Pico GFX-70 Controllers User Manual: 4 - Wiring with Pico GFX-70, pages 261 to 268

Pages 261 to 268 of 400, from Pico GFX-70 Controllers User Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley GFX-70 1760-DUB

Page 261

Wiring with Pico GFX-70

4-151

Figure 4.74 Signal diagram of timing relay, single pulse 2

1

2

3

4 t t ts

D

E

• Range D: The Reset coil resets the timing relay. • Range E: The Reset coil resets the timing relay. The Trigger coil is still activated after the Reset coil has been deactivated and the time is still running.

Timing Relay, Synchronous and Asynchronous Flashing Time value >I1: Pulse time Time value >I2: Pause time Synchronous (symmetrical) flashing: >I1 equal >I2 Asynchronous flashing: >I1 not equal >I2 Figure 4.75 Signal diagram of timing relay, synchronous and asynchronous flashing

1

2

3

4 ts1 ts2 ts1 ts2 ts1

A t ts2 ts1 ts2 ts1 t1 + B t2 = ts2 ts1 ts2 C

1: trigger coil T..EN

Publication 1760-UM002B-EN-P - March 2005

Page 262

4-152

Wiring with Pico GFX-70

2: stop coil T..ST 3: reset coil T..RE 4: switching contact (make contact) T..Q1 • Range A: The relay flashes for as long as the Trigger coil is activated. • Range B: The Stop coil interrupts the timing out of the set time. • Range C: The Reset coil resets the relay.

Value Limitation Pico GFX-70 provides 32 value limitation function blocks VC01 to VC32. The value limitation function block allows you to limit values. You can define an upper and lower limit value. The function block will then only output values within these limits.

Wiring of a Value Limitation Function Block You can integrate a value limitation function block into your circuit as a coil. Figure 4.76 Pico GFX-70 circuit diagram with VC value limitation M 48----------------------------[ VC27EN

VC27

+

>I1 >SH >SL QV>

Publication 1760-UM002B-EN-P - March 2005

Table 4.77 Parameter display and parameter set for the VC function block VC27

VC value limitation function block number 27

+

Appears in the parameter display

>I1

Input value

>SH

Upper limit value

>SL

Lower limit value

QV>

Output value limited

Page 263

Wiring with Pico GFX-70

4-153

Inputs The function block inputs >I1, >SH and >SL can be assigned the following operands: • Constants • Markers MD, MW, MB • Analog inputs IA01 to IA04 – IA01: terminal I7 – IA02: terminal I8 – IA03: terminal I11 – IA04: terminal I12 • Analog output QA01 • Actual value … QV> of another function block

Output The function block output QV> can be assigned the following operands: • Markers MD, MW, MB • Analog output QA01

Value Range for Inputs and Outputs

Value range >I1

Input value

>SH

Upper limit value

>SL

Lower limit value

QV>

Output value

-2147483648 to +2147483647

Displaying the Parameter Set in the PARAMETERS Menu • + Access enabled • - Access disabled

Coil VC01EN to VC32EN, function block enable

Publication 1760-UM002B-EN-P - March 2005

Page 264

4-154

Wiring with Pico GFX-70

Memory Requirement of the Value Limitation Function Block The value limitation function block requires 40 bytes of memory plus 4 bytes per constant on the function block input.

Function of the Value Limitation Function Block

The function block must be enabled so that it can work. Coil VC..EN is active. If coil VC..EN is not active, the entire function block is deactivated and reset. The output value is set to zero.

IMPORTANT

The value is accepted at input VC...I1 if the enable coil is active. If the value is greater than the upper limit value or less than the lower limit value, the respective limit value is output at VC..QV.

Example with Timing Relay and Counter Function Block A warning light flashes when the counter reaches 10. In the example, both function blocks C 01 and T 01 are wired. Figure 4.78 Hardwiring with relays L01+

P1

S2

S1

C

K1T

R

P1

H1

K1T

L01– Counter Value 10

Publication 1760-UM002B-EN-P - March 2005

2s

Page 265

Wiring with Pico GFX-70

4-155

Figure 4.79 Wiring with the Pico GFX-70 L01+ L01–

F1

S1

+24V 0V 0V

S2

I1 I2 I3

I 01----I 02-

--Ä Q 01

ALT

DEL OK ESC

1

Q1

*

2

H1 L01–

Figure 4.80 Pico GFX-70 wiring and circuit diagram I 05---------------------------[ C 01C I 06---------------------------[ C 01RE C 01---------------------------[ T 01EN T 01Q1-------------------------[ Q 01

Entering function block parameters from the circuit diagram. You can access the parameter entry from the contact as well as from a coil. 1. Enter the circuit diagram up to C 01 as a coil.

Publication 1760-UM002B-EN-P - March 2005

Page 266

4-156

Wiring with Pico GFX-70

C 01C is the counter coil of the counter 01 function block.

Figure 4.81 Pico GFX-70 wiring and circuit diagram I 05---------------------------[ C 01C I 06---------------------------[ C 01RE C 01---------------------------[ T 01EN T 01Q1-------------------------[ Q 01

2. Keep the cursor on the number. 3. Press the OK button.

IMPORTANT

If the cursor is on the contact number, Pico GFX-70 will call up the parameter display when you press OK.

The first part of the parameter set of a counter is displayed. C 01

+

>SH +10 >SL >SV

4. Move the cursor down over the + character to the value input behind >SH: – >SH means: function block input upper counter setpoint value – The + character means that the parameters of this timing relay can be modified using the PARAMETERS menu. 5. Change the upper counter setpoint to 10: – Use the left and right arrow buttons to move the cursor onto the tens digit. – Use the up and down arrow buttons to modify the value of the digit. 6. Press OK to save the value and ESC to return to the circuit diagram.

IMPORTANT

Pico GFX-70 has specific parameter displays for the function blocks. The meaning of these parameters is explained under each function block type.

7. Enter the circuit diagram up to contact T 01 of the timing relay. Set the parameters for T 01.

Publication 1760-UM002B-EN-P - March 2005

Page 267

Wiring with Pico GFX-70

T 01 Ü

S

+

>I1 002.000

4-157

The timing relay works like a flashing relay. The Pico GFX-70 symbol for the flashing relay is . The function is set on the top right beside the number in the parameter display.

>I2 002.000

The time base is set to the right of the “flashing” function. Leave the time base set to S for seconds.

QV>

8. Move the cursor to the right over the + character to input the time setpoint value >I1. If the same setpoint value is input for >I1 and >I2, the timing relay functions as a synchronous flasher. The + character means that the parameters of this timing relay can be modified using the PARAMETERS menu. 9. Confirm the value input with OK. 10. Press ESC to leave circuit diagram entry. 11. Complete the circuit diagram. 12. Test the circuit diagram using the power flow display. 13. Switch Pico GFX-70 to RUN mode and return to the circuit diagram. Each parameter set can be displayed using the power flow display for the circuit diagram.

C 01

+

14. Move the cursor onto C 01 and press OK. The parameter set for the counter is displayed with actual and setpoint values.

>SL

15. Move the cursor downwards until you see the value QV>.

>SV QV>+0

16. Switch the input I5. The actual value changes. C 01 >SL

+

On the display C_ indicates that the counting coil is actuated.

>SV QV>+1 .. C_ .. ..

If the actual and upper setpoint values of the counter are the same, the timing relay switches the warning light on and off every 2 seconds.

Publication 1760-UM002B-EN-P - March 2005

Page 268

4-158

Wiring with Pico GFX-70

Doubling the flashing frequency: T 01 Ü

S

+

>I1 001.000 >I2

1. Select the power flow display T 01 and change the constant of the setpoint time to 001.000.

QV> 0.550 .. EN..

When you press OK, the warning light will flash at twice the frequency. On the display EN indicates that the enable coil is actuated. Setpoint value settings with constants can be modified via the PARAMETERS menu.

IMPORTANT

Publication 1760-UM002B-EN-P - March 2005

The actual value is only displayed in RUN mode. Call up the parameter display for this via the power flow display or PARAMETERS menu.