Page 307
Chapter
6
Pico-Link and Point-to-Point Serial Connections
Introduction to Pico-Link
All Pico GFX-70 units have Pico-Link terminals. The Pico-Link is designed for eight stations. Using the Pico-Link you can: • Process additional inputs and outputs. • Implement faster and improved control using decentralized programs. • Synchronize date and time • Read and write inputs and outputs. • Send values to other stations. • Receive values from other stations. • Load programs from or to any station. The Pico-Link is based on the CAN network (Controller Area Network). CAN is specified by the ISO 11898 standard. CAN has the following in-built features: • Message oriented transmission protocol. • Multimaster bus access capabilities with non-destructive bit-wise bus arbitration via priority messaging (Arbitration: An instance which defines which hardware can use the bus next). • Multicast broadcast messaging with receiver side message filtering. • High level of real-time capability (short reaction time for high priority messages, short fault message get times). • Functionality in environments with severe interference (short block lengths). • High level of error security.
1
Publication 1760-UM002B-EN-P - March 2005
Page 308
6-2
Pico-Link and Point-to-Point Serial Connections
IMPORTANT
Pico-Link Topologies, Addressing and Functions
CAN has been used as the basis for the design of the Pico-Link. The messages have been adapted and optimized to suit the requirements of the Pico GFX-70 environment.
The Pico-Link allows the configuration of a line topology. There are two wiring methods which can be used for the required addressing options: • “Loop through the unit” wiring arrangement, • Wiring arrangement using a T connector and a spur line.
Loop Through the Unit Wiring Method With this wiring method it is possible to implement the addressing of the stations via station 1 or the PicoSoft Pro. If the line is interrupted, the network is no longer operational from this point in the network.
T-Connector and Spur Line Each device must be addressed individually with this wiring method by: • Downloading the program • Downloading the address with PicoSoft Pro • Using the display or • The device is already assigned an address. If a spur line is removed on a station, all other devices in the network remain functional.
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
The spur line between the T connector and the device must not exceed 0.3 m. Otherwise communication via the Pico-Link may be impaired.
Page 309
Pico-Link and Point-to-Point Serial Connections
6-3
Topology and Addressing Examples
Physical location, place
Station number
Loop through the unit
Example 1
Example 2
1
1
1 Pico GFX
2
2
3
4
5
6
7
7
8
8
Pico GFX
7 Pico GFX
6
Pico GFX
8 Pico GFX
5
Pico GFX
4 Pico GFX
4
Pico GFX
3 Pico GFX
3
T connector and spur line
2
6
5
Pico GFX Pico GFX Pico GFX
Pico GFX Pico GFX Pico GFX Pico GFX
• Example 1: physical location is the same as the station number • Example 2: physical location is not the same as the station number (apart from location 1 being the same as station 1).
IMPORTANT
Physical location 1 is always assigned as station 1. Station 1 is the only station which must be present.
Publication 1760-UM002B-EN-P - March 2005
Page 310
6-4
Pico-Link and Point-to-Point Serial Connections
Position and Addressing of the Operands via the Pico-Link
Stations
Basic unit
Local expansion
Network bit data
Network word data
Input
Output
Input
Output
Input
Output
I
Q
R
S
RN
SN
1
1 I 1 to 16
1 Q 1 to 8
1 R 1 to 16 1 S 1 to 8
2 to 8 RN 1 to 32
2 to 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
2
2 I 1 to 16
2 Q 1 to 8
2 R 1 to 16 2 S 1 to 8
1, 3 to 8 RN 1 to 32
1, 3 to 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
3
3 I 1 to 16
3 Q 1 to 8
3 R 1 to 16 3 S 1 to 8
1, 2, 4 to 8 RN 1 to 32
1, 2, 4 to 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
4
4 I 1 to 16
4 Q 1 to 8
4 R 1 to 16 4 S 1 to 8
1 to 3, 5 to 8 RN 1 to 32
1 to 3, 5 to 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
5
5 I 1 to 16
5 Q 1 to 8
5 R 1 to 16 5 S 1 to 8
1 to 4, 6 to 8 RN 1 to 32
1 to 4, 6 to 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
6
6 I 1 to 16
6 Q 1 to 8
6 R 1 to 16 6 S 1 to 8
1 to 5, 7, 8 RN 1 to 32
1 to 5, 7, 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
7
7 I 1 to 16
7 Q 1 to 8
7 R 1 to 16 7 S 1 to 8
1 to 6, 8 RN 1 to 32
1 to 6, 8 SN 1 to 32
GT 1 to 32 PT 1 to 32
8
8 I 1 to 16
8 Q 1 to 8
8 R 1 to 16 8 S 1 to 8
1 to 7 RN 1 to 32
1 to 7 SN 1 to 32
GT 1 to 32 PT 1 to 32
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
Receive
Send
The RN-SN connection is a point-to-point connection between the stations indicated. With RN and SN the number of the contact must have the same number as the coil. Example: 2SN30 from station 8 is sent to 8RN30 of station 2.
Page 311
Pico-Link and Point-to-Point Serial Connections
IMPORTANT
6-5
Every station with a circuit diagram has read access to the physical station inputs and outputs of other stations and can process them locally.
Example 1 Station 1 is to read the input I1 of station 2 and write to output Q1 of station 2. Station 2 does not have a circuit diagram. Figure 6.1 Circuit diagram in station 1 2I 01-----------------------------[2Q 01
Example 2: Marker M 01 of station 4 is to switch the output Q1 of station 3 via the network. Both stations have a circuit diagram. Figure 6.2 Circuit diagram in station 4: Set coil 01 in station 3 M 01-----------------------------[3SN 01
Figure 6.3 Circuit diagram in station 3: Get value from coil 01 in station 4 4RN 01-----------------------------[ Q 01
Publication 1760-UM002B-EN-P - March 2005
Page 312
6-6
Pico-Link and Point-to-Point Serial Connections
Functions of the Stations in the Network The stations on the Pico-Link can have two different functions: • Intelligent stations with their own programs (stations 1 to 8) • Input/output devices (REMOTE IO) without their own program (stations 2 to 8)
IMPORTANT
Station 1 must always have a circuit diagram.
Possible Write and Read Authorization in the Network The stations have differing read and write authorization on the Pico-Link according to their functions and configuration.
Station 1 Authorized read access to all inputs and outputs of all stations regardless of the function. Observe the setting of SEND IO. See Send Each Change on the Inputs/Outputs (SEND IO) on page 6-9. Authorized write access to the station's own local outputs. Authorized write access to the physical digital outputs of the stations which are functioning as input/output devices. Write authorization to the network bit data 2 to 8 SN 1 to 32.
Stations 2 to 8 Input/output device function
No read and write authorization. Intelligent station function
Authorized read access to all inputs and outputs of all stations regardless of the function. Observe the setting of SEND IO. See Send Each Change on the Inputs/Outputs (SEND IO) on page 6-9. Write authorization to its own local outputs. Write authorization to the network bit data SN 1 to 32.
Publication 1760-UM002B-EN-P - March 2005
Page 313
Pico-Link and Point-to-Point Serial Connections
Configuring the Pico-Link
6-7
The Pico-Link can be configured so that it can be optimized for your application.
Station Number The station number is identified as the Pico-Link ID in the device. The station number can be set on devices with a display using the buttons on the Pico GFX-70.
IMPORTANT
All the Pico-Link settings are best carried out on station 1. The entire network can be configured via station 1. The configuration should only be carried out locally when a device is replaced.
Valid station numbers for operation are 01 to 08. Station number 00 = factory default setting With station number 00, double address assignment cannot occur when an existing device is being exchanged.
Transmission Speed The Pico GFX-70 device hardware allows you set transmission speeds between 10 and 1000 kBaud in specific stages. The length of all cables is determines the maximum permissible data transfer rate (see General on page A-1). The data transfer rate is set under the BAUDRATE: menu item. Possible baud rates are: 10, 20, 50, 125, 250, 500 and 1000 KB 125 KB = factory default setting
Publication 1760-UM002B-EN-P - March 2005
Page 314
6-8
Pico-Link and Point-to-Point Serial Connections
Pause Time, Changing the Write Repetition Rate Manually Every Pico-Link segment automatically determines the number of active stations, the baud rate, and the total number of bytes which are transmitted. The minimum pause time which a device requires is automatically determined using this data to ensure that all devices can send their messages. If a pause time is to be increased, the value of the BUSDELAY: must be set greater than zero. Value “1” doubles the pause time, value “15” will increase it by a factor of 16. tpnew = tp x (1 + n) tpnew = new pause time tp = pause time determined by the network n = value on BUSDELAY
IMPORTANT
An increase in the pause time means that fewer messages (inputs, outputs, bit data, word data) are transferred per time unit. The reaction speed of the entire controller depends on the baud rate, the pause time and the quantity of transferred data. The smaller the amount of data transferred, the faster the reaction times of the system.
IMPORTANT
Publication 1760-UM002B-EN-P - March 2005
An increase in the pause time is only useful during commissioning. To ensure that the data for the power flow display is updated faster in the PC, a longer range for this data is created on the network within this pause time.