Page 231
Wiring with Pico GFX-70
ATTENTION
4-121
If circuit connections are skipped, the states of the coils are retained. The time value of timing relays that have been started will continue to run
Power Flow Display Jumped ranges are indicated by the coils in the power flow display. All coils after the jump coil are shown with the symbol of the jump coil.
Example A selector switch allows two different sequences to be set. • Sequence 1: Switch on Motor 1 immediately. • Sequence 2: Switch on Guard 2, Wait time, then switch on Motor 1. Contacts and relays used: • I1 Sequence 1 • I2 Sequence 2 • I3 Guard 2 moved out • I12 Motor-protective circuit-breaker switched on • Q1 Motor 1 • Q2 Guard 2 • T 01 Wait time 30.00 s, on-delayed • D 01 Text “motor-protective circuit-breaker tripped”
Publication 1760-UM002B-EN-P - March 2005
Page 232
4-122
Wiring with Pico GFX-70
Circuit diagram:
Power flow display: I 01 selected:
I 01------[ : 01
I 01------[ : 01
I 02------[ : 02
I 02--------: 01
: 01
: 01
--------|-[ Q 01 |-R
---------|[ Q 01 |R
Q 02
Q 02
----------[ : 08
----------[ : 08
: 02------[ Q 02
: 02--------: 08
Q 02-I 03-T T 02
Q 02--I 03--: 08
T 02------[ Q 01
T 02--------: 08
: 08
: 08
I 12 -------[ D 01
I 12 -------[ D 01
Range from jump label 1 processed. Jump to label 8. Range to jump label 8 skipped. Jump label 8, circuit diagram processed from this point on.
Master Reset The master reset function block allows you to reset the state of the markers and all outputs to the 0 state with a single command. Depending on the operating mode of this function block, it is possible to reset the outputs only, or the markers only, or both. 32 function blocks are available. Figure 4.53 Pico GFX-70 circuit diagram with master reset function block M 96-----------------------------[ MR16T
Parameter Display and Parameter Set for the Master Reset Function Block MR16
Q
+
MR16
Master reset function block number 16
Q
Reset outputs mode
+
Appears in the parameter display
Operating modes • Q: Acts on the outputs Q.., *Q.., S.., *S.., *SN.., QA01; *: network station address • M: acts on the marker range MD01 to MD48. • ALL: acts on Q and M.
Contacts MR01Q1 to MR32Q1
Publication 1760-UM002B-EN-P - March 2005
Page 233
Wiring with Pico GFX-70
4-123
The contact switches on the marker if the trigger coil MR..T has the 1 state.
Coils MR01T to MR32T: trigger coils
Memory Requirement of the Data Function Block The master reset function block requires 20 bytes of memory.
Function of the Data Master Reset The outputs or the markers are set to the 0 state in accordance with the operating mode when a rising edge is detected on the trigger coil.
IMPORTANT
The master reset function block should be used as the last function block in a program so that all data ranges are cleared reliably. Otherwise subsequent function blocks may overwrite the data ranges.
The contacts MR01Q1 to MR32Q1 assume the state of their own trigger coil.
Numerical Converters Pico GFX-70 provides 32 numerical converters NC01 to NC32. A numerical converter function block enables you to convert BCD coded values to decimal values or decimal coded values to BCD coded values.
Wiring of a Numerical Converter A numerical converter in the circuit diagram only has the enable coil. Figure 4.54 Pico GFX-70 circuit diagram with numerical converter I 05---------------------------[ NC02EN
Parameter display and parameter set for the numerical converter: NC02 BCD
+
>I1 QV>
Publication 1760-UM002B-EN-P - March 2005
Page 234
4-124
Wiring with Pico GFX-70
NC02
Numerical converter function block number 02
BCD
Convert BCD code to decimal value mode
+
Appears in the parameter display
>I1
Input value
QV>
Output value
In the parameter display of a numerical converter you can change the mode and the enable of the parameter display.
Numerical Converter Modes
Parameter
Mode
BCD
Convert BCD coded values to decimal values
BIN
Convert decimal value to BCD coded values
Number Range
Publication 1760-UM002B-EN-P - March 2005
Value
Number system
-161061273 to +161061273
BCD
-9999999 to +9999999
Decimal
Page 235
Wiring with Pico GFX-70
BCD code
Decimal value
0001
1
0010
2
0011
3
0100
4
0101
5
0110
6
0111
7
1000
8
1001
9
1010 to 1111
Not permissible
10000
10
10001
11
IMPORTANT
4-125
The BCD code only allows the number range 0hex to 9hex. The number range Ahex to Fhex cannot be represented. The NC function block converts the impermissible range to 9.
Inputs The function block input >I1 can be assigned the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block
Publication 1760-UM002B-EN-P - March 2005
Page 236
4-126
Wiring with Pico GFX-70
Actual Value …QV> The actual value …QV> can be assigned the following operands: • Markers MD, MW, MB • Analog output QA01
Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled
Coil NC01EN to NC32EN: enable coil.
Memory Requirement of the Numerical Converter The numerical converter function block requires 32 bytes of memory plus 4 bytes per constant on the function block input.
Function of the Numerical Converter Function Block
IMPORTANT
The numerical converter function block must be enabled so that it can work. Coil NC..EN is active. If coil NC..EN is not active, the entire function block is deactivated and reset. The output value is set to zero.
BCD Mode The BCD value at >I1 is provided in decimal format at the input. The binary value is formed from this. The binary value is interpreted as a BCD value. Values greater than 9 (1001) are set to the value 9. The BCD value is output as a decimal value at the output QV>. Example 1: Input value >I1: +9dec Binary value: 1001 Decimal value QV>: + 9 Example 2: Input value>I1: +14dec Binary value: 1110 Decimal value QV>: + 9
Publication 1760-UM002B-EN-P - March 2005
Page 237
Wiring with Pico GFX-70
IMPORTANT
4-127
The highest binary value represented in BCD is 1001 = 9. All other higher binary values from 1010 to 1111 are output as 9. This behavior is correct as BCD encoders do not normally generate these values.
Example 3: Input value>I1: 19dec Binary value: 00010011 Decimal value QV>: 13 Example 4: Input value>I1: 161061273dec Binary value: 1001100110011001100110011001 Decimal value QV>: 9999999 Example 5: Input value>I1: -61673dec Binary value: 10000000000000001111000011101001 Decimal value QV>: -9099
IMPORTANT
Bit 32 is the sign bit. Bit 32 = 1 →Sign = Minus.
Example 6: Input value>I1: 2147483647dec Binary value: 01111111111111111111111111111111 Decimal value QV>: 9999999
IMPORTANT
Values greater than 161061273 are output as 9999999. Values less than -161061273 are output as -9999999. The working range of the function block has been exceeded.
BIN Mode The decimal value is assigned to input >I1. The decimal value is represented as a BCD coded value. The BCD coded value is interpreted as a hexadecimal value and output as a decimal value at output QV>.
Publication 1760-UM002B-EN-P - March 2005
Page 238
4-128
Wiring with Pico GFX-70
Example 1: Input value >I1: +7dec BCD binary value: 0111 Hexadecimal value: 0111 Decimal value QV>: + 7 Example 2: Input value >I1: +11dec BCD binary value: 00010001 Hexadecimal value: 00010001 Decimal value QV>: +17 (1 + 16) Hexadecimal value: Bit 0 has the value 1. Bit 4 has the value 16 Total: Bit 0 plus Bit 4 = 17 Example 3: Input value >I1: 19dec BCD binary value: 00011001 Hexadecimal value: 00011001 Decimal value QV>: 25 (1 + 8 + 16) Example 4: Input value >I1: 9999999dec BCD binary value: 1001100110011001100110011001 Hexadecimal value: 1001100110011001100110011001 Decimal value QV>: 161061273 Example 5: Input value >I1:-61673dec BCD binary value: 10000000000001100001011001110011 Hexadecimal value: 10000000000001100001011001110011 Decimal value QV>: -398963
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
Bit 32 is the sign bit. Bit 32 = 1 →Sign = Minus.
Page 239
Wiring with Pico GFX-70
4-129
Example 6: Input value >I1: 2147483647dec BCD binary value: 01111111111111111111111111111111 Hexadecimal value: 01111111111111111111111111111111 Decimal value QV>: 161061273
IMPORTANT
Values greater than 9999999 are output as 161061273. Values less than -9 999999 are output as -161061273. The working range of the function block has been exceeded.
Operating Hours Counter Pico GFX-70 provides 4 independent operating hours counters. The counter states are retained even when the device is switched off. As long as the enable coil of the operating hours counter is active, Pico GFX-70 counts the hours in minute cycles. Figure 4.55 Pico GFX-70 circuit diagram with operating hours counter. I 10-----------------------------[ OT01EN M 42-----------------------------[ OT01RE OT01Q1---------------------------[ Q 01
OT04
+
Parameter display and parameter set for the operating hours counter function block:
>I1 QV>
OT04
Operating hours counter number 04
+
Appears in the parameter display
>I1
Upper threshold value in hours
QV>
Actual value of the operating hours counter
Contacts OT01Q1 to OT04Q1 The contact switches when the upper threshold value has been reached (greater than or equal to).
Coils • OT01EN to OT04EN: enable coil • OT01RE to OT04RE: reset coil Publication 1760-UM002B-EN-P - March 2005
Page 240
4-130
Wiring with Pico GFX-70
Memory Requirement of the Operating Hours Counter The operating hours counter function block requires 36 bytes of memory plus 4 bytes per constant on the function block input.
Function of the Operating Hours Counter Function Block If the enable coil OT..EN is triggered to the 1 state, the counter adds the value 1 to its actual value every minute (basic clock rate: 1 minute). If the actual value on QV> reaches the setpoint value of >I1, the contact OT..Q1 switches for as long as the actual value is greater than or equal to the setpoint value. The actual value is retained in the unit until the Reset coil OT..RE is actuated. The actual value is then set to zero.
IMPORTANT
Operating mode change RUN, STOP, Voltage On, Off, Delete program, Change program, Load new program. All these actions do not delete the actual value of the operating hours counter.
Accuracy The operating hours counter is accurate to the nearest minute. If the enable coil signal is terminated within a minute, the value for seconds is lost. The value range of the operating hours counter is between 0 hours and 100 years.
PUT, Send a Value onto the Network The function block allows you to selectively send a 32-bit value onto the network. The PUT function block provides data that another Pico-Link station indicates it requires via the GET function block. Figure 4.56 Pico GFX-70 circuit diagram with PUT function block T 01Q1---------------------------[ PT16T PT16Q1---------------------------[ C 01C