The text of a manual · part 17 of 46
Pico GFX-70 Controllers User Manual: 4 - Wiring with Pico GFX-70, pages 131 to 140
Pages 131 to 140 of 400, from Pico GFX-70 Controllers User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley GFX-70 1760-DUB
Page 131
Wiring with Pico GFX-70
4-21
Deleting Contacts and Coils 1. Move the cursor to a contact or coil field. 2. Press DEL. The contact or the coil will be deleted, together with any connections.
Changing Make Contacts to Break Contacts Every contact in the Pico GFX-70 circuit diagram can be defined as either a make contact or a break contact. 1. Switch to Entry mode and move the cursor over the contact name. 2. Press ALT. The make contact will change to a break contact. 3. Press OK twice to confirm the change. Figure 4.7 Change contact I 03 from make to break
I 02--|---
I 02--|----
I 02--|----
I 03--|
I 03--|
I 03--|
ALT
OK
2x
Creating and Modifying Connections Contacts and relay coils are connected with the arrow in the Connect mode. Pico GFX-70 displays the cursor in this mode as an arrow. 1. Use the arrow buttons to move the cursor onto the contact field or coil field from which you wish to create a connection.
IMPORTANT
Do not position the cursor on the first contact field. At this position the ALT button has a different function (Insert circuit connection).
Publication 1760-UM002B-EN-P - March 2005
Page 132
4-22
Wiring with Pico GFX-70
2. Press ALT to switch to Connect mode. 3. Use the left and right arrow buttons to move the diagonal arrow between the contact fields and coil fields and the up and down arrow buttons to move between circuit connections. 4. Press ALT to leave Connect mode. Pico GFX-70 will leave the mode automatically when you move the diagonal arrow onto a contact field or coil field which has already been assigned.
IMPORTANT
In a circuit connection, Pico GFX-70 automatically connects contacts and the terminal to the relay coil if there are no empty fields in-between.
Never work backwards. You will learn why wiring backwards does not work in Effects on the Creation of the Circuit Diagram on page 8-3. Figure 4.8 Circuit diagram with five contacts, invalid I 01----Q 04----I 03--| | |--------------|-I 02----I 04-----------S Q 02
When wiring more than four contacts in series, use one of the 96 M marker relays. Figure 4.9 Circuit diagram with M marker relay I 01----Q 04----I 03-----------S M 01 I 02----I 04----M 01-----------S Q 02
Deleting Connections 1. Move the cursor onto the contact field or coil field to the right of the connection that you want to delete. Press ALT to switch to Connect mode. 2. Press DEL. Pico GFX-70 will delete a connection. Closed adjacent connections will be retained.
Publication 1760-UM002B-EN-P - March 2005
Page 133
Wiring with Pico GFX-70
4-23
If several circuit connections are connected to one another, Pico GFX-70 first deletes the vertical connection. If you press DEL again, it will delete the horizontal connection as well.
IMPORTANT
You cannot delete connections that Pico GFX-70 has created automatically.
3. Close the delete operation with ALT or by moving the cursor to a contact or coil field.
Inserting and Deleting a Circuit Connection The Pico GFX-70 circuit diagram display shows three of the 256 circuit connections on the display at the same time. Pico GFX-70 automatically scrolls up or down the display to show hidden circuit connections - even empty ones - if you move the cursor past the top or bottom of the display. A new circuit connection is added below the last connection or inserted above the cursor position: 1. Position the cursor on the first contact field of a circuit connection. 2. Press ALT. The existing circuit connection with all its additional connections is “shifted” downwards. The cursor is then positioned directly in the new circuit connection. Figure 4.10 Inserting a new circuit connection I 02--|-----I 03--|
I 02--|------| I 03--|
Publication 1760-UM002B-EN-P - March 2005
Page 134
4-24
Wiring with Pico GFX-70
Saving Circuit Diagrams 1. Press the ESC button to save a circuit diagram. The menu on the left appears in the status line. I 01----I 02--Q 01----HY01Q1-| ▲ SAVE
▼
2. Press OK to save the entire program, circuit diagram and function blocks. After saving you will be in the CIRCUIT DIAGRAM menu.
Aborting Circuit Diagram Entry 1. If you want to exit without saving the circuit diagram, press ESC. I 01----I 02--Q 01----HY01Q1-| ▲ CANCEL
▼
2. Use the arrow buttons to select the CANCEL menu. 3. Press OK. The circuit diagram is closed without saving.
Searching for Contacts and Coils You can search for contacts and coils in the following way: I 01----I 02--Q 01----HY01Q1-| ▲ SEARCH
▼
1. Press ESC. Use the arrow buttons to select the SEARCH menu. 2. Press OK. 3. Select the desired contact, coil and number.
I 01----I 02--Q 01----HY01Q1-|
SEARCH
I 01
Publication 1760-UM002B-EN-P - March 2005
With function relays, select the function block, the number and the coil. 4. Confirm the search with the OK button.
Page 135
Wiring with Pico GFX-70
I 01----I 02--Q 01----HY01Q1-|
L:
1 C:1 B:7140
4-25
The device will search for the first occurrence of the contact or coil from the start of the search to the end of the circuit diagram. If no contact or coil is found, the Pico GFX-70 circuit diagram editor will continue the search from the start of the circuit diagram. If a contact or coil is found, the Pico GFX-70 editor automatically jumps to the respective field in the circuit diagram.
“Go To” a Circuit Connection The Pico GFX-70 circuit diagram editor provides a Go To function to enable fast access to a circuit connection. 1. Press ESC and use the arrow keys to select the GO TO menu. 2. Press OK. 3. Select the required circuit connection (L... …). I 01----I 02--Q 01----HY01Q1-|
L:
1 C:1 B:7140
I 01----I 02--Q 01----HY01Q1-|
L:
The first contact on the circuit connection is always indicated. 4. Press OK. The cursor remains stationary at the required circuit connection contact L 1.
1 C:1 B:7140
Deleting the Circuit Connection Pico GFX-70 only removes empty circuit connections (without contacts or coils). 1. Delete all the contacts and coils from the circuit connection. 2. Position the cursor on the first contact field of the empty circuit connection. 3. Press DEL.
Publication 1760-UM002B-EN-P - March 2005
Page 136
4-26
Wiring with Pico GFX-70
The subsequent circuit connection(s) will be “pulled up” and any existing links between circuit connections will be retained.
Switching Via the Cursor Buttons With Pico GFX-70, you can also use the four cursor buttons as hard-wired inputs in the circuit diagram. The buttons are wired in the circuit diagram as contacts P 01 to P 04. The P buttons can be activated and deactivated in the h System menu.
P2 P1
OK
P3
P4
The P buttons can also be used for testing circuits or manual operation. These button functions are also useful for servicing and commissioning purposes. Example 1 A lamp at output Q1 is switched on and off via inputs I1 and I2 or by using the up/down arrow buttons. Figure 4.11 Switch Q1 via I1, I2, or the up/down arrow buttons I 01--|------------------------S Q 01 | P 02-I 02--|------------------------R Q 01 | P 04--
Example 2 Input I1 is used to control output Q1. I5 switches over to cursor operation and via m 01 disconnects the circuit connection I 01. Figure 4.12 I5 switches over to the cursor buttons. I 05---------------------------S M 01 I 01----M 01--|----------------S Q 01 | P 01----M 01--
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
The P buttons are only detected as switches in the Status menu.
Page 137
Wiring with Pico GFX-70
4-27
The Status menu display shows whether the P buttons are used in the circuit diagram. Displayed on the Status display: I123456789… P2 MO 14:55 Q.2…6.8
RUN
• P: button function wired and active • P2: button function wired, active and P2 button (up arrow key) pressed • P-: button function wired and not active • Empty field: P buttons not used
Checking the Circuit Diagram Pico GFX-70 contains a built-in measuring device enabling you to monitor the switching states of contacts, relays and function block coils during operation. 1. Create the small parallel circuit below and save it. Figure 4.13 Parallel circuit I 02--|------------------------S Q 01 I 03--|
2. Switch Pico GFX-70 to RUN mode via the main menu. 3. Return to the circuit diagram display. You are now unable to edit the circuit diagram.
IMPORTANT
If you switch to the circuit diagram display and are unable to modify a circuit diagram, first check whether Pico GFX-70 is in STOP mode.
The circuit diagram display performs two functions depending on the mode:
Publication 1760-UM002B-EN-P - March 2005
Page 138
4-28
Wiring with Pico GFX-70
• STOP: Creation of the circuit diagram • RUN: Power flow display 4. Switch on I3. Figure 4.14 Power flow display I 02--|------------------------S Q 04 I 03--| L:001 C:1
RUN
In the power flow display, energized connections are thicker than non-energized connections. You can follow a current-carrying connection across all circuit connections by scrolling the display up and down. The bottom right of the power flow display indicates that the controller is in RUN mode. See Power Flow Display with Zoom Function on page 3-11. . IMPORTANT
The power flow display will not show signal fluctuations in the millisecond range. This is due to the inherent delay factor of LCD displays.
Function Block Editor The Pico GFX-70 has the FUNCTION RELAYS menu for editing the function blocks without circuit diagrams. The function blocks are an inherent component of the program.
Publication 1760-UM002B-EN-P - March 2005
Page 139
Wiring with Pico GFX-70
4-29
Calling the Function Blocks via the FUNCTION RELAYS Menu Figure 4.15 Explanation of the function block display Function, special function, parameter display Displays the function blocks used Current cursor line
❚❚ ❚❚ ❚❚❚ ❚❚❚ ❚ ❚❚ ❚❚ ❚❚❚ ❚❚ ❚❚ B:❚ ❚ ❚ ❚
L:001
Free memory in bytes
Display of the Function Blocks for Editing Figure 4.16 Function block display during editing Unit/special function Function Function block number Function block name
Parameter display (+ appears/ - does not appear)
❚❚ ❚❚ ❚❚❚ ❚❚❚ ❚
Function block inputs Function block outputs
>I1
❚❚❚❚❚❚❚❚❚❚❚
>I2
❚❚❚❚❚❚❚❚❚❚❚
Variable, operand for inputs
QV> ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚
Variable, operand for outputs
Editing Function Blocks 1. Go to the FUNCTION RELAYS menu. 2. Press the OK button. The following display appears if no function blocks are present. z z
The cursor flashes. L:001
B:7898
3. Press the OK button.
Publication 1760-UM002B-EN-P - March 2005
Page 140
4-30
Wiring with Pico GFX-70
The editor for inputting a function block is displayed. 4. Select the desired function block and number. AR01
L:001
B:7988
The functions of the individual function blocks are explained in the individual function block descriptions on the following pages. This display appears if there are function blocks present.
AR01 ADD
+
CP10
+
T 18 ?X
-
L:001
B:6488
The function blocks are created in the sequence in which they were edited.
Calling up Function Blocks from the Circuit Diagram If you enter a function block parameter from the circuit diagram, you will jump from the circuit diagram editor to the function block editor automatically. Once you have assigned the parameters, you will return to the position where you left the circuit diagram with Save or Cancel. The operation is carried out in the same way as with circuit diagram operation. Example: timing relay function block
T 01 X?
M:S +
>I1 20:30 >I2
Function block:
Timing relay
Switch function:
On-delayed with random switching
Time range:
M:S (Minute:Seconds)
Set time >I1:
20 min 30 s
Actual time QV>:
Copied to MD96
QV>MD96 L:001
B:7808
Publication 1760-UM002B-EN-P - March 2005