The text of a manual · part 13 of 46

Pico GFX-70 Controllers User Manual: 3 - Commissioning, pages 95 to 102

Pages 95 to 102 of 400, from Pico GFX-70 Controllers User Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley GFX-70 1760-DUB

Page 95

Commissioning

3-17

Configuring a Pico-Link Network The Pico-Link network can only be configured from station 1. Requirement: All stations are correctly connected to the network and the termination resistors have been connected. All stations have a power supply and are in STOP mode. The POW LED is permanently lit. The NET LED is permanently lit.

IMPORTANT

NET PARAMETERS.. STATIONS... CONFIGURE

CONFIGURE?

CONFIGURATION IN PROGRESS.

If the connected stations are configured, all stations automatically switch to the STOP mode.

1. Proceed to the CONFIGURE menu item and press the OK button.

You will be asked to acknowledge whether you want to configure the system. 2. Press the OK button. The message on the left appears: All NET LEDs on the stations which are assigned station numbers higher than 1 (2 to 8) switch to the OFF state of the Pico-Link. As soon as the configuration has been successfully completed, the NET LEDs on all stations flash. The Pico-Link network is ready for operation.

IMPORTANT

ERR: ID-CONFLICT

An error message will appear if a station is assigned a station address which does not correspond to the physical location in the station list.

If you want to overwrite the station address press the OK button. The configuration can be aborted by pressing the ESC button.

OVERWRITE CONFIGURATION ?

Changing the Pico-Link Configuration The configuration of the Pico-Link network can be modified at any time at station 1, physical location 1.

Publication 1760-UM002B-EN-P - March 2005

Page 96

3-18

Commissioning

The NET parameters are modified as described for inputting parameters for the first time. Station addresses in the STATIONS menu are changed as follows: 1. Go to the physical location which is to be modified. 2. Press the OK button.

IMPORTANT

Existing station numbers can only be modified to free, non-assigned station numbers. If all eight numbers are assigned, all station numbers which are to be modified must be set to zero. Thereafter, all station numbers can be reassigned. (Pico GFX-70 sets all station numbers to zero which are assigned a physical location behind the leading zero.)

3. Select the required station number and confirm your input with the OK button. 4. Configure all Pico-Link stations again using the CONFIGURATION menu. Further information concerning the Pico-Link network topic can be found in Pico-Link and Point-to-Point Serial Connections on page 6-1.

Displaying the Status Display of Other Stations On every device with a display, you can display the states of the inputs and outputs of each network station.

Publication 1760-UM002B-EN-P - March 2005

Page 97

Commissioning

3-19

1. Change to the Status display and press the ESC button. 1I12.......... I NT1

P-

MO 06:42 1Q1.......

RUN

2. Change the number of the required station using the up/down arrow keys.

3I12.....7.... I NT3

P-

3. Press the OK button.

MO 06:42 3Q1.3..6..

RUN

4. If you want to view the state of the inputs and outputs of a local expansion, press the OK button.

3R12.....7.... I NT3 DC

P-

MO 06:45 3S1.3..6..

The cursor changes to the display of the network station NT.. and flashes. The station number is displayed in front of the inputs and outputs.

RUN

If you press the ESC button again or the OK button, the display of the input and output states of the station is terminated. IMPORTANT

The station showing the status on its display cannot read its own data from the network. Example: NT3 flashes on station 3. The inputs and outputs 3I.., 3R.., 3Q.. and 3S.. cannot be displayed. If the NT3 display is not flashing, the inputs and outputs are shown.

Publication 1760-UM002B-EN-P - March 2005

Page 98

3-20

Commissioning

Configuring the Connection for the Terminal Mode

If you wish to set up point-to-point communication with another station, this can be done using either the serial interface or the Pico-Link. The GFX must be provided with a display and keypad. The connection must be configured for this purpose (see also: Introduction to the Serial Interface on page 6-16).

IMPORTANT

Ensure that the other station supports the Serial Interface mode.

Proceed as follows: 1. Connect both stations together. Only use original connection cables. The connector marked POW-Side must be plugged into a GFX. The GFX feeds the interface electronics of the connection line at both ends. 2. Connect both stations to the power supply. Figure 3.11 Serial connection example with two stations

The GFX is the active station and the second station is the remote station. 3. Switch on the power supply at both stations.

Publication 1760-UM002B-EN-P - March 2005

Page 99

Commissioning

3-21

4. Ensure that the power supply for both stations is switched on. The POW LED must light up or flash. It is only possible to configure the stations which have an active power supply. 5. Go to the GFX device that is the active station running the serial interface.

IMPORTANT

The following tasks are only possible in STOP mode.

Setting up the Serial Interface

ATTENTION

The GFX device can either run as a Pico-Link station or as a station in a Serial Interface connection. Do not switch a GFX device running as a Pico-Link station to Serial Interface. If this is done with the Pico-Link in the RUN mode, the entire Pico-Link network will be deactivated. There will be no further data transfer. Solution: 1. Deactivate the Serial Interface. 2. Re-enter the Pico-Link address. 3. Switch the power supply off and then on again. 4. Reconfigure the Pico-Link on station 1.

1. Simultaneously press the DEL and ALT buttons with the Status display active. SECURITY... SYSTEM... MENU LANGUAGE CONFIGURATOR...

The System menu appears 2. Select the CONFIGURATOR menu option. 3. Press the OK button.

NET.. COM... LINK....

4. Select the COM... menu option. 5. Press the down arrow button. 6. Press the OK button.

Publication 1760-UM002B-EN-P - March 2005

Page 100

3-22

Commissioning

BAUDRATE: 9600B Serial Interface REMOTE MARKER...

The menu BAUDRATE: 9600B will appear. The two baud rates are for 9600 or 19200 baud. Select the baud rate that your connection will support.

Baud Rate Selection

IMPORTANT

Select 19200 baud as the baud rate. Badly laid cables may give rise to electromagnetic interference. Select 9600 baud as the baud rate. If this is not satisfactory, the connection cable must be laid in a different location.

1. Press the OK button.

: BAUDRATE:19200B Serial Interface REMOTE MARKER...

2. Select 19200 baud as the baud rate. 3. Press the up/down arrow button. 4. Confirm with the OK button. 5. Switch on the COM connection.

IMPORTANT

The Serial Interface must only be switched at the active station. Two devices with Serial Interface ✓ switched on cannot communicate with each other.

6. Press the press the down arrow button. BAUDRATE:19200B Serial Interface ✓ REMOTE MARKER...

7. Press the OK button. The tick on the Serial Interface menu item indicates that Serial Interface has been selected. No tick means that Serial Interface has not been selected.

IMPORTANT

The following applies to the active station: If you wish to run data transfers between the two devices in both directions, you must select the marker range on the active station.

Publication 1760-UM002B-EN-P - March 2005

Page 101

Commissioning

3-23

8. Select the REMOTE MARKER menu item. BAUDRATE:19200B Serial Interface ✓ REMOTE MARKER...

The following selection will only be displayed if the Serial Interface menu item has been ticked. 9. Press the OK button.

READ: 1MD00 Ç 1MD00 WRITE: 1MD00 Ç 1MD00

The data is physically located in the second station, i.e. the remote station.

IMPORTANT

The active station reads and writes data from and to the markers of the remote station. At the same time, the remote station has read and write access to the same marker range. Ensure that both stations do not have write access to the same markers simultaneously. The last write operation will be the one that is retained. Example: READ 1MD2 -> 1MD2 WRITE 1MD3 -> 1MD3 The GFX device accesses the markers with station address 1xx... These markers correspond to the local markers MD2 and MD3 in the remote station. These marker double words contain: MD2, MW3, MW4, MB5; MB6, MB7, MB8, M33 to M64 MD3, MW5, MW6, MB9, MB19, MB11, MB12; M65 to M96

The following marker ranges can be selected: 1MD1 to 1MD20 This corresponds to the following range in the remote station: MD1 to MD20

Publication 1760-UM002B-EN-P - March 2005

Page 102

3-24

Commissioning

10. Press the OK button. READ: 1MD00 Ç 1MD00 WRITE: 1MD00 Ç 1MD00

READ: 1MD11 Ç 1MD14 WRITE: 1MD00 Ç 1MD00

11. Use the up arrow button to select the start of the READ marker range.

12. Use the right arrow button to enter the upper limit of the READ range. 13. Use the up arrow button to select the value. 14. Confirm the entry with the OK button.

READ: 1MD11 Ç 1MD14 WRITE: 1MD00 Ç 1MD00

READ: 1MD11 Ç 1MD14 WRITE: 1MD00 Ç 1MD00

READ: 1MD11 Ç 1MD14 WRITE: 1MD15 Ç 1MD17

BAUDRATE:19200B Serial Interface ✓ REMOTE MARKER...

I 12.4.67..... I COM PFR 02:02 ST Q........ STOP

Publication 1760-UM002B-EN-P - March 2005

15. Use the down arrow button to enter the WRITE range. 16. Enter the WRITE range.

17. Press ESC to leave the entry menu.

The Serial Interface has now been set. No COM settings are required at the remote station. 18. Press ESC to return to the Status display.

The entry in the second COM line indicates that the COM connection is active.