The text of a manual · part 10 of 46
Pico GFX-70 Controllers User Manual: 2 - Installation, pages 71 to 78
Pages 71 to 78 of 400, from Pico GFX-70 Controllers User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley GFX-70 1760-DUB
Page 71
Installation
2-37
Figure 2.44 Bus termination resistors Terminating Resistor
Location 1
First Station on the Pico-Link
Station 1
R 1 - 12
GFX-70 S1-8
Location 2
GFX-70
GFX-70
Station 2
Location 3
GFX-70
Station 3
Location 8
Last Station on the Pico-Link
Station 8
GFX-70
Terminating Resistor
Both RJ45 interfaces are visible after the cover plate has been removed. When a cable is plugged in, the mechanical connection must be audible (click) and visible. Before a plug or cable is removed, the mechanical locking feature must be undone. Figure 2.45 Plugging and unplugging cables
1
2 3
Publication 1760-UM002B-EN-P - March 2005
Page 72
2-38
Installation
Connecting the Serial Interface
The GFX processor unit is provided with a multi-function interface. This can be used to set up point-to-point communication between different devices. The interface is also used for connecting PicoSoft Pro. The serial interface must be implemented using special cables. The standard 1760-CBL-2M cable is 2m in length.
IMPORTANT
The 1760-CBL-2M cable must not be lengthened in order ensure compliance with EMC requirements.
1. Remove the interface cover or other plugs from the interface. 2. Fit the connectors in the devices.
Publication 1760-UM002B-EN-P - March 2005
Page 73
Installation
2-39 a
IMPORTANT
It must be ensured in all circumstances that the connector with the marking POW-Side is fitted in the interface of the GFX device. The serial interface only functions if the GFX device is providing the power feed required for the interface cable.
Figure 2.46 Point-to-point serial interface
POW-Side
Publication 1760-UM002B-EN-P - March 2005
Page 74
2-40
Installation
Expanding Inputs/Outputs
You can add expansion units to all GFX types with an expansion I/O socket to increase the number of inputs and outputs: Table 2.47 Pico Expansion I/O Modules Processor Unit
I/O Modules
Description
1760-LDF 1760-LDFA 1760-LDFC 1760-LDFCA
1760-IA12XOW6I
12 AC inputs, 6 relay outputs
1760-IB12XOB8
12(1) DC inputs, 8 transistor outputs
1760-IB12XOW6I
12 DC inputs, 6 isolated relay outputs
1760-OW2
2 relay outputs
(1) Four of the digital dc inputs can alternately be used as 0 to 10V dc analog inputs. These inputs can be used as either digital or analog, not both. For example you could use 4 analog inputs plus 8 digital inputs.
Local Expansion Local expansion units are fitted directly next to the processor unit with the expansion I/O socket connection. Figure 2.48 Connecting local expansion units with Pico GFX-70 processors 1760-RPLCONN processor unit
ATTENTION expansion I/O
The following electrical separation is implemented between the processor unit of the GFX device and the expansion unit (separation always in local connection of expansion unit) • Simple isolation 400V ac (+10%) • Safe isolation 240V ac (+10%) Units may be destroyed if the value 400V ac +10% is exceeded, and may cause the malfunction of the entire system or machine.
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
GFX processor units and expansion units can be fed by different DC power supplies.
Page 75
Installation
2-41
Remote Expansion Expansion I/O modules can be located remotely from the primary controller by using the Pico-Link or serial interface. See Configuring a Pico-Link Network on page 3-14 and Configuring the Connection for the Terminal Mode on page 3-20 for more information.
Installing the Remote Processor
The remote processor is used for terminal mode operation of Pico controllers and I/O modules. The remote processor is used with either a Display or Display/Keypad Unit. Figure 2.49 Remote Processor Terminal Operation 1760-LDF...
1760-RM-GFX
Mounting and Removal Flush Mounting Figure 2.50 Flush Mounting Display and Remote Processor
3
2
1
M = 1.2 – 2 Nm 10.6 - 17.7 lb-in
2
1. Insert the display unit through the mounting holes on the panel.
Publication 1760-UM002B-EN-P - March 2005
Page 76
2-42
Installation
2. Attach the fixing rings. 3. Attach the processor unit.
Removal Procedure Figure 2.51 Removing the Remote Processor
3
2 1 1760 -RM
1. Insert the screwdriver into the mounting slide. 2. Push screwdriver to the right to open the slide. 3. Remove the processor unit from the display unit. 4. Loosen the fixing rings. 5. Remove the display unit from the panel.
Making Connections Connecting the Power Supply Figure 2.52 Remote Processor Power Supply Connection 1760-RM… L01+
L02+
L01–
>1 A U e = 24 V dc (20.4 – 28.8 V H dc) I e = 150 mA
0.6 x 3.5 x 100 24V 0V
Publication 1760-UM002B-EN-P - March 2005
Page 77
Installation
2-43
Connecting the Serial Cable
4
2
1
3
Cable Wire Color Code
1760- RM... cable
X5 X4 X3 X2 X1
X5 X4 X3 X2 X1 green white yellow brown gray
1. Remove the interface cover. 2. Using a screwdriver, push on the terminal latch. 3. Insert each wire into its designated terminal on the interface connector. 4. Replace the interface cover. Plug the other end of the cable into the Pico controller or I/O module.
Publication 1760-UM002B-EN-P - March 2005
Page 78
2-44
Installation
Publication 1760-UM002B-EN-P - March 2005