Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 7 of 46

Pico GFX-70 Controllers User Manual: 2 - Installation, pages 44 to 52

Pages 44 to 52 of 400, from Pico GFX-70 Controllers User Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley GFX-70 1760-DUB

Page 44

2-10

Installation

Figure 2.13 Mounting the Processor Unit

Mounting the Inputs/Outputs onto the Processor Unit

Publication 1760-UM002B-EN-P - March 2005

Page 45

Installation

IMPORTANT

2-11

The inputs/outputs can be mounted before or after mounting the processor unit onto the fixing shaft.

Removing the Inputs/Outputs

1. Press the two catches together. 2. Pull one side out of the catch. 3. Pull the other side out of the second catch.

Publication 1760-UM002B-EN-P - March 2005

Page 46

2-12

Installation

Remove the I/O module.

Removing the Processor Unit The processor unit can be removed with or without the I/O module.

IMPORTANT

If there is another fixing point for the DIN rail, apart from the one for the display/keypad, undo it.

Use a screwdriver with a 100 x 3.5 mm slot width. 1. Insert the screwdriver into the lug of the fixing shaft catch. 2. Lever out the slide catch. 3. Pull out the processor unit from the fixing shafts.

Publication 1760-UM002B-EN-P - March 2005

Page 47

Installation

2-13

Mounting on a DIN Rail The processor unit can be mounted on a DIN rail without the display/keypad. The fastening catches must be removed in order to mount the device on a fastened DIN rail. 1. Remove the spring with a screwdriver.

2. Pull the slide catch out of the guide and remove it.

Publication 1760-UM002B-EN-P - March 2005

Page 48

2-14

Installation

3. Hook the Pico GFX-70 to the top edge of the DIN rail and hinge into place while pressing down slightly.

4. Press down lightly on both the device and the DIN rail until the unit snaps over the lower edge of the DIN rail. The Pico GFX-70 will clip into place automatically. 5. Check that the device is seated firmly. The device is mounted vertically on a DIN rail in the same way.

Screw Mounting The processor unit can be screwed onto a mounting plate without the display/keypad. For screw mounting on a mounting plate, mounting feet must be used that can be fixed to the back of the Pico GFX-70. The mounting feet are available as an accessory.

Publication 1760-UM002B-EN-P - March 2005

Page 49

Installation

CK

CLI

2-15

!

1760-NMF mounting feet

IMPORTANT

Three mounting feet are sufficient for a device with four fixing points.

Figure 2.14 Screw mounting for the GFX

Figure 2.15 Screw mounting for the 1760-IA12XOW6I and 1760-IB12XOB8

Publication 1760-UM002B-EN-P - March 2005

Page 50

2-16

Installation

Connecting the Expansion Unit

You can only add one Pico expansion I/O module to each controller.

Terminals

Tool for Cage Clamp Terminals

Figure 2.16 Connecting expansion units

Slot-head screwdriver, width 3.5 mm x 0.6 mm.

Connection Cross-Sections of the Cage Clamp Terminal Cables • Solid: 0.2 to 4 mm2 (AWG 24 -12) • Flexible with ferrule: 0.2 to 2.5 mm2 (AWG 24-12)

Tool for Slot-Head Screws for Expansion I/O Unit Slot-head screwdriver, width 3.5 x 0.6 mm, tightening torque 0.6 Nm.

Connection Cross-Sections of Screw Terminal Cables • Solid: 0.2 to 4 mm2 (AWG 22 - 12) • Flexible with ferrule: 0.2 to 2.5 mm2 (AWG 22 -12)

Publication 1760-UM002B-EN-P - March 2005

Page 51

Installation

Connecting the Power Supply

2-17

The required connection data for both device types GFX, 1760-IB12XOB8 with 24V dc and 1760-IA12XOW6I with standard voltages of 100V ac to 240V ac are shown on page A-1.

TIP

The Pico GFX-70 devices run a system test for one second after the power supply has been switched on. Either RUN or STOP mode will be activated after this time depending on the default setting.

1760-IA12XOW6I Expansion Units Figure 2.17 Power supply on the AC expansion units L N F1

E+ E-

R1

ATTENTION

...

R12 L N N 100-240 V ~

A short current surge will be produced when switching on for the first time. Do not switch on the module via Reed contacts since these may burn or melt.

Publication 1760-UM002B-EN-P - March 2005

Page 52

2-18

Installation

DC Power Supply for the GFX-70 Figure 2.18 Power supply on the GFX L02+

L01+ L01– >1A

+24V 0V 0V

The GFX processor unit supplies the necessary power supply to itself, the display, the input/output electronics, the expansion I/O, and optionally the Pico-Link cable.

IMPORTANT

Publication 1760-UM002B-EN-P - March 2005

The GFX device processor unit is protected against reverse polarity. Ensure the correct polarity of the terminals to ensure that the GFX functions correctly.