For the Allen-Bradley GFX-70 1760-DUB

Page 241

Wiring with Pico GFX-70

4-131

Parameter display and parameter set for the PUT function block: PT01 11

-

>I1

PT01

PUT function block (places a value onto the network), number 11

-

Does not appear in the parameter display

>I1

Setpoint value which is put onto the Pico-Link network

Input The function block input >I1 can be assigned the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block

Contacts PT01Q1 to PT32Q1: state of the trigger coil

Coils PT01T to PT32T: trigger coils

Memory Requirement of the PUT Function Block The PUT function block requires 36 bytes of memory plus 4 bytes per constant on the function block input.

PUT Diagnostics The PUT function block only functions when the Pico-Link network is functioning correctly (see Signs of Life of the Individual Stations and Diagnostics on page 6-12).

Publication 1760-UM002B-EN-P - March 2005

Page 242

4-132

Wiring with Pico GFX-70

Function of the PUT Function Block Figure 4.57 Signal diagram of PUT function block

1

2

3

1: trigger coil 2: trigger coil contact feedback 3: send

Pulse Width Modulation Pico GFX-70 provides 2 pulse width modulation function blocks PW01 and PW02. The function blocks are connected directly to the outputs. They are assigned as follows: PW01 →Q1 PW02 →Q2

IMPORTANT

When using the pulse width modulation function block with a minimum on time of less than 1 s only use devices with transistor outputs.

The pulse width modulation function block is primarily used for outputting the manipulated variable of a PID controller. The maximum frequency is 200 kHz. This corresponds to a period duration of 5 ms. The maximum period duration is 65.5 s.

Wiring a Pulse Width Modulation Function Block A pulse width modulation function block is integrated in the circuit diagram as a contact or coil.

IMPORTANT

Publication 1760-UM002B-EN-P - March 2005

To prevent unpredictable switching states, use each coil of a relay once only in the circuit diagram.

Page 243

Wiring with Pico GFX-70

4-133

Figure 4.58 Pico GFX-70 circuit diagram with pulse width modulation M 95---------------------------[ PW01EN PW01E1-------------------------[ M 96

Parameter Display and Parameter Set for Pulse Width Modulation PW02

+

>SV >PD >ME

PW02

Pulse width modulation function block number 02

+

Appears in the parameter display

>SV

Manipulated variable input

>PD

Period duration in ms

>ME

Minimum on duration, minimum off duration in ms

The parameter display for a timing relay is used to modify the period duration, the minimum on time and the enabling of the parameter display.

Value and Time Ranges

Parameter

Value and time range

Resolution

SV

0 to 4095

1 digit

PD

0 to 65535 m

ME

0 to 65535 ms

IMPORTANT

The minimum time setting for the period duration is: 0.005 s (5 ms)

Inputs The function block inputs >SV, >PD and >ME can be assigned the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12

Publication 1760-UM002B-EN-P - March 2005

Page 244

4-134

Wiring with Pico GFX-70

• Analog output QA01 • Actual value … QV> of another function block

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Contacts PW01E1 to PW02E1, the minimum on duration or the minimum off duration was undershot.

Coils PW01EN to PW02EN, enable coil.

Memory Requirement of the Function Block The pulse width modulation function block requires 48 bytes of memory plus 4 bytes per constant on the function block input.

Function of the Pulse Width Modulation Function Block

IMPORTANT

The pulse width modulation function block must be enabled so that it can work. Coil PW..EN is active. If coil PW..EN is not active, the entire function block is deactivated and reset. The output value is set to zero.

The manipulated variable at function block input >SV is converted to a pulse string with a constant period duration. The pulse width is proportional to the manipulated variable >SV. The period duration and the minimum on duration can be selected as required within the specified limits. The function block causes a direct output of the pulse to the corresponding output. The output image of the circuit diagram is always updated.

IMPORTANT

The following applies if the output of a pulse width modulator is used as a coil in the circuit diagram: The state of the output is not refreshed from the circuit diagram.

Publication 1760-UM002B-EN-P - March 2005

Page 245

Wiring with Pico GFX-70

IMPORTANT

4-135

The following applies to the minimum on duration: • The minimum on duration is the same as the minimum off duration. • The minimum on duration must not exceed 10% of the period duration. The ratio of period duration/minimum on duration (P/M) determines which percentage of the manipulated variable has no effect. The minimum on duration must be set as low as possible so that the P/M ratio is as high as possible. If the minimum on duration must not be too low, due to the output relay, the period duration must be increased accordingly. • The minimum on duration is 1 ms. • If the actual value of the pulse length is less than the minimum on duration, the minimum on duration has the effect of the pulse time. Note the state of the contact PW..E1. • If the off duration of the pulse is less than the minimum off duration, outputs Q1 and Q2 are continuously in operation. Note the state of the contact PW..E1.

Setting Date/Time This function block allows you to selectively place the date and time onto the network. All other stations accept the date and time of the sending station. The function block name is SC01 (send clock). Figure 4.59 Pico GFX-70 circuit diagram with SC function block HW01QW1---------------------------[ SC01T

Publication 1760-UM002B-EN-P - March 2005

Page 246

4-136

Wiring with Pico GFX-70

Parameter Display and Parameter Set for the SC Function Block The SC01 function block has no parameters as it is a triggered system service.

Coil SC01T: trigger coil

Memory Requirement of the SC Function Block The SC function block requires 20 bytes of memory.

SC Diagnostics The SC function block only functions when the Pico-Link network is functioning correctly (see Signs of Life of the Individual Stations and Diagnostics on page 6-12).

Function of the Date/Time Function Block If the trigger coil of the function block is activated, the current date, the day of the week and time from the sending station is automatically put onto the Pico-Link network. All other network stations must accept these values.

IMPORTANT

The station that sends its date and time does this when the seconds value is zero. Example: The trigger pulse is actuated at 03:32:21 (hh:mm:ss). The other stations are synchronized at 03:33:00. This time is accessed by all other stations.

This process can be repeated as often as desired. The trigger coil must be triggered again from the 0 to the 1 state.

Accuracy of Time Synchronization The maximum time deviation between the functional stations is 5 s.

Publication 1760-UM002B-EN-P - March 2005

Page 247

Wiring with Pico GFX-70

4-137

Set Cycle Time Pico GFX-70 provides one set cycle time function block ST01. The set cycle time function block is a supplementary function block for the PID controller. The set cycle time function block provides a fixed cycle time for processing the circuit diagram and the function blocks.

Wiring a Set Cycle Time Function Block The ST set cycle time function block is integrated in the circuit diagram as a coil.

IMPORTANT

To prevent unpredictable switching states, use each coil of a relay once only in the circuit diagram.

Figure 4.60 Pico GFX-70 circuit diagram with enabling of set cycle time function block. -------------------------------[ ST01EN

Parameter display for set cycle time: ST01

+

>I1

ST01

Set cycle time function block number 01

+

Appears in the parameter display

>I1

Set cycle time

The parameter display is used to modify the set cycle time, the minimum on time and the enabling of the parameter display. Table 4.61 Time Range Parameter

Value and time range

Resolution

I1

0 to 1000 ms

Inputs The function block input >I1 can be assigned the following operands: • Constants

Publication 1760-UM002B-EN-P - March 2005

Page 248

4-138

Wiring with Pico GFX-70

• Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Coils ST01EN, enable coil.

Memory Requirement of the Set Cycle Time Function Block The set cycle time function block requires 24 bytes of memory plus 4 bytes per constant on the function block input.

Function of the Set Cycle Time Function Block The function block is used to define a fixed cycle time.

IMPORTANT

The function block must be enabled so that it can work. Coil ST01EN is active. If coil ST01EN is not active, the entire function block is deactivated and reset.

Actual cycle time is less than the set cycle time:

If the maximum cycle time present is less than the set cycle time, the set cycle time is constant. Actual cycle time is greater than the set cycle time:

If the maximum cycle time present is greater than the set cycle time, the set cycle time has no effect.

Publication 1760-UM002B-EN-P - March 2005

Page 249

Wiring with Pico GFX-70

ATTENTION

4-139

The shorter the cycle time, the faster the control and regulation process. Set as small a value for the set cycle time as possible. The processing of the function blocks, reading of the inputs and writing of outputs is only carried out once every cycle. Exception: All function blocks that are processed irrespective of the controller.

Timing Relay Pico GFX-70 provides 32 timing relays from T 01 to T 32. A timing relay is used to change the switching duration and the make and break times of a switching contact. The delay times can be configured between 5 ms and 99 h 59 min.

Wiring a Timing Relay You integrate a timing relay into your circuit in the form of a contact and coil. The function of the relay is defined via the parameter display. The relay is started via the trigger coil T..EN and can be selectively reset via the reset coil T..RE. The actual timeout running can be stopped via the third coil T..ST.

IMPORTANT

To prevent unpredictable switching states, use each coil of a relay once only in the circuit diagram.

Figure 4.62 Pico GFX-70 circuit diagram with timing relay. I 01---------------------------[ T 02EN I 02---------------------------[ T 02RE T 02Q1-------------------------[ Q 01 I 03---------------------------[ T 02ST

Publication 1760-UM002B-EN-P - March 2005

Page 250

4-140

Wiring with Pico GFX-70

T 02 X

M:S +

>I1 >I2 QV>

Table 4.63 Parameter display and parameter set for timing relay T 02

Timing relay function block number 02

X

On-delayed mode

M:S

Time range Minute: Seconds

+

Appears in the parameter display

>I1

Time setpoint value 1

>I2

Time setpoint value I2 (on a timing relay with 2 setpoint values)

QV>

Timed-out actual time in RUN mode

The parameter display for a timing relay is used to modify the switching function, time base or setpoint times and enable the parameter display. Table 4.64 Timing Relay Modes Parameter

Switch function

X

On-delayed switching

?X

On-delayed with random time range

❚

Off-delayed switching

?❚

Off-delayed with random time range

X❚

On and off delayed Off-delayed with random time range, setpoint retriggerable

?

Off-delayed with random time range, retriggerable

?X❚

On and off delayed switching with random time, 2 time setpoints Single-pulse switching Switch with flashing, synchronous, 2 time setpoint values Switch with flashing, asynchronous, 2 time setpoint values

Publication 1760-UM002B-EN-P - March 2005