Page 251

Wiring with Pico GFX-70

4-141

Table 4.65 Time Range Parameter

Time range and setpoint time

Resolution

S 000.000

Seconds, 0.005 to 999.995s for constants and variable values

5 ms

M:S 00:00

Minutes: Seconds 00:00 to 99:59 only for constants 1 s and variable values

H:M 00:00

Hours: Minutes, 00:00 to 99:59 only for constants and variable values

IMPORTANT

1 min.

Minimum time setting: 0.005 s (5 ms). If a time value is less than the Pico GFX-70 cycle time, the elapsed time will only be recognized in the next cycle.

Inputs The function block inputs >I1 and >I2 can have the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block

Actual Value …QV> The actual value …QV> can be assigned the following operands: • Markers MD, MW, MB • Analog output QA01

Publication 1760-UM002B-EN-P - March 2005

Page 252

4-142

Wiring with Pico GFX-70

Variable Setpoint Values Behavior of the setpoint value when variable values are used. • Variable values can be used. • Variable values must be transferred using operands. • With the time base “s” the value is accepted as a “value in ms”. • The last position is rounded up to a zero or five. • With the time base “M:S” the value is accepted as a “value in s”. • With the time base “H:M:” the value is accepted as a “value in M (minutes)”.

IMPORTANT

The delay times are the same as described for the constants.

Example:

Time base “s” The operand has the value 9504. The time value is 9.50s. The Operand value is 45507. The time value is 45.510s. Time base "M:S" The operand has the value 5999. The time value is 99 min, 59s. This is the maximum value. Time base "H:M" The operand has the value 5999. The time value is 99 hours, 59 min.

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Contacts T 01Q1 to T 32Q1

Coils • T 01EN to T 32EN: trigger coil; • T 01RE to T 32RE: reset coil; • T 01ST to T 32ST: stop coil.

Publication 1760-UM002B-EN-P - March 2005

Page 253

Wiring with Pico GFX-70

4-143

Memory Requirement of the Timing Relay The time relay function block requires 48 bytes of memory plus 4 bytes per constant on the function block input.

Retention Timing relays can be operated with retentive actual values. The number of retentive timing relays can be selected in the SYSTEM →RETENTION menu. If a timing relay is retentive, the actual value is retained when the operating mode changes from RUN to STOP as well as when the power supply is switched off. If Pico GFX-70 is started in RUN mode, the timing relay operates with the retentively saved actual value. The state of the trigger pulse must correspond to the function of the timing relay. 1 signal when: • on-delayed, • single pulse, • flashing. 0 status for off delayed.

Function of the Timing Relay Function Block Timing relay, on-delayed with and without random switching

Random switching The contact of the timing relay switches randomly within the setpoint value range.

Publication 1760-UM002B-EN-P - March 2005

Page 254

4-144

Wiring with Pico GFX-70

Figure 4.66 Signal diagram of timing relay, on-delayed (with and without random switching)

1

2

3

4 t ts A

B t1 + t 2 = t s C

1: trigger coil T..EN 2: stop coil T..ST 3: reset coil T..RE 4: switching contact (make contact) T..Q1 ts: setpoint time • Range A: The set time elapses normally. • Range B: The entered setpoint does not elapse normally because the trigger coil drops out prematurely. • Range C: The Stop coil stops the time from elapsing.

Publication 1760-UM002B-EN-P - March 2005

Page 255

Wiring with Pico GFX-70

4-145

Figure 4.67 Signal diagram of timing relay, on-delayed (with and without random switching)

1

2

3

4 ts tF ts D

E ts F

• Range D: The Stop coil is inoperative after the time has elapsed. • Range E: The Reset coil resets the relay and the contact. • Range F: The Reset coil resets the time during the timeout sequence. After the Reset coil drops out, the time elapses normally.

Timing relay, off-delayed with and without random switching

Random switching, with and without retriggering: The contact of the timing relay randomly switches within the set value range. Retriggering: When the time is running and the trigger coil is reactivated or deactivated, the actual value is reset to zero. The set time of the timing relay is timed out once more.

Publication 1760-UM002B-EN-P - March 2005

Page 256

4-146

Wiring with Pico GFX-70

Figure 4.68 Signal diagram of timing relay, off-delayed (with/without random switching with/without retriggering)

1

2

3

4

A ts t1 + t 2 = t s B

C ts t D

1: trigger coil T..EN 2: stop coil T..ST 3: reset coil T..RE 4: switching contact (make contact) T..Q1 ts: setpoint time • Range A: The time elapses after the trigger coil is deactivated. • Range B: The Stop coil stops the time from elapsing. • Range C: The Reset coil resets the relay and the contact. After the Reset coil drops out, the relay continues to work normally. • Range D: The Reset coil resets the relay and the contact when the function block is timing out.

Publication 1760-UM002B-EN-P - March 2005

Page 257

Wiring with Pico GFX-70

4-147

Figure 4.69 Signal diagram of timing relay, off-delayed (with/without random switching with/without retriggering)

1

2

3

4 t1 + t 2 = t s E t1 F ts

• Range E: The Trigger coil drops out twice. The set time ts consists of t1 plus t2 (switch function not retriggerable). • Range F: The Trigger coil drops out twice. The actual time t1 is cleared and the set time ts elapses completely (retriggerable switch function).

Timing relay, on-delayed and off-delayed with and without random switching

Time value >I1: On-delayed time Time value >I2: Off-delayed time Random switching: The contact of the timing relay switches randomly within the setpoint value range.

Publication 1760-UM002B-EN-P - March 2005

Page 258

4-148

Wiring with Pico GFX-70

Figure 4.70 Signal diagram of timing relay, on and off-delayed 1

1

2

3

4 ts1

A ts2 t B t1 + t2 = ts1 ts2 C ts1

D ts2

1: trigger coil T..EN 2: stop coil T..ST 3: reset coil T..RE 4: switching contact (make contact) T..Q1 ts1: pick-up time ts2: drop-out time • Range A: The relay processes the two times without any interruption. • Range B: The trigger coil drops out before the on-delay is reached. • Range C: The Stop coil stops the timeout of the on-delay. • Range D: The stop coil has no effect in this range.

Publication 1760-UM002B-EN-P - March 2005

Page 259

Wiring with Pico GFX-70

4-149

Figure 4.71 Signal diagram of timing relay, on and off-delayed 2

1

2

3

4 ts1 t1 + t2 = ts2 E ts1 t F ts1 G ts2

• Range E: The Stop coil stops the timeout of the off-delay. • Range F: The Reset coil resets the relay after the on delay has elapsed • Range G: The Reset coil resets the relay and the contact whilst the on delay is timing out. After the Reset coil drops out, the time elapses normally.

Figure 4.72 Signal diagram of timing relay, on and off-delayed 3

1

2

3

4 ts1 t H

• Range H: The Reset signal interrupts the timing out of the set time.

Publication 1760-UM002B-EN-P - March 2005

Page 260

4-150

Wiring with Pico GFX-70

Timing Relay, Single Pulse

1

2

3

4 ts A ts B t1 + t 2 = t s C

Figure 4.73 Signal diagram of timing relay, single pulse 1 1: trigger coil T..EN 2: stop coil T..ST 3: reset coil T..RE 4: switching contact (make contact) T..Q1 • Range A: The trigger signal is short and is lengthened • Range B: The Trigger signal is longer than the set time. • Range C: The Stop coil interrupts the timing out of the set time.

Publication 1760-UM002B-EN-P - March 2005