Page 141

Wiring with Pico GFX-70

4-31

Assigning Operands to an Input of a Function Block

IMPORTANT

Only the following variables can be assigned to the input of a function block: • Constants, e.g.: 42, • Markers such as MD, MW, MB, • Analog output QA, • Analog inputs IA, • All output variables of the function blocks …QV>

Assigning operands to a QV Output of a Function Block

IMPORTANT

Only markers such as MD, MW, MB or the analog output QA can be assigned to a variable output of a function block.

Deleting Operands on the Function Block Inputs and Outputs Position the cursor on the required operand. T 01 X? >I1

M:S +

❚ ❚ :30

1. Press the DEL button.

>I2 QV> MD96

The operand is deleted. T 01 X?

M:S +

>I1 ❚ ❚ >I2 QV>MD96 L:001

B:7808

Deleting an Entire Function Block AR01 ADD

+

CP10

+

T 18 ?X

-

L:002

B:7808

Ensure that all contacts and coils of the function block are deleted. 1. Select the required function block from the list. In this case CP10. 2. Press the DEL button. The function block is deleted.

AR01 ADD

+

T 18 ?X

-

L:001

Publication 1760-UM002B-EN-P - March 2005

Page 142

4-32

Wiring with Pico GFX-70

Checking Function Blocks You can check function blocks in the same way as circuit diagrams. The device is in RUN mode. Checking from the circuit diagram: Position the cursor on a contact or a coil of the required function block. Press OK. The function block will be displayed, in this case a timing relay. T 01 X? >I1

M:S +

• >I1= set time of the timing relay, • QV> = the actual value is 14 minutes 42 seconds, • The enable coil is actuated, EN is visible.

20:30

>I2 QV> 14:42 .. EN..

If a coil of a function block is actuated in RUN mode, the coil name with the coil designation will appear on the display.

Checking the Function Block via the Function Block Editor You access the function block list via the FUNCTION RELAYS menu. 1. Select the required function block. In this case the arithmetic function block AR01 in the Adder mode. AR01 ADD

+

CP10

+

T 18 ?X

-

L:001

2. Press the OK button.

RUN

The function block is presented with the actual values and the result. AR01 ADD >I1

20056

>I2

1095

+

QV> 21151

Publication 1760-UM002B-EN-P - March 2005

Displaying the Operands When Checking the Function Blocks If you want to know which operands are used on the function block inputs and outputs when checking the function block, press the ALT button on the displayed value.

Page 143

Wiring with Pico GFX-70

4-33

The operand is displayed. AR01 ADD >I1

C 01QV>

>I2

1095

+

• >I1 = Actual value of counter C 01 • >I2 = Constant 1095 • QV> = Marker double word MD56

QV> MD 56

3. Press the ALT button again. The display shows the values. AR01 ADD >I1

20056

>I2

1095

+

QV> 21151

Coil Functions You can set the coil function to determine the switching behavior of relay coils. The following coil functions are assigned to all coils: Table 4.17 Coil Function Pico GFX-70 display

Coil function

Example

[

Contactor function

[Q01,[D02,[S04,[:01,[M07,..

Impulse relay function

Q03, M04, D08, S07, :01,..

S

Set

SQ08,SM02,SD03,SS04..

R

Reset

RQ04,RM05,RD07,RS03..

]

Contactor function with ]Q06, ]M96.. negated result Cycle pulse with rising edge

M01..

Cycle pulse with falling edge

M42..

IMPORTANT

The function block descriptions state which coil functions can be used with the function block concerned.

Publication 1760-UM002B-EN-P - March 2005

Page 144

4-34

Wiring with Pico GFX-70

Rules for Wiring Relay Coils Relay with contactor function

IMPORTANT

A coil should only be used once to retain an overview of the relay states. However, retentive coil functions such as S, R, can be used several times. The following applies to non-retentive coil functions such as [ (contactor), ] (negated contactor), , (rising and falling edge detection): Each coil must only be used once. The last coil in the circuit diagram determines the status of the relay. Exception: When working with jumps, the same coil can be used twice.

Coil with Contactor Function [ The output signal follows immediately after the input signal and the relay acts as a contactor. Figure 4.18 Signal diagram of contactor function on on

Impulse Relay ä The relay coil switches whenever the input signal changes from 0 to 1. The relay behaves like a bistable flip-flop. Figure 4.19 Signal diagram of impulse relay

: on on

Publication 1760-UM002B-EN-P - March 2005

Page 145

Wiring with Pico GFX-70

4-35

A coil is automatically switched off if the power fails and if STOP mode is active. Exception: Retentive coils retain signal 1 (see Retention on page 7-22).

“Set” S and “Reset” R Coil Function The “Set” S and “Reset” R coil functions are normally used in pairs. The relay picks up when the coil is set (A) and remains in this state until it is reset (B) by the coil function. The supply voltage is switched off (C), the coil does not have a retentive effect. Figure 4.20 Signal diagram of “Set” and “Reset” on S on R on

A

B

C

If both coils are triggered at the same time, priority is given to the coil in the circuit diagram with the higher circuit connection number. This is shown in the above signal diagram in section B. Figure 4.21 Simultaneous triggering of Q 01 I 05---------------------------S Q 01 I 10---------------------------R Q 01

In the example above, the reset coil has priority with simultaneous triggering of the set and reset coils.

Publication 1760-UM002B-EN-P - March 2005

Page 146

4-36

Wiring with Pico GFX-70

Coil Negation (Inverse Contactor Function) ] The output signal is simply an inversion of the input signal; the relay operates like a contactor with contacts that have been negated. If the coil is triggered with the 1 state, the coil switches its make contacts to the 0 state. Figure 4.22 Signal diagram of inverse contactor function on on

Rising Edge Evaluation (Cycle Pulse)

,

If the coil is only meant to switch on a rising edge, this function will be applied. With a change in the coil state from 0 to 1, the coil switches its make contacts to the 1 state for one cycle. Figure 4.23 Signal diagram of cycle pulse with rising edge on on

Falling Edge Evaluation (Cycle Pulse) If the coil is only meant to switch on a falling edge, this function will be applied. With a change in the coil state from 1 to 0, the coil switches its make contacts to the 1 state for one cycle.

Publication 1760-UM002B-EN-P - March 2005

Page 147

Wiring with Pico GFX-70

4-37

Figure 4.24 Signal diagram of cycle pulse with falling edge on on

IMPORTANT

A set coil is automatically switched off if the power fails and if the device is in STOP mode. Exception: Retentive coils retain signal 1 (see Retention on page 7-22).

Publication 1760-UM002B-EN-P - March 2005

Page 148

4-38

Wiring with Pico GFX-70

Function Blocks

The function blocks are used to simulate some of the devices used in conventional open-loop and closed-loop control systems. Pico GFX-70 provides the following function blocks: • Analog value comparator/threshold controller (only with Pico GFX-70 24V dc variants) • Arithmetic – addition, subtraction, multiplication, division • Compare data blocks • Transfer data blocks • Boolean sequences • Counters – up and down counters with upper and lower threshold values, preset – frequency counters – high-speed counters – incremental encoder counters • Comparators • Text, output freely editable texts, enter values • Data function block • PID controllers • Smoothing filters • Value scaling • Pulse width modulator • Read (GET) Pico-Link data • Time switches – weekday/time – year, month, day (date) • Numerical converters • Master reset • Operating hours counter • Write (PUT) Pico-Link data • Synchronization of date and time via the Pico-Link • Timing relays – on-delayed – on-delayed with random switching – off-delayed, also retriggerable – off-delayed with random switching, also retriggerable – on and off delayed – on and off delayed with random switching

Publication 1760-UM002B-EN-P - March 2005

Page 149

Wiring with Pico GFX-70

4-39

– single pulse – synchronous flashing – asynchronous flashing • Set cycle time • Value limitation The following applies to function blocks:

IMPORTANT

The most recent actual values are cleared if the power supply is switched off or if Pico GFX-70 is switched to STOP mode. Exception: Retentive data keeps its state (see Retention on page 7-22). The most recent actual values are transferred to the operands every cycle. The data function block is an exception.

ATTENTION

IMPORTANT

The following applies to RUN mode: Pico GFX-70 processes the function block after a pass through the circuit diagram. The last state of the coils is used for this.

If you want to prevent other people from modifying the parameters, change the access enable symbol from “+” to “-” when creating the circuit diagram and setting parameters and protect the circuit diagram with a password.

Publication 1760-UM002B-EN-P - March 2005

Page 150

4-40

Wiring with Pico GFX-70

ATTENTION

The function blocks are designed so that a function block output can be assigned directly to the input of another function block. This enables you always to have an overview of which value is transferred. If different data formats are used, such as if the first function block uses 32 bits and an 8-bit or 16-bit format is used for further processing, sign value errors or value errors may occur when transferring from one function block to another one.

Analog Value Comparator/Threshold Value Switch Pico GFX-70 provides 32 analog value comparators from A 01 to A 32. With an analog value comparator or threshold value switch you can, for example, compare analog input values with a set point value. All Pico GFX-70 DC variants have analog inputs. The following comparisons are possible: • Function block input >I1 greater than or equal to, equal to, less than or equal to function block input >I2 • Using the factors >F1 and >F2 as inputs enables you to amplify and adjust the values of the function block inputs. • The >OS function block input can be used as an offset for the >I1 input. • The >HY function block input is used for the positive and negative switching hysteresis of the input >I2. The contact switches according to the selected comparison mode of the function block.

Publication 1760-UM002B-EN-P - March 2005