The text of a manual · part 14 of 46
Pico GFX-70 Controllers User Manual: 3 - Commissioning, pages 103 to 110
Pages 103 to 110 of 400, from Pico GFX-70 Controllers User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley GFX-70 1760-DUB
Page 103
Commissioning
Terminal Mode
3-25
The GFX device also supports the TERMINAL MODE operating mode. This allows you to remotely control other devices. This is especially useful if the other device is located in an inaccessible place. Terminal mode can also be used to show the menus and displays of devices that do not have their own display or keypad. Terminal mode can be used both with the serial interface and in the Pico-Link. The serial interface enables you to access a remote device. If you use the Pico-Link network, all other network stations can be addressed.
IMPORTANT
IMPORTANT
Terminal mode is a separate operating mode like RUN mode. It only functions when a program is not running. For this mode to be active, the GFX must be in STOP mode.
All connected devices must also support Terminal mode.
The following topologies are permissible.
Publication 1760-UM002B-EN-P - March 2005
Page 104
3-26
Commissioning
Terminal Mode Using the Point-to-Point Serial Interface Figure 3.12 Terminal mode using the point-to-point serial interface
TERMIN AL
Terminal mode using the Pico-Link topology
Figure 3.13 Terminal mode using the Pico-Link topology
R 1 - 12
GFX-70 S1-8
GFX-70
GFX-70
GFX-70
GFX-70
In the above topology, the physical location is not identical to the station number. The GFX device was connected in the middle of the network line. Terminal mode functions irrespective of the device location and station number.
Publication 1760-UM002B-EN-P - March 2005
Page 105
Commissioning
3-27
Figure 3.14 Terminal mode in Pico-Link with two GFX devices
GFX-70
GFX-70
GFX-70
GFX-70
The above topology allows two GFX devices to be run in Pico-Link Terminal mode. Each GFX device can run with the other devices in Terminal mode.
Publication 1760-UM002B-EN-P - March 2005
Page 106
3-28
Commissioning
Figure 3.15 Terminal mode in Pico-Link as well as via two serial interfaces
GFX-70
GFX-70
GFX-70
GFX-70
The above topology is a combination of Pico-Link operation and serial interface operation. Bear in mind the access rights of the individual Pico-Link devices and in the corresponding point-to-point serial interface.
Publication 1760-UM002B-EN-P - March 2005
Page 107
Commissioning
ATTENTION
3-29
Data collision! To ensure proper operation, the following conditions must be observed. The following applies: If there is more than one GFX device in Terminal mode, each GFX device must access a different Pico-Link station. A device running in Terminal mode must not access any two devices communicating with each other in Terminal mode. If a PC with PicoSoft Pro or a GFX device with a serial interface is in active communication with a Pico-Link station, this station must not be accessed at the same time in Terminal mode via the Pico-Link.
Proceed as follows: Your Pico-Link or point-to-point serial interface must be running correctly. 1. Press the OK button from the Status Display. PROGRAM... STOP ✓ RUN PARAMETERS SET CLOCK... STOP ✓ RUN PARAMETERS SET CLOCK... TERMINAL MODE...
STATION ID: 0 START MODE
The first menu will appear. 2. Press the Up Arrow button. This will display the TERMINAL MODE menu item. 3. Press the OK button.
The START MODE menu item will flash. 4. Press the Up Arrow button.
Publication 1760-UM002B-EN-P - March 2005
Page 108
3-30
Commissioning
STATION ID: 0 START MODE
5. Select the second station. This station will control the display and respond to the keypad.
IMPORTANT
Station ID: 0 = Station at the point-to-point serial interface 1 = Pico-Link Station 1 2 = Pico-Link Station 2 3 = Pico-Link Station 3 4 = Pico-Link Station 4 5 = Pico-Link Station 5 6 = Pico-Link Station 6 7 = Pico-Link Station 7 8 = Pico-Link Station 8
6. Press the OK button. STATION ID: 0 START MODE
Select your station. 1. Press the Up or Down Arrow button. 2. Press the OK button. Select the START MODE menu option.
STATION ID: 0 START MODE
1. Press the Down Arrow button. 2. Press the OK button.
STATION ID: 2 START MODE
In this case Pico-Link station 2 is connected.
Connection establishment
The GFX tries to establish connection to the selected device. The text flashes.
in progress...
Once the connection is established, the menu appears or the Status display in which the selected device is active.
Publication 1760-UM002B-EN-P - March 2005
Page 109
Commissioning
IMPORTANT
3-31
If the text “Connection establishment in progress...” is displayed for longer than 10 s, the connection to the selected device is faulty. Press ESC to cancel the selection. Rectify the fault. Try to re-establish the connection.
The following applies if the device to be operated is in RUN mode and is displaying a screen: This screen is not displayed in Terminal mode. GFX message: “The remote device is in Graphic mode.” 1. Press the ALT and ESC button simultaneously. This will call up the Status display.
I 1..4..789... * I NT2 PTU 06.05.2003 Q 1..45678 RUN
Pico-Link station 2 controls the display of the GFX device.
TIP
ATTENTION
The activation of Terminal mode is indicated by the flashing star at the top right of the Status display.
In Terminal mode, you can operate a device that may be positioned far from your actual location. All access rights that you would also require "locally" are granted to you. It is not always possible to obtain a view of the situation “locally”. Use of this operating mode and the execution of any changes to device settings should only be carried out with the utmost caution. A device with a display and keypad can also be operated locally. In this case, operation at the device concerned is always faster than operation via Terminal mode. Bear in mind that this may lead to conflicts that may trigger faults or unforeseen events.
Publication 1760-UM002B-EN-P - March 2005
Page 110
3-32
Commissioning
IMPORTANT
In Terminal mode, the GFX device makes its display and keypad available to the connected device. Only data for the display and the status of the buttons is sent via the connection. This ensures that the local data of the connected device is not destroyed in the event of a communication fault.
2. Close Terminal mode. 3. Press the * button to close the Terminal mode. STATION ID: 2 START MODE
IMPORTANT
The * button cannot be assigned to other tasks if you wish to use Terminal mode in your application. Use the * button to change from the visualization to the Status display. Otherwise the Terminal mode menu cannot be reached.
4. Press the * button. This returns you back to your local device.
STATION ID: 2 START MODE
5. Press the ESC button twice.
The Status display is active. I ..345..89... I PSA 06:47 ST Q 2 4 STOP
The flashing star at the top right of the display is no longer present.
TIP
The display must be initialized again if the processor was fitted to it under live conditions. Press the DEL and ESC buttons simultaneously to reinitialize the display.
Publication 1760-UM002B-EN-P - March 2005