Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 15 of 46

Pico GFX-70 Controllers User Manual: 4 - Wiring with Pico GFX-70, pages 111 to 120

Pages 111 to 120 of 400, from Pico GFX-70 Controllers User Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley GFX-70 1760-DUB

Page 111

Chapter

4

Wiring with Pico GFX-70

This chapter describes all the functions available with Pico GFX-70.

Pico GFX-70 Operation

Buttons for Drawing Circuit Diagrams and Function Block Usage

ALT

DEL OK ESC

*

DEL: Delete circuit connection, contact, relay or empty line in the circuit diagram. ALT: Toggle between break and make contact. Connect contacts and relays. Add circuit connections. Cursor buttons: (up, down): change values (left, right): change place Cursor buttons set as P buttons: (left): Input P1 (right): Input P3 (up): Input P2 (down): Input P4 OK: Change, add contact/relay Save setting ESC: Undo setting from previous OK Exit current display or menu *:Terminal mode on/off

1

Publication 1760-UM002B-EN-P - March 2005

Page 112

4-2

Wiring with Pico GFX-70

Operating Principles The cursor buttons in the Pico GFX-70 circuit diagram perform three functions. The current mode is indicated by the appearance of the flashing cursor. • Move • Entering • Connect In Move mode, you can the up, down, left, and right arrows buttons to move the cursor around the circuit diagram to select a circuit connection, contact or relay coil. Use OK to switch to Entry mode so that you can enter or change a value at the current cursor position. If you press ESC in Entry mode, Pico GFX-70 will undo the most recent changes. Press ALT to switch to Connect mode for wiring contacts and relays. Press ALT again to return to Move. Press ESC to leave the circuit diagram and parameter display.

IMPORTANT

Pico GFX-70 performs many of these cursor movements automatically. For example, Pico GFX-70 switches the cursor to Move mode if no further entries or connections are possible at the selected cursor position.

Opening the Parameter Display for Function Blocks with Contacts or Coils If you specify the contact or coil of a function relay type in Entry mode, the Pico GFX-70 automatically switches from the contact number to the function block parameter display when you press OK. Press the right arrow key to switch to the next contact or coil field without entering any parameters.

Publication 1760-UM002B-EN-P - March 2005

Page 113

Wiring with Pico GFX-70

4-3

Program A program is a sequence of commands which the Pico GFX-70 executes cyclically in RUN mode. A Pico GFX-70 program consists of the necessary settings for the device, the Pico-Link, Serial Interface, password, system settings, a circuit diagram and/or function blocks and/or the visualization screens. The circuit diagram is that part of the program where the contacts are connected together. In RUN mode a coil is switched on and off in accordance with the current flow and the coil function specified.

Function Blocks Function blocks are program elements with special functions. Example: timing relays, time switches, arithmetic function blocks. Function blocks are elements provided with or without contacts and coils as required. In RUN mode the function blocks are processed according to the circuit diagram and the results are updated accordingly. Examples: Timing relay = function block with contacts and coils Time switch = function block with contacts

Visualization Screens Visualization screens are the sections of programs containing the display and operator functions.

Relays Relays are switching devices which are electronically simulated in Pico GFX-70. They actuate their contacts according to their designated function. A relay consists of a coil and at least one contact.

Contacts You modify the current flow with the contacts in the Pico GFX-70 circuit diagram. Contacts such as make contacts carry a 1 signal when closed and 0 when open. Every contact in the Pico GFX-70 circuit diagram can be defined as either a make contact or a break contact.

Publication 1760-UM002B-EN-P - March 2005

Page 114

4-4

Wiring with Pico GFX-70

Coils Coils are the actuating mechanisms of relays. In RUN mode, the results of the wiring are sent to the coils, which switch on or off accordingly. Coils can have seven different coil functions. Table 4.1 Usable Contacts Contact

Pico GFX-70 display

Make contact, open in release position

I, Q, M, A, …. Other contacts a Table

Break contact, closed in release position i, q, m, a, … Other contacts a Table

Pico GFX-70 works with different contacts, which can be used in any order in the contact fields of the circuit diagram. Table 4.2 Contacts Contact

Make contact

Break contact

Number

Page

*I

*I

01…12

6-4

COM slave inputs

1I

1I

01..12

Pico GFX-70 input terminal

I

I

01…12

-

Cursor button

P

P

01…04

-

Network station expansion input terminal

*R

*R

01…12

6-4

1R

1R

01...12

Input terminal for expansion module

R

R

01…12

-

Bit inputs via the network

*RN

*RN

01…32

6-4

Inputs Inputs of a network station * = Station address 1 to 8

* = Station address 1 to 8 Input terminal for expansion module COM slave

* = Station address 1 to 8

Publication 1760-UM002B-EN-P - March 2005

Page 115

Wiring with Pico GFX-70

4-5

Table 4.2 Contacts Contact

Make contact

Break contact

Number

Page

*I

*I

14

8-8

*I

*I

15…16

8-7

COM slave expansion unit status

1I

1I

14

COM slave short-circuit/overload

1I

1I

15…16

Expansion status

I

I

14

8-8

Short-circuit/overload

I

I

15…16

8-7

Short-circuit/overload in expansion network station

*R

*R

15…16

8-7

Short-circuit/overload in COM slave expansion

1R

1R

15…16

Short circuit/overload with expansion

R

R

15…16

Deactivate backlight of the GFX display

LE

LE

01

Red LED of GFX display

LE

LE

02

Green LED of GFX display

LE

LE

03

Pico GFX-70 output Pico GFX-70 network station

*Q

*Q

01…08

COM slave output

1Q

1Q

01…08

Pico GFX-70 output

Q

Q

01…08

-

Pico GFX-70 output expansion with network station

*S

*S

01…08

6-4

Output of COM slave expansion

1S

1S

01…08

Pico GFX-70 output expansion

S

S

01…08

-

Bit outputs via the network

*SN

*SN

01…32

6-4

Diagnostics inputs Expansion network station status * = Station address 1 to 8 Network station short-circuit/overload * = Station address 1 to 8

* = Station address 1 to 8

8-7

Outputs

6-4

* = Station address 1 to 8

* = Station address 1 to 8

* = Station address 1 to 8

Publication 1760-UM002B-EN-P - March 2005

Page 116

4-6

Wiring with Pico GFX-70

Table 4.2 Contacts Contact

Make contact

Break contact

Number

Page

Markers

M

M

01…96

4-12

COM slave marker (REMOTE MARKER)

1M

1M

01..96

6-18

Jump label

:

01…32

4-119

Diagnostics messages

ID

ID

01…16

6-13

COM slave diagnostics messages

1ID

1ID

01…16

6-17

Analog value comparator function block

A X Q1

A X Q1

X=01…32

4-40

Arithmetic value overflow (CARRY) function block

AR X CY A R X CY

X=01…32

4-43

Zero arithmetic value (zero) function block

AR X ZE A R X ZE

X=01…32

4-43

Data block comparator function block, BC X E1 BC X E1 X=01…32 error: number of elements exceeded

4-47

Data block comparator function block, BC X E2 BC X E2 X=01…32 error: range overlap

4-47

Data block comparator function block, BC X E3 BC X E3 X=01…32 error: invalid offset

4-47

Data block comparator function block, BC X EQ BC X EQ X=01…32 comparison result

4-54

Data block comparator function block, BT X E1 BT X E1 X=01…32 error: number of elements exceeded

4-54

Data block transfer function block, error: range overlap

BT X E2 BT X E2 X=01…32

4-54

Data block transfer function block, error: invalid offset

BT X E3 BT X E3 X=01…32

4-54

Boolean sequence function block, value zero

BV X ZE BV X ZE X=01…32

4-64

Other contacts

Function blocks

Publication 1760-UM002B-EN-P - March 2005

Page 117

Wiring with Pico GFX-70

4-7

Table 4.2 Contacts Contact

Make contact

Break contact

Number

Page

Counter function block, upper set point value exceeded (Overflow)

C X OF

C X OF

X=01…32

4-68

Counter function block, lower set point value undershot (Fall below)

C X FB

C X FB

X=01…32

4-68

Counter function block, actual value equal to zero

C X ZE

C X ZE

X=01…32

4-68

Counter function block, actual value has exceeded counter range (CARRY)

C X CY

C X CY

X=01…32

4-68

Frequency counter function block, upper set point value exceeded (Overflow)

CF X OF CF X OF X=01…04

4-75

Frequency counter function block, lower set point value undershot (Fall below)

CF X FB CF X FB X=01…04

4-75

Frequency counter function block, actual value equal to zero

CF X ZE CF X ZE X=01…04

4-75

High-speed counter function block, upper set point value exceeded (Overflow)

CH X OF CH X OF X=01…04

4-79

High-speed counter function block, lower set point value undershot (Fall below)

CH X FB CH X FB X=01…04

4-79

High-speed counter function block, actual value equal to zero

CH X ZE CH X ZE X=01…04

4-79

High-speed counter function block, actual value has exceeded counter range (CARRY)

CH X CY CH X CY X=01…04

4-79

Incremental encoder counter function block, upper set point value exceeded (Overflow)

CI X OF CI X OF X=01…02

4-85

Incremental encoder counter function CI X FB CI X FB X=01…02 block, lower set point value undershot (Fall below)

4-85

CI X ZE CI X ZE X=01…02

4-85

Incremental encoder counter function block, actual value equal to zero

Publication 1760-UM002B-EN-P - March 2005

Page 118

4-8

Wiring with Pico GFX-70

Table 4.2 Contacts Contact

Make contact

Break contact

Number

Page

Incremental encoder counter function block, actual value has exceeded counter range (CARRY)

CI X CY CI X CY X=01…02

4-85

Comparator function block,

CP X LT CP X LT X=01…32

4-90

CP X EQ CP X EQ X=01…32

4-90

CP X GT CP X GT X=01…32

4-90 less than Comparator function block, equal to Comparator function block, greater than

Publication 1760-UM002B-EN-P - March 2005

Text output function block

D X Q1

X=01…32

4-92

Data function block

DB X Q1 DB X Q1 X=01…32

4-93

PID controller, value range of manipulated variable exceeded

DC X LI DC X LI X=01…32

4-95

Receive a variable from a station (Get) GT X Q1 GT X Q1 X=01…32

4-95

Seven-day time switch

HW X Q1 HW X Q1 X=01…32

4-106

Year time switch function block

HY X Q1 HY X Q1 X=01…32

4-111

Master reset, sets all outputs and markers to zero state

MR X Q1 MR X Q1 X=01…32

4-122

Operating hours counter function block, set time reached

OT X Q1 OT X Q1 X=01…04

4-129

Operating hours counter, value overflow (CARRY)

OT X CY OT X CY X=01…04

4-129

Send a variable to the network, enable active Put

PT X Q1 PT X Q1 X=01…32

4-130

Pulse width modulation, error minimum on or off time exceeded

PW X E1 PW X E1 X=01…02

4-132

Send date and time via the Pico-Link network function block

SC X Q1 SC X Q1 X=01

4-135

Timing relay function block

T X Q1

D X Q1

T X Q1

X=01…32

4-139

Page 119

Wiring with Pico GFX-70

4-9

Usable Relays and Function Blocks (coils) Pico GFX-70 provides various relay types as well as function blocks and their coils for wiring in a circuit diagram. Table 4.3 Usable Relays and Function Blocks (Coils) Relay/function block

Pico GFX-70 display

Number

Coil

Parameter

*Q

01…08

✓

-

Pico GFX-70 output relay

Q

01…08

✓

-

Pico GFX-70 output relay expansion, network stations (only network master)

*S

01…08

✓

-

Pico GFX-70 expansion output relay

S

01…08

✓

-

Bit outputs

*SN

01…32

✓

-

Markers

M

01…96

✓

-

COM slave marker (REMOTE MARKER)

1M

01…96

✓

-

Jump label

:

01…32

✓

-

Analog value comparator function block

A

01…32

-

✓

Arithmetic function block

AR

01…32

-

✓

Data block comparator, activate

BC X EN 01 32

✓

✓

Transfer data block, trigger coil

BT X T_ 01 32

✓

✓

Boolean sequences

BV

01…32

-

✓

X=01…32

✓

✓

Outputs Pico GFX-70 output relays, network stations (only network master) * = Station address 2 to 8

* = Station address 2 to 8

* = Station address 1 to 8 General coils

Function blocks

Counter function block, counter input C X C_

Publication 1760-UM002B-EN-P - March 2005

Page 120

4-10

Wiring with Pico GFX-70

Table 4.3 Usable Relays and Function Blocks (Coils)

Publication 1760-UM002B-EN-P - March 2005

Relay/function block

Pico GFX-70 display

Number

Coil

Parameter

Counter function block, direction

C X D_

X=01…32

✓

✓

Counter function block, set counter value (Preset)

C X SE

X=01…32

✓

✓

Counter function block, reset counter C X RE value

X=01…32

✓

✓

Frequency counter function block, activate counter (enable)

CF X EN X=01…04

✓

✓

High-speed counter function block, direction

CH X D_ X=01…04

✓

✓

High-speed counter function block, activate counter (enable)

CH X EN X=01…04

✓

✓

High-speed counter function block, set counter value (Preset)

CH X SE X=01…04

✓

✓

High-speed counter function block, reset counter value

CH X RE X=01…04

✓

✓

Incremental encoder counter function CI X SE X=01…02 block, set counter value (Preset)

✓

✓

Incremental encoder counter function CI X EN X=01…02 block, activate counter (enable)

✓

✓

Incremental encoder counter function CI X RE X=01…02 block, reset counter value

✓

✓

Comparator function block

CP

X=01…32

-

✓

Activate text output function block (enable)

D X EN

X=01…32

✓

✓

Data function block, trigger coil

DB X T_ X=01…32

✓

✓

PID controller, activate

DC X EN X=01…32

✓

✓

PID controller, activate P component

DC X EP X=01…32

✓

✓

PID controller, activate I component

DC X EI X=01…32

✓

✓

PID controller, activate D component

DC X ED X=01…32

✓

✓

PID controller, accept manual manipulated variable

DC X SE X=01…32

✓

✓

Activate signal smoothing filter

FT X EN X=01…32

✓

✓