Page 79

Chapter

3

Commissioning

Before startup check whether the power supply, inputs, outputs, the serial interface and the Pico-Link cable are properly connected:

Switching On

• 24V dc version: – Terminal +24V: +24V voltage – Terminal 0V: 0V voltage – Terminals I1 to I12, R1 to R12: Actuation via +24V • 230V ac version – Terminal L: Phase conductor L – Terminal N: Neutral conductor N – Terminals R1 to R12: Actuation via phase conductor L If you have already integrated devices into a system, secure any parts of the system connected to the working area to prevent access and ensure that no-one can be injured if, for example, motors start up unexpectedly.

Setting the Menu Language When you switch on the Pico GFX-70 for the first time, you will be asked to select the menu language.

ENGLISH

✓

1. Use the up and down arrow buttons to select the language required.

DEUTSCH FRANCAIS ESPANOL

1

– English – German – French – Spanish – Italian – Portuguese – Dutch – Swedish – Polish – Turkish

Publication 1760-UM002B-EN-P - March 2005

Page 80

3-2

Commissioning

2. Press OK to confirm your choice and press ESC to exit the menu. GFX will then switch to the Status display.

IMPORTANT

You can change the language setting at a later date, if you wish. See Changing the Menu Language on page 7-8. If you do not set the language, the Pico GFX-70 will display this menu every time you switch on and wait for you to select a language.

Operating Modes

Pico GFX-70 operating modes - RUN, STOP and TERMINAL MODE. In RUN mode the GFX continuously processes a stored program until you select STOP, disconnect the power supply or switch to TERMINAL MODE. The program, parameters and the GFX settings are retained in the event of a power failure. All you will have to do is reset the real-time clock after the back-up time has elapsed. Circuit diagram entry is only possible in STOP mode.

IMPORTANT

In RUN mode, the processor will immediately run the program saved in the unit when the power supply is switched on. This will not happen if STOP or TERMINAL mode was set as startup mode. In RUN mode, outputs are activated according to the switch logic involved.

The following applies to devices without display/keypad: • Memory module containing a valid circuit diagram must be fitted. • Device must be switched on. If the device has no program, the program stored on the memory module is loaded automatically and the device immediately starts running the program in RUN mode.

Publication 1760-UM002B-EN-P - March 2005

Page 81

Commissioning

Creating your First Circuit Diagram

3-3

The following single line diagram takes you step by step through wiring up your first circuit diagram. In this way you will learn all the rules, quickly enabling you to use Pico GFX-70 for your own projects. As with conventional wiring, you use contacts and relays in the Pico GFX-70 diagram. With Pico GFX-70, however, you no longer have to connect up components individually. At the push of a few buttons, the Pico GFX-70 circuit diagram produces all the wiring required. All you have to do is then connect any switches, sensors, lamps or contactors you wish to use. Figure 3.1 Lamp controller with relays L01+ F1

S1

K1

S2

K1

H1 L01-

Publication 1760-UM002B-EN-P - March 2005

Page 82

3-4

Commissioning

In the following example, Pico GFX-70 carries out all the wiring and performs the tasks of the circuit diagram shown below. Figure 3.2 Lamp controller with GFX L01+ L01–

F1

S1

+24V 0V 0V

S2

I1 I2 I3

I 01----I 02-

--Ä Q 01

ALT

DEL OK ESC

1

H1 L01–

Publication 1760-UM002B-EN-P - March 2005

Q1

2

*

Page 83

Commissioning

3-5

Starting Point Status Display I ............ I

P-

MO 02:00 Q........

When you switch on Pico GFX-70, it opens the Status display immediately to show the switching state of the inputs and outputs. It also indicates whether the processor is already running a program. Note: If another display is visible, a visualization screen is shown.

STOP

The examples were written without the use of expansion units. If an expansion unit is connected, the Status display will first show the status of the basic unit and then the status of the expansion unit before showing the first selection menu.

TIP

In this case Pico GFX-70 must be in STOP mode. 1. Press OK to switch to the main menu. PROGRAM... STOP ✓

RUN

PARAMETERS

2. Press OK to switch to the next menu level, and press ESC to move one level back.

SET CLOCK...

TIP

OK has two other functions: • Press OK to save modified settings. • In the circuit diagram, you can also press OK to insert and modify contacts and relay coils.

CIRCUIT DIAGRAM FUNCTION RELAYS

3. Press OK twice to enter the circuit diagram display via menu items PROGRAM… −−> PROGRAM. This is where you will create the circuit diagram.

Publication 1760-UM002B-EN-P - March 2005

Page 84

3-6

Commissioning

Circuit Diagram Display ❚

The circuit diagram display is currently empty. The cursor flashes at the top left, which is where you will start to create your diagram. The location of the cursor is indicated in the status line. L: = Circuit connection (line), C: = Contact or coil (contact), B: = Free memory available in bytes. Start value 7944, with the first three circuit connections already generated. The Pico GFX-70 circuit diagram supports 4 contacts and one coil in series. The Pico GFX-70 display can display 6 circuit diagram contact fields.

❚❚❚❚❚❚❚M-❚❚❚❚❚❚❚m -❚❚❚❚❚❚❚ l ❚❚❚❚❚❚❚ L ❚❚❚❚❚❚❚-❚❚❚❚❚❚❚L: 1 C:1 B:7944

Use the up, down, left and right arrow buttons to move the cursor over the invisible circuit diagram grid. The first four columns are contact fields, the fifth column is a coil field. Each line is a circuit connection. Pico GFX-70 automatically connects the contact to the power supply. Figure 3.3 Circuit diagram with inputs I1, I2 and output Q1 I 01----I 02--...-[ Q 01

L: 1 C:1 B:7944

Now try to wire up the following Pico GFX-70 diagram. Switches S1 and S2 are at the input. I 01 and I 02 are the contacts for the input terminals. Relay K1 is represented by the relay coil [ Q 01. The symbol [ identifies the coil's function, in this case a relay coil acting as a contactor. Q 01 is one of the Pico GFX-70 output relays.

Publication 1760-UM002B-EN-P - March 2005

Page 85

Commissioning

3-7

From the First Contact to the Output Coil With Pico GFX-70, you work from the input to the output. The first input contact is I 01. 1. Press OK. I 01

Pico GFX-70 proposes the first contact I 01 at the cursor position. L: 1 C:1 B:7944

I 01

I flashes and can be changed, for example, to a P for a push button input using the up/down arrows keys. However, nothing needs to be changed at this point.

2. Press OK twice, to move the cursor across the 01 to the second contact field.

❚

L: 1 C:1 B:7944

You could also move the cursor to the next contact field using the left arrow button. 3. Press OK.

I 01

I 02

L: 1 C:2 B:7944

Again, Pico GFX-70 inserts a contact I 01 at the cursor position. Change the contact number to I 02, so that break contact S2 can be connected to input terminal I2. 4. Press OK so that the cursor jumps to the next position and use the up/down arrow keys to change the number to 02. TIP

You can press DEL to delete a contact at the cursor position.

5. Press OK to move the cursor to the third contact field. -I 02

Â

You do not need a third relay contact, so you can now wire the contacts directly up to the coil field. L: 1 C:3 B:7944

Publication 1760-UM002B-EN-P - March 2005

Page 86

3-8

Commissioning

Wiring Pico GFX-70 displays a small arrow l in the circuit diagram when creating the wiring. 1. Press ALT to activate the wiring arrow cursor and use the arrow buttons to move it.

TIP

ALT also has two other functions depending on the cursor position: • In the left contact field, you can press ALT to insert a new empty circuit connection. • The contact under the cursor can be changed between a make and break contact by pressing the ALT button.

❚❚❚❚❚❚❚ M-❚❚❚❚❚❚❚❚❚❚❚ml❚❚-l❚❚❚❚❚❚❚L -❚❚❚❚❚❚❚❚❚❚❚❚❚❚

The wiring arrow works between contacts and relays. When you move the arrow onto a contact or relay coil, it changes back to the cursor and can be reactivated with ALT if required.

L: 1 C:1 B:7944

TIP

-I 02 l

Pico GFX-70 automatically wires adjacent contacts in a circuit connection up to the coil.

2. Press ALT to wire the cursor from I 02 through to the coil field. The cursor changes into a flashing wiring arrow and automatically jumps to the next possible wiring position. 3. Press the left arrow button. Contact I 02 will be connected up to the coil field. TIP

You can use DEL to erase a connection at the cursor or arrow position. Where connections intersect, the vertical connections are deleted first, then, if you press DEL again, the horizontal connections are deleted.

4. Press the left arrow button again. The cursor will move to the coil field. 5. Press OK. --------[ Q 01

Pico GFX-70 inserts the relay coil Q 01. The specified coil function [ and the output relay Q 01 are correct and do not have to be changed. L: 1 C:1 B:7944

Your first working Pico GFX-70 circuit diagram now looks like this: Publication 1760-UM002B-EN-P - March 2005