The text of a manual · part 12 of 46
Pico GFX-70 Controllers User Manual: 3 - Commissioning, pages 87 to 94
Pages 87 to 94 of 400, from Pico GFX-70 Controllers User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley GFX-70 1760-DUB
Page 87
Commissioning
3-9
Figure 3.4 Your first circuit diagram I 01----I 02-------------------[ Q 01
L: 1 C:1 B:7944
= visible area
6. Press ESC to leave the circuit diagram display. The SAVE menu appears. Figure 3.5 SAVE menu I 01----I 02-------------------[ Q 01
SAVE
Ó
= visible area
7. Press the OK button. The circuit diagram is stored. Once you have connected push button actuators S1 and S2, you can test your circuit diagram.
Publication 1760-UM002B-EN-P - March 2005
Page 88
3-10
Commissioning
Testing the Circuit Diagram 1. Switch to the main menu and select the STOP RUN menu option. PROGRAM... STOP ✓ RUN
With a tick at RUN or STOP you switch to the RUN or STOP operating modes.
PARAMETERS SET CLOCK...
Pico GFX-70 runs in the mode indicated by the tick. 2. Press the OK button. Pico GFX-70 will change to RUN mode. The mode assigned the tick is always active.
TIP
The Status display shows the current mode and the switching states of the inputs and outputs. 3. Change to the Status display and press push button actuator S1. I 12.......... I
P-
MO 14:42 Q 1.......
RUN
The contacts (boxes) for inputs I1 and I2 are activated and relay Q1 picks up. This is indicated on the numbers which are displayed.
Power Flow Display The Pico GFX-70 allows you to check circuit connections in RUN mode. This means that you can check your circuit diagram via the built-in power flow display while it is being processed by the Pico GFX-70. 1. Change to the Circuit diagram display and press push button actuator S1. The relay picks up. Pico GFX-70 shows the power flow. Figure 3.6 Power flow display: Inputs I1 and I2 are closed, relay Q1 has picked up I 01====I 02===================[ Q 01
L: 1 C:1 RUN
= visible area
2. Press push button actuator S2, that has been connected as a break contact. The circuit connection is interrupted and relay Q1 drops out.
Publication 1760-UM002B-EN-P - March 2005
Page 89
Commissioning
3-11
Figure 3.7 Power flow display: Input I1 is closed, input I2 is open, relay Q1 has picked up I 01====I 02-------------------[ Q 01
L: 1 C:1 RUN
= visible area
3. Press ESC to return to the Status display. TIP
With Pico GFX-70 you can test parts of a circuit diagram before it is entirely completed. Pico GFX-70 simply ignores any incomplete wiring that is not yet working and only runs the finished wiring.
Power Flow Display with Zoom Function The Pico GFX-70 enables you to check the following at a glance: • all four contacts plus one coil in series • and 3 circuit connections Change to the Circuit diagram display and press the ALT button. Press push button actuator S1. Figure 3.8 Power flow display in Zoom function: Input I1 and I2 are closed, relay Q1 picked up ❚==❚========[❚
L: 001
I 01
❚ Contact closed, coil is triggered Contact opened, coil dropped out 1. Press push button actuator S2, that has been connected as a break contact. The circuit connection is interrupted and relay Q1 drops out.
❚==#--------[#
L: 001
I 01
Publication 1760-UM002B-EN-P - March 2005
Page 90
3-12
Commissioning
Use the arrow keys to move between the contacts or coil. 2. Press the up cursor button.
❚==#--------[#
L: 002
I 02
The cursor moves to the second contact. 3. Press the ALT button. The display changes to display status with contact and/or coil designation.
Figure 3.9 Power flow display: Input I1 is closed, input I2 is open, relay Q1 has dropped out I 01====I 02-------------------[ Q 01
L: 1 C:2 RUN
= visible area
Publication 1760-UM002B-EN-P - March 2005
Page 91
Commissioning
3-13
Deleting the Circuit Diagram 1. Switch the Pico GFX-70 to STOP mode.
IMPORTANT
Pico GFX-70 must be in STOP mode in order to extend, delete or modify the circuit diagram.
2. Use PROGRAM… to switch from the main menu to the next menu level. 3. Select DELETE PROGRAM PROGRAM... DELETE PROGRAM
The Pico GFX-70 will display the prompt DELETE? 4. Press OK to delete the program or ESC to cancel. 5. Press ESC to return to the Status display.
Fast Circuit Diagram Entry You can create a circuit diagram in several ways: The first option is to enter the elements in the circuit and then to wire all the elements together. The other option is to use the enhanced operator guidance of Pico GFX-70 and create the circuit diagram in one go, from the first contact through to the last coil. If you use the first option, you will have to select some of the elements in order to create and connect up your circuit diagram. The second, faster option is what you learned in the example. In this case you create the entire circuit connection from left to right.
Publication 1760-UM002B-EN-P - March 2005
Page 92
3-14
Commissioning
Configuring a Pico-Link Network
If you want to work with the Pico-Link network and communicate with several stations, the network must be configured first. Proceed as follows: 1. Connect all network stations. Pico-Link socket 2e to Pico-Link socket 1L. 2. The first station 1 (socket 1L) and the last station (socket 2e) must be provided with a network termination resistor a. 3. Connect all stations to the power supply. Figure 3.10 Example topology with two Pico-Link stations 1
Resistor
Location 1 Station 1 1
Terminating R1 – 12
Location 2 Station 2
Resistor
GFX-70 S1 – S8
1. Switch on the power supply on all stations. 2. Ensure that all stations have a power supply. The POW LED must light up or flash. It is only possible to configure the stations which are supplied with voltage.
Publication 1760-UM002B-EN-P - March 2005
Page 93
Commissioning
3-15
3. Proceed to the first physical station (Location 1). This station has the termination resistor inserted on socket 1.
IMPORTANT
The following tasks are only possible in STOP mode.
Entering the Network Station Number 1. Simultaneously press the DEL and ALT buttons while the GFX displays the Status display. SECURITY... SYSTEM... MENU LANGUAGE CONFIGURATOR...
NET.. COM... LINK....
NET PARAMETERS... STATIONS... CONFIGURE
NET-ID : 00 ▲ BAUDRATE: 125KB BUSDELAY: 00 SEND IO ✓ ▼ REMOTE RUN REMOTE IO NET-ID : 01 ▲ BAUDRATE: 125KB BUSDELAY: 00 SEND IO ✓ ▼ REMOTE RUN REMOTE IO
The System menu appears 2. Select the CONFIGURATOR menu option. 3. Press the OK button. The NET menu appears. 4. Press the OK button. The NET PARAMETERS… menu appears. 5. Press the OK button. 6. Press the OK button and select the station number using the up/down arrows keys. In this case the station number (Pico-Link ID) “01”. 7. Press the OK button. 8. Exit the NET PARAMETERS menu with ESC.
IMPORTANT
The station designated station number 1 is the active station. For this reason the REMOTE RUN and REMOTE IO functions are not available.
Publication 1760-UM002B-EN-P - March 2005
Page 94
3-16
Commissioning
Entering Network Stations Only the network station at physical location 1 with station number 1 has a station list.
IMPORTANT
The left-hand column is the physical location. You can only assign a physical location to unused station numbers. Physical location 1 is permanently assigned to station number 1.
1. Use the up/down arrow keys to select the STATION menu and press the OK button.
1 2 3 4
1 0 0 0
▲
1 2 3 4
1 2 0 0
▲
▼
▼
2. Proceed to the station with physical address 2. 3. Select the required physical location with the up/down arrow keys. Press the OK button. 4. Use up/down arrow keys to select station number 2. 5. Press the OK button. At physical location 2, the station has been assigned station address 2. 6. Press ESC to return to the STATIONS menu item.
Publication 1760-UM002B-EN-P - March 2005