically simulated in Pico GFX-70. They actuate their contacts according to their designated function. A relay consists of a coil and at least one contact.
Contacts You modify the current flow with the contacts in the Pico GFX-70 circuit diagram. Contacts such as make contacts carry a 1 signal when closed and 0 when open. Every contact in the Pico GFX-70 circuit diagram can be defined as either a make contact or a break contact.
Publication 1760-UM002B-EN-P - March 2005
Page 114
4-4
Wiring with Pico GFX-70
Coils Coils are the actuating mechanisms of relays. In RUN mode, the results of the wiring are sent to the coils, which switch on or off accordingly. Coils can have seven different coil functions. Table 4.1 Usable Contacts Contact
Pico GFX-70 display
Make contact, open in release position
I, Q, M, A, …. Other contacts a Table
Break contact, closed in release position i, q, m, a, … Other contacts a Table
Pico GFX-70 works with different contacts, which can be used in any order in the contact fields of the circuit diagram. Table 4.2 Contacts Contact
Make contact
Break contact
Number
Page
*I
*I
01…12
6-4
COM slave inputs
1I
1I
01..12
Pico GFX-70 input terminal
I
I
01…12
-
Cursor button
P
P
01…04
-
Network station expansion input terminal
*R
*R
01…12
6-4
1R
1R
01...12
Input terminal for expansion module
R
R
01…12
-
Bit inputs via the network
*RN
*RN
01…32
6-4
Inputs Inputs of a network station * = Station address 1 to 8
* = Station address 1 to 8 Input terminal for expansion module COM slave
* = Station address 1 to 8
Publication 1760-UM002B-EN-P - March 2005
Page 115
Wiring with Pico GFX-70
4-5
Table 4.2 Contacts Contact
Make contact
Break contact
Number
Page
*I
*I
14
8-8
*I
*I
15…16
8-7
COM slave expansion unit status
1I
1I
14
COM slave short-circuit/overload
1I
1I
15…16
Expansion status
I
I
14
8-8
Short-circuit/overload
I
I
15…16
8-7
Short-circuit/overload in expansion network station
*R
*R
15…16
8-7
Short-circuit/overload in COM slave expansion
1R
1R
15…16
Short circuit/overload with expansion
R
R
15…16
Deactivate backlight of the GFX display
LE
LE
01
Red LED of GFX display
LE
LE
02
Green LED of GFX display
LE
LE
03
Pico GFX-70 output Pico GFX-70 network station
*Q
*Q
01…08
COM slave output
1Q
1Q
01…08
Pico GFX-70 output
Q
Q
01…08
-
Pico GFX-70 output expansion with network station
*S
*S
01…08
6-4
Output of COM slave expansion
1S
1S
01…08
Pico GFX-70 output expansion
S
S
01…08
-
Bit outputs via the network
*SN
*SN
01…32
6-4
Diagnostics inputs Expansion network station status * = Station address 1 to 8 Network station short-circuit/overload * = Station address 1 to 8
* = Station address 1 to 8
8-7
Outputs
6-4
* = Station address 1 to 8
* = Station address 1 to 8
* = Station address 1 to 8
Publication 1760-UM002B-EN-P - March 2005
Page 116
4-6
Wiring with Pico GFX-70
Table 4.2 Contacts Contact
Make contact
Break contact
Number
Page
Markers
M
M
01…96
4-12
COM slave marker (REMOTE MARKER)
1M
1M
01..96
6-18
Jump label
:
01…32
4-119
Diagnostics messages
ID
ID
01…16
6-13
COM slave diagnostics messages
1ID
1ID
01…16
6-17
Analog value comparator function block
A X Q1
A X Q1
X=01…32
4-40
Arithmetic value overflow (CARRY) function block
AR X CY A R X CY
X=01…32
4-43
Zero arithmetic value (zero) function block
AR X ZE A R X ZE
X=01…32
4-43
Data block comparator function block, BC X E1 BC X E1 X=01…32 error: number of elements exceeded
4-47
Data block comparator function block, BC X E2 BC X E2 X=01…32 error: range overlap
4-47
Data block comparator function block, BC X E3 BC X E3 X=01…32 error: invalid offset
4-47
Data block comparator function block, BC X EQ BC X EQ X=01…32 comparison result
4-54
Data block comparator function block, BT X E1 BT X E1 X=01…32 error: number of elements exceeded
4-54
Data block transfer function block, error: range overlap
BT X E2 BT X E2 X=01…32
4-54
Data block transfer function block, error: invalid offset
BT X E3 BT X E3 X=01…32
4-54
Boolean sequence function block, value zero
BV X ZE BV X ZE X=01…32
4-64
Other contacts
Function blocks
Publication 1760-UM002B-EN-P - March 2005
Page 117
Wiring with Pico GFX-70
4-7
Table 4.2 Contacts Contact
Make contact
Break contact
Number
Page
Counter function block, upper set point value exceeded (Overflow)
C X OF
C X OF
X=01…32
4-68
Counter function block, lower set point value undershot (Fall below)
C X FB
C X FB
X=01…32
4-68
Counter function block, actual value equal to zero
C X ZE
C X ZE
X=01…32
4-68
Counter function block, actual value has exceeded counter range (CARRY)
C X CY
C X CY
X=01…32
4-68
Frequency counter function block, upper set point value exceeded (Overflow)
CF X OF CF X OF X=01…04
4-75
Frequency counter function block, lower set point value undershot (Fall below)
CF X FB CF X FB X=01…04
4-75
Frequency counter function block, actual value equal to zero
CF X ZE CF X ZE X=01…04
4-75
High-speed counter function block, upper set point value exceeded (Overflow)
CH X OF CH X OF X=01…04
4-79
High-speed counter function block, lower set point value undershot (Fall below)
CH X FB CH X FB X=01…04
4-79
High-speed counter function block, actual value equal to zero
CH X ZE CH X ZE X=01…04
4-79
High-speed counter function block, actual value has exceeded counter range (CARRY)
CH X CY CH X CY X=01…04
4-79
Incremental encoder counter function block, upper set point value exceeded (Overflow)
CI X OF CI X OF X=01…02
4-85
Incremental encoder counter function CI X FB CI X FB X=01…02 block, lower set point value undershot (Fall below)
4-85
CI X ZE CI X ZE X=01…02
4-85
Incremental encoder counter function block, actual value equal to zero
Publication 1760-UM002B-EN-P - March 2005
Page 118
4-8
Wiring with Pico GFX-70
Table 4.2 Contacts Contact
Make contact
Break contact
Number
Page
Incremental encoder counter function block, actual value has exceeded counter range (CARRY)
CI X CY CI X CY X=01…02
4-85
Comparator function block,
CP X LT CP X LT X=01…32
4-90
CP X EQ CP X EQ X=01…32
4-90
CP X GT CP X GT X=01…32
4-90 less than Comparator function block, equal to Comparator function block, greater than
Publication 1760-UM002B-EN-P - March 2005
Text output function block
D X Q1
X=01…32
4-92
Data function block
DB X Q1 DB X Q1 X=01…32
4-93
PID controller, value range of manipulated variable exceeded
DC X LI DC X LI X=01…32
4-95
Receive a variable from a station (Get) GT X Q1 GT X Q1 X=01…32
4-95
Seven-day time switch
HW X Q1 HW X Q1 X=01…32
4-106
Year time switch function block
HY X Q1 HY X Q1 X=01…32
4-111
Master reset, sets all outputs and markers to zero state
MR X Q1 MR X Q1 X=01…32
4-122
Operating hours counter function block, set time reached
OT X Q1 OT X Q1 X=01…04
4-129
Operating hours counter, value overflow (CARRY)
OT X CY OT X CY X=01…04
4-129
Send a variable to the network, enable active Put
PT X Q1 PT X Q1 X=01…32
4-130
Pulse width modulation, error minimum on or off time exceeded
PW X E1 PW X E1 X=01…02
4-132
Send date and time via the Pico-Link network function block
SC X Q1 SC X Q1 X=01
4-135
Timing relay function block
T X Q1
D X Q1
T X Q1
X=01…32
4-139
Page 119
Wiring with Pico GFX-70
4-9
Usable Relays and Function Blocks (coils) Pico GFX-70 provides various relay types as well as function blocks and their coils for wiring in a circuit diagram. Table 4.3 Usable Relays and Function Blocks (Coils) Relay/function block
Pico GFX-70 display
Number
Coil
Parameter
*Q
01…08
✓
-
Pico GFX-70 output relay
Q
01…08
✓
-
Pico GFX-70 output relay expansion, network stations (only network master)
*S
01…08
✓
-
Pico GFX-70 expansion output relay
S
01…08
✓
-
Bit outputs
*SN
01…32
✓
-
Markers
M
01…96
✓
-
COM slave marker (REMOTE MARKER)
1M
01…96
✓
-
Jump label
:
01…32
✓
-
Analog value comparator function block
A
01…32
-
✓
Arithmetic function block
AR
01…32
-
✓
Data block comparator, activate
BC X EN 01 32
✓
✓
Transfer data block, trigger coil
BT X T_ 01 32
✓
✓
Boolean sequences
BV
01…32
-
✓
X=01…32
✓
✓
Outputs Pico GFX-70 output relays, network stations (only network master) * = Station address 2 to 8
* = Station address 2 to 8
* = Station address 1 to 8 General coils
Function blocks
Counter function block, counter input C X C_
Publication 1760-UM002B-EN-P - March 2005
Page 120
4-10
Wiring with Pico GFX-70
Table 4.3 Usable Relays and Function Blocks (Coils)
Publication 1760-UM002B-EN-P - March 2005
Relay/function block
Pico GFX-70 display
Number
Coil
Parameter
Counter function block, direction
C X D_
X=01…32
✓
✓
Counter function block, set counter value (Preset)
C X SE
X=01…32
✓
✓
Counter function block, reset counter C X RE value
X=01…32
✓
✓
Frequency counter function block, activate counter (enable)
CF X EN X=01…04
✓
✓
High-speed counter function block, direction
CH X D_ X=01…04
✓
✓
High-speed counter function block, activate counter (enable)
CH X EN X=01…04
✓
✓
High-speed counter function block, set counter value (Preset)
CH X SE X=01…04
✓
✓
High-speed counter function block, reset counter value
CH X RE X=01…04
✓
✓
Incremental encoder counter function CI X SE X=01…02 block, set counter value (Preset)
✓
✓
Incremental encoder counter function CI X EN X=01…02 block, activate counter (enable)
✓
✓
Incremental encoder counter function CI X RE X=01…02 block, reset counter value
✓
✓
Comparator function block
CP
X=01…32
-
✓
Activate text output function block (enable)
D X EN
X=01…32
✓
✓
Data function block, trigger coil
DB X T_ X=01…32
✓
✓
PID controller, activate
DC X EN X=01…32
✓
✓
PID controller, activate P component
DC X EP X=01…32
✓
✓
PID controller, activate I component
DC X EI X=01…32
✓
✓
PID controller, activate D component
DC X ED X=01…32
✓
✓
PID controller, accept manual manipulated variable
DC X SE X=01…32
✓
✓
Activate signal smoothing filter
FT X EN X=01…32
✓
✓