Page 53

Installation

2-19

1760-IB12XOB8 Expansion Module Figure 2.19 Power supply on the DC expansion units L01+ L01F1

E+ E-

IMPORTANT

R1

...

R12 24V 0V 0V 24 V

The module is protected against polarity reversal. To ensure that module works correctly, ensure that the polarity of each terminal is correct.

Cable Protection Provide cable protection (F1) for at least 1A (slow).

IMPORTANT

When the expansion I/O or the GFX is switched on for the first time, its power supply circuit behaves like a capacitor. Use a suitable device for switching on the power supply and do not use any Reed relay contacts or proximity switches.

Publication 1760-UM002B-EN-P - March 2005

Page 54

2-20

Installation

Connecting the Inputs

The inputs switch electronically. Once you have connected a contact via an input terminal, you can reuse it as a contact in your Pico GFX-70 circuit diagram as often as you like. Figure 2.20 Connecting the inputs L +24 V S1

N 0V

I1 I1 i1

Connect contacts such as push button actuators or switches to the input terminals.

Connecting AC Inputs

ATTENTION

Publication 1760-UM002B-EN-P - March 2005

Connect the inputs to the same line as the power feed in accordance with the VDE, IEC, UL and CSA safety regulations. Otherwise the module will not detect the switching level and may be damaged or destroyed by overvoltage.

Page 55

Installation

2-21

Figure 2.21 1760-IA12XOW6I Expansion unit L1 N F1

E+ E–

R1 R2 R3 R4

R5

R6

R7 R8 R9

R10 R11 R12

L

N

N

100-240 V

Connect the inputs, for example, to push button actuators, switches or relay/contactor contacts. Input signal voltage range • OFF signal: 0V ac to 40V ac • ON signal: 79V ac to 264V ac Input current • R1 to R12 0.5 mA/0.25 mA at 230V ac/115V ac

Cable Lengths Severe interference can cause a “1” signal on the inputs without a proper signal being applied. Observe therefore the following maximum cable lengths: • R1 to R12: 40m without additional circuit The following applies to expansion units: With longer cables, connect a diode (e.g. 1N4007) for 1A, minimum 1 000V reverse voltage, in series to the input. Ensure that the diode is pointing towards the input as shown in the circuit diagram, otherwise the module will not detect the 1 state.

Publication 1760-UM002B-EN-P - March 2005

Page 56

2-22

Installation

Figure 2.22 1760-IB12XOB8 with a diode on the inputs L1 N F1

E+ E–

R1 R2 R3 R4

R5

R6

R7 R8 R9

R10 R11 R12

L

N

N

100-240 V

Two-wire proximity switches have a residual current with the “0” state. If this residual current is too high, the input may detect a “1” signal. If inputs with a higher input current are required, an additional input circuit must be used.

Increasing the Input Current The following input circuit can be used in order to prevent interference and also when using two-wire proximity switches: Figure 2.23 Increasing the input current L1 N F1

100 nF/275 V h

E+ E–

R1 R2 R3 R4

R5

R6

100-240 V

Publication 1760-UM002B-EN-P - March 2005

R7 R8 R9

R10 R11 R12

L

N

N

Page 57

Installation

IMPORTANT

2-23

When using a 100 nF capacitor, the drop-out time of the input increases by 80 (66.6) ms at 50 (60) Hz.

A resistor can be connected in series with the circuit shown in order to restrict the inrush current. Figure 2.24 Limitation of the inrush current with a resistor L1 N F1

1 kO 100 nF/275 V h

E+ E–

R1 R2 R3 R4

R5

R6

R7 R8 R9

R10 R11 R12

L

N

N

100-240V

Connecting DC Inputs Use input terminals I1 to I12 to connect push button actuators, switches or 3 or 4-wire proximity switches. Given the high residual current, do not use 2-wire proximity switches. Input signal voltage range • I1 to I6, I9, I10 – OFF signal: 0V dc to 5V dc – ON signal: 15V dc to 28.8V dc • I7, I8, I11, I12 – OFF signal: < 8V dc – ON signal: > 8V dc Input current • I1 to I6, I9, I10, R1 to R12: 3.3 mA at 24V dc • I7, I8, I11, I12: 2.2 mA at 24V dc

Publication 1760-UM002B-EN-P - March 2005

Page 58

2-24

Installation

Figure 2.25 GFX DC L01+

L02+

L01– >1A

+24V 0V 0V

IMPORTANT

I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12

The digital inputs must have the same voltage as the power supply of the GFX.

Figure 2.26 1760-IB12XOB8 L01 + L01 – F1

E+ E–

R1 R2 R3 R4

R5

R6

24 V H

Publication 1760-UM002B-EN-P - March 2005

R7 R8 R9

R10 R11 R12 +24V 0V

0V

Page 59

Installation

2-25

Connecting Analog Inputs Inputs I7, I8, I11 and I12 can also be used to connect analog voltages ranging from 0V dc to 10V dc. The following applies: • I7 = IA01 • I8 = IA02 • I11 = IA03 • I12 = IA04 The resolution is 10-bit = 0 to 1023.

ATTENTION

Analog signals are more sensitive to interference than digital signals. Consequently, more care must be taken when laying and connecting the signal lines. Incorrect switching states may occur if they are not connected correctly.

• Use shielded twisted pair cables to prevent interference with the analog signals. • For short cable lengths, ground the shield at both ends using a large contact area. If the cable length exceeds 30m or so, grounding at both ends can result in equalization currents between the two grounding points and thus in the interference of analog signals. In this case, only ground the cable at one end. • Do not lay signal lines parallel to power cables. • Connect inductive loads to be switched via the Pico GFX-70 outputs to a separate power feed, or use a suppressor circuit for motors and valves. If loads such as motors, solenoid valves or contactors are operated with Pico GFX-70 via the same power feed, switching may give rise to interference on the analog input signals. The following circuits contain examples of applications for analog value processing.

IMPORTANT

Ensure that the reference potential is connected. Connect the 0V of the power supply unit for the different set point potentiometers and sensors shown in the examples to the 0V terminal of the Pico GFX-70 power feed.

Publication 1760-UM002B-EN-P - March 2005

Page 60

2-26

Installation

Set Point Potentiometer Figure 2.27 Set Point potentiometer, set point potentiometer with upstream resistor L01+

L02+

L01– >1A

1.3 kO/0.25 W 1 kO/0.25 W h H 0V

+24V 0V 0V

I1

I2

I3

I4 I5

I6 I7

+12 V

I8 I9 I10 I11 I12

Use a potentiometer with a resistance of greater than or equal to1 kΩ, e.g. 1 kΩ, 0.25W.

Temperature Sensor, Brightness Sensor, 20 mA Sensor Figure 2.28 Temperature sensor, brightness sensor, 20 mA sensor L02+

L01+ L01– h H

>1A 0V

+12 V

+24 V H 0...10 V a –35...55 ˚C

4...20 mA

0V Out 0...10 V

500 O

+24V 0V 0V

I1

I2

I3

I4 I5

I6 I7

I8 I9 I10 I11 I12

4 to 20 mA (0 to 20 mA) sensors can be connected using an external 500 Ω resistor. The following values apply: • 4 mA = 1.9V • 10 mA = 4.8V • 20 mA = 9.5V (according to U = R x I = 478 Ω x 10 mA ~ 4.8V) Publication 1760-UM002B-EN-P - March 2005

Page 61

Installation

2-27

Connecting High-Speed Counters and Frequency Generators High-speed counter signals on the Pico GFX-70 can be counted correctly on inputs I1 to I4 independently of the cycle time. Figure 2.29 High-speed counter, frequency generator L02+

L01+ L01– >1A

+24V 0V 0V

I1

I2

I3

I4 I5

I6 I7

I8 I9 I10 I11 I12

Connecting Incremental Encoders Inputs I1, I2 and I3, I4 on the Pico GFX-70 can each be used for the high-speed counting of an incremental encoder independently of the cycle time. The incremental encoder must generate two 24V dc square wave signals with a 90° phase shift between them. Figure 2.30 Connecting incremental encoders L01+

L02+

L01– >1A

A

+24V 0V 0V

B

I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12

Publication 1760-UM002B-EN-P - March 2005