Page 62
2-28
Installation
Connecting the Outputs
The Q... outputs function inside the Pico GFX-70 as isolated contacts. Figure 2.31 Output “Q”
Q1 1
2
The respective relay coils are actuated in the Pico GFX-70 circuit diagram via the output relays Q 01 to Q 04 or S 01 to S 06 (S 08). You can use the signal states of the output relays as make or break contacts in the Pico GFX-70 circuit diagram for additional switching conditions. The relay or transistor outputs are used to switch loads such as fluorescent tubes, filament bulbs, contactors, relays or motors. Check the technical thresholds and output data before installing such devices. (See page A-1.)
Connecting Relay Outputs
1760-IB12XOW4IF, 1760-IB12XOW4IOF Figure 2.32 1760-IB12XOW4IF, 1760-IB12XOW4IOF relay outputs R 1 f 10 000 000
Q1
1
2
Q2
2
1
2
Q3
1
2
24 V H 8 A 115 V h 8 A 230 V h 8 A 1000 W
Q4
10 x 58 W
M 0 V H, N f 8 A/B 16 L1, L2, L3 (115/250 V h) +24 V H
Publication 1760-UM002B-EN-P - March 2005
...
...
2A 2A 2A
...
25 000
Page 63
Installation
2-29
1760-IA12XOW6I Figure 2.33 1760-IA12XOW6I relay outputs 1 2 S1
1 2 S2
1 2 S3
1 2
1 2 S4
S5
1 2
R
S6
24 V H 8 A 115 V h 8 A 230 V h 8 A
10 000 000
2A 2A 2A
1000 W 0 V H, N
10 x 58 W
25 000
F 8 A/B 16 L1, L2, L3 (115/230 V h) + 24 V H
1760-OW2 Figure 2.34 1760-OW2 relay outputs 1 S1 10 000 000
2
1 2
R S2
24 V H 8 A 115 V h 8 A 230 V h 8 A
2A 2A 2A
1000 W 0 V H, N
10 x 58 W
25 000
F 8 A/B 16 L1, L2, L3 (115/230 Vh) + 24 V H
Unlike the inputs, the 1760-IB12XOW4IF, 1760-IB12XOW4IOF, and 1760-IA12XOW6I, relay outputs can be connected to different lines.
ATTENTION
Do not exceed the maximum voltage of 250V ac on a relay contact. If the voltage exceeds this threshold, flashover may occur at the contact, resulting in damage to the device or a connected load.
Publication 1760-UM002B-EN-P - March 2005
Page 64
2-30
Installation
Connecting Transistor Outputs
1760-IB12XOB4IF, 1760-IB12XOB4IOF Figure 2.35 1760-IB12XOB4IF, 1760-IB12XOB4IOF transistor outputs R + 24 V H (20.4 – 28.8 V H)
24 V H
0.5 A
0.5 A 5 W/24 V
F 10 A 24 VQ
0 VQ
Q1
Q2
Q3
Q4
1760-IB12XOB8 Figure 2.36 1760-IB12XOB8 transistor outputs
24 VQ S1
S2
S3
S4
S5
S6
S7
0 VQ
S8
F 10 A
0VH f 2.5 A
R + 24 V H (20.4 – 28.8 V H)
24 V H
0.5 A
0.5 A 5 W/24 V
Parallel connection: Up to four outputs can be connected in parallel in order to increase the power. The output current will increase in this case to a maximum of 2 A.
Publication 1760-UM002B-EN-P - March 2005
Page 65
Installation
ATTENTION
ATTENTION
2-31
Outputs may only be connected in parallel within a group (Q1 to Q4 or Q5 to Q8, S1 to S4 or S5 to S8), such as Q1 and Q3 or Q5, Q7 and Q8. Outputs connected in parallel must be switched at the same time.
Please note the following when switching off inductive loads: Suppressed inductive loads cause less interference in the entire electrical system. For optimum suppression the suppressor circuits are best connected directly in the proximity of the inductive load.
If inductive loads are not suppressed, the following applies: Several inductive loads should not be switched off simultaneously to avoid overheating the driver blocks in the worst possible case. If in the event of an emergency stop the +24V dc power supply is to be switched off by means of a contact, and if this would mean switching off more than one controlled output with an inductive load, then you must provide suppressor circuits for these loads (see the following diagrams). Figure 2.37 Inductivity with suppressor circuit + 24 V H Uemax < UZ < 33 V Q., S.
Q., S.
0VH
Short-Circuit and Overload Behavior Should a short circuit or overload occur on a transistor output, this output will switch off. The output will switch on up to maximum temperature after the cooling time has elapsed. This time depends on the ambient temperature and the current involved. If the fault condition persists, the output will keep switching off and on until the fault is corrected or until the power supply is switched off. (See Monitoring of Short-Circuit and Overload with 1760-IB12XOB8 on page 8-7).
Publication 1760-UM002B-EN-P - March 2005
Page 66
2-32
Installation
Connecting Analog Outputs
1760-IB12XOW4IOF and 1760-IB12XOB4IOF each have an analog output QA 01, 0V dc to 10V dc, 10 bit resolution (0 to 1023). The analog output allows you to control servo valves and other final controlling elements.
ATTENTION
Analog signals are more sensitive to interference than digital signals. Consequently, more care must be taken when laying and connecting the signal lines. Incorrect switching states may occur if they are not connected correctly.
Connecting Servo Valves Figure 2.38 Connecting servo valves L01+
L02+
L01– >1A
A
+24V 0V 0V
Publication 1760-UM002B-EN-P - March 2005
I1
I2
B
I3
I4 I5
I6 I7
I8 I9 I10 I11 I12 0V 0V QA 1
Page 67
Installation
2-33
Setpoint Entry for a Drive Figure 2.39 Setpoint entry for a drive L02+
L01+ L01– >1A
0V IA
A
+24V 0V 0V
Connecting the Pico-Link
I1
I2
B
I3
I4 I5
I6 I7
I8 I9 I10 I11 I12 0V 0V QA 1
Pico GFX-70 with network connection (1760-LDFC) can be used for creating the Pico-Link network. Up to eight devices can be connected to this network. Further information can be found in Pico-Link and Point-to-Point Serial Connections on page 6-1.
Accessories Connection Plug 8-pole RJ45, 1760-CONN-RJ45
Connection Assignment of the RJ45 Socket on the Device Figure 2.40 RJ45 socket 1 2 3 4 5 6 7 8
Publication 1760-UM002B-EN-P - March 2005
Page 68
2-34
Installation
Connection Cable 4-pair twisted cable; see General on page A-1 Figure 2.41 Connection assignment A A B B
1 ECAN_H 2 ECAN_L 3 GND (Ground) 4 SEL_IN
ECAN_H data cable, pin 1, cable pair A ECAN_L data cable, pin 2, cable pair A Ground cable GND, pin 3, cable pair B Select cable SEL_IN, pin 4, cable pair B
IMPORTANT
Minimum operation with Pico-Link functions with the cables ECAN_H, ECAN_L and GND. The SEL_IN cable is only used for automatic addressing.
Table 2.42 Prefabricated Cables (RJ45 plug on both ends) Catalog Number
Cable Length (cm)
1760-CBL-INT01
30
1760-CBL-INT03
80
1760-CBL-INT05
150
Material for Self-Manufactured Cables • 100m cable: 1760-CBL-INT300 • Crimping tool for RJ45 plug
Bus Termination Resistor The first and last stations in the network must be provided with a bus termination resistor. • Value: 124 Ω • Termination connector: 1760-TERM1
Publication 1760-UM002B-EN-P - March 2005
Page 69
Installation
2-35
Cable Length and Cross-Sections For correct operation of the network, the cable lengths, cross-sections and cable resistances must correspond to the following table. Table 2.43 Cable length
Cable Resistance
Cross-section m mΩ/m mm2
AWG up to 40
≤ 140
0.13
26 up to 175
≤ 70
0.25 to 0.34
23, 22 up to 250
≤ 60
0.34 to 0.5
22, 21, 20 up to 400
≤ 40
0.5 to 0.6
20, 19 up to 600
≤ 26
0.75 to 0.8
18 up to 1000
≤ 16
1.5
16
The surge impedance of the cables used must be 120 Ω.
Calculating the Cable Length with Known Cable Resistance If the resistance of the cable per unit of length is known (resistance per unit length R’ in Ω/m), the entire cable resistance RL must not exceed the following values. RL depends on the selected baud rates:
Baud rate
Cable resistance RL kBaud
Ω
10 to 125
≤ 30
250
≤ 25
500
≤ 12
1000 lmax = maximum cable length in m RL = Total cable resistance in Ω R’ = Cable resistance per unit length in Ω/m lmax = RL R’
Publication 1760-UM002B-EN-P - March 2005
Page 70
2-36
Installation
Calculating Cross-Section with Known Cable Lengths The minimum cross-section is determined for the known maximum extent of the network. l = cable length in m Smin = minimum cable cross-section in mm2
ρ cu = resistivity of copper, if not otherwise stated 0.018 Ω mm2/m
Smin = l x ρ cu 12.4
IMPORTANT
If the result of the calculation does not yield a standard cross-section, the next larger cross-section is used.
Calculating Length with Known Cable Cross-Section The maximum cable lengths are calculated for a known conductor cross-section. lmax = cable length in m S = minimum cable cross-section in mm2
ρ cu = resistivity of copper, if not otherwise stated 0.018 Ω mm2/m lmax = S x 12.4 ρ cu
Plugging and Unplugging Network Cables Pico GFX-70 is provided with two RJ45 network sockets. The socket 1 in the first station is for the bus terminating resistor. For other stations, socket 1 is used for plugging in the incoming cable. Socket 2 is used for the outgoing cable or for the bus termination resistor on the last physical station in the network.
Publication 1760-UM002B-EN-P - March 2005