Visualization with Pico GFX-70
5-31
Associated variable tab - On the Associated variable tab you define the variable with the value for activating the output text. Message texts tab - Assign in the Message texts tab the value of the associated variable for its corresponding message text, and select the language and the default text. Visibility tab - The Visibility tab enables you to make the screen element invisible via an associated variable. Display change tab - The Display change tab offers the following display forms of the message, which can be controlled with an associated variable: • flashing • Inverted Message Text Example Program 1 – Activating Message Texts with a Boolean Variable
The program consists of seven screens that can be selected using the up and down cursor buttons. The screen change was defined in the Button editor (see Button Editor on page 5-37). The circuit diagram uses six on-delayed timing relays that activate outputs Q1 to Q4 and LED03 in succession after an elapsed time. This operation is run in a continuous loop since timing relay T06 resets all timing relays after a set time. The message texts are controlled in all screens by means of Boolean variables. As these only have two states (0/1), only two different messages can be output via each message text element. If other variable types are used, the number of possible message texts can be increased accordingly. Standard path: C:\Program Files\PicoSoft 6 Pro\samples\ Program: Visibility_Display change_manual screen change.e60 Screen 1 - Screen 1 illustrates the activation of message texts by means of the associated variable. The output of two different texts in one message text element is also illustrated. The first screen contains four message text elements. These are activated via the outputs Q1 to Q4 and appear in the display. The Message text tab is used to assign the message to be output with a particular state of the associated variable. In this example, if Q1 = 0, the message “no data” is output, and “Information” is output if Q1 = 1. All other message text elements have only one message text which is displayed when the corresponding output Q.. = 1.
Publication 1760-UM002B-EN-P - March 2005
Page 300
5-32
Visualization with Pico GFX-70
Figure 5.33 Text display using Boolean operands Q1 = 0 no data
Screen 2/Text 1
Text 2
Q1, Q2, Q3 = 1
Information with Boolean operands!
Screen 2: - Screen 2 illustrates the activation of message texts by means of the associated variable. A message text is also enlarged in the display. The screen contains two message text elements. These are activated via the outputs Q1 and Q3 and appear in the display. The texts are only displayed if the corresponding outputs are 1. No message is assigned to output status 0. Screen 3 - Screen 3 illustrates the control of an enlarged message text element containing two message texts that are assigned to the two states of output Q2. Q2 = 0 a Message text: Q2 OFF Q2 = 1 a Message text: Q2 ON Figure 5.34 Message texts using an associated variable
Q2 OFF
Q2
ON
Screen 4 - Screen 4 is basically the same as screen 3 except that it also includes the Visibility element. The message text can be made invisible via input I1. The setting for this was made in the Visibility tab. Make contact bit logic is selected. With break contact bit logic, the message text element is made visible when actuating I1. Figure 5.35 Hiding a message text I1 not actuated
I1 actuated invisible via I1
Invisible via I1
Q2 ON Screen 5 - Screen 5 is basically the same as screen 4 except that the Invisible function has been replaced with Flash as the Display change function. When input I2 = 1 (make contact bit logic), the message text can be made to flash. Figure 5.36 Message text flashing I2 not actuated
I2 actuated flashing via I2!
flashing via I2!
Q2 ON Publication 1760-UM002B-EN-P - March 2005
Q2 OFF
Page 301
Visualization with Pico GFX-70
5-33
Screen 6 - Screen 6 is basically the same as screen 5 except that Inverted was selected for the Display change function. When input I2 = 1 (make contact bit logic), the message text in this screen can thus be inverted. Figure 5.37 Message text inverted I2 not actuated
I2 actuated invert via I2!
invert via I2!
Q2 ON
Q2 OFF
Screen 7 - Screen 7 is basically the same as screen 6 except that the inverted display is controlled by timing relay T07 (asynchronous clock pulse). The text flashes in the display at different pulse and pause times. Figure 5.38 Message text inverted flashing flashing via timer flashing via timer
Q2 ON
Q2 ON
Message Text Example Program 2 – Activating Message Texts with a Timing Relay
The program consists of two screens containing message texts. The screens are activated automatically in succession in the display. The circuit diagram uses six on-delayed timing relays T01 to T06 that activate outputs Q1 to Q4 and LE03 in succession after an elapsed time. This operation is run in a continuous loop since timing relay T06 resets all timing relays after a set time. The screen activation is executed via counter C01. This has the value 1 as the upper setpoint SH. The counter values 0 and 1 are therefore used as activation values for the two screens. The resetting of timing relays T01 to T06 by T06 activates counter C01 which then reaches the value 1 and therefore has already reached its upper setpoint. This then causes screen 2 to be displayed. The on-delayed timing relay T08 resets counter C01 back to 0 after the set time (0.8 s) has elapsed. Screen 1 is then displayed again and timing relay T08 is no longer activated. This loop is repeated continuously. Standard path: C:\Program Files\PicoSoft 6 Pro\samples\ Program: Message text_manual screen change.e60 Start Machine 1 Start Machine 2 Start Machine 3 Start Machine 4
RESTART
Screen 1 - The first screen contains four message text elements. These are activated in succession via the outputs Q1 to Q4 and appear in the display.
Screen 2 - The second screen contains one message text element with one message text.
Publication 1760-UM002B-EN-P - March 2005
Page 302
5-34
Visualization with Pico GFX-70
Message Text Example Program 3 – Message Text with a Display Change
The program consists of two screens containing message texts. The screens are activated automatically in succession in the display. This program is an extension of the program Message text_manual screen change.e60. The extension consists of two messages being contained in one message text element in screen 2, which are also toggled automatically. A display change is also executed in one message text. The circuit diagram uses six on-delayed timing relays T01 to T06, that activate outputs Q1 to Q4 and LE03 in succession after an elapsed time. This operation is run in a continuous loop since timing relay T06 resets all timing relays after a set time. The make contacts (C01ZE) of the counter in the circuit diagram are switched directly before the outputs Q1 to Q4 as well as before LE 3. The outputs are only meant to be active with screen 1, i.e. when the counter has the value 0. The screens are activated via counter C01. This has the value 2 as the upper setpoint SH, thus providing the counter values 0, 1 and 2. Counter value 0 activates screen 1, counter value 1 activates the first message text in screen 2 and counter value 2 the second message text in screen 2. When the timing relays T01 to T06 are reset, the counter receives a pulse and is incremented by one value. If the counter C01 reaches its upper setpoint with the second pass, this starts the on-delayed timing relay T08. This then resets the counter C01 to 0 after the set time has elapsed (0.8 s). This loop is repeated continuously. Standard path: C:\Program Files\PicoSoft 6 Pro\samples\ Program: Two messages in screen_automatic screen change.e60 Start Machine 1 Start Machine 2 Start Machine 3 Start Machine 4
Screen 1 - The first screen contains four message text elements. These are activated in succession via the outputs Q1 to Q4 and appear in the display. Screen 2 - The second screen contains a message text element with two message texts. The message texts are activated via counter values 1 and 2. The first resetting of timing relays T01 to T06 by T06 also activates counter C01 which then reaches the value 1. The Error message text is then displayed. This flashes since Flashing was set on the Display change tab and with function block parameter FB (counter value <= 1). RESTART is displayed if the counter value of C01 is 2. Figure 5.39 Message text as status display
Error
Publication 1760-UM002B-EN-P - March 2005
RESTART
Page 303
Visualization with Pico GFX-70
5-35
Message Text Example Program 4 – Activating Message Texts with a Default Text
The program consists of two screens containing message texts. The screens are activated automatically in succession in the display. This program is an extension of the program Two messages in screen_automatic screen change.e60. The extension consists of the display of a default text in screen 2 when the counter takes on values that are not assigned to any messages. The circuit diagram uses six on-delayed timing relays T01 to T06 that activate outputs Q1 to Q4 and LE03 in succession after an elapsed time. This operation is run in a continuous loop since timing relay T06 resets all timing relays after a set time. Counter make contacts (C01ZE) in the circuit diagram are switched directly before outputs Q1 to Q4 and LE03 so that the outputs are only active if screen 1 is active when counter C01 has the value 0. The screen activation is executed via counter C01. This has the value 4 as the upper setpoint SH. This therefore generates the counter values 0, 1, 2, 3 and 4. The counter is activated with every reset of timing relays T01 to T06. The counter value 0 activates screen 1 and counter value 1 screen 2. Screen 2 remains activated when the counter value is 2, 3 or 4, and counter value 2 and 3 cause the default text to be displayed as there are no message text assigned to these values. The counter value 4 causes the message text RESTART to be displayed in screen 2. If the counter C01 reaches its upper setpoint with this value, this starts the on-delayed timing relay T08. This then resets the counter C01 to 0 after the set time of 0.8 s has elapsed. This loop is repeated continuously. Standard path: C:\Program Files\PicoSoft 6 Pro\samples\ Program: Two messages in screen_automatic screen change+default.e60 Start Machine 1 Start Machine 2 Start Machine 3 Start Machine 4
Screen 1 - The first screen contains four message text elements. These are activated in succession via the outputs Q1 to Q4 and appear in the display. Screen 2 - The second screen contains a message text element with two message texts. The message texts are activated via counter values 1 and 4. A default text “default” has also been defined. • Status value 1. “Error” message text • Status value 2 and 3: “default” as default text • Status value 4. “RESTART” message text If the status value of C01 is 1, the message “error” flashes as the function block parameter FB has been set in the Display change area in the Display change tab. The function block parameter switches if the SL value (lower switch threshold) of the counter is reached (refer to PicoSoft Pro function block editor, counter C01).
Publication 1760-UM002B-EN-P - March 2005
Page 304
5-36
Visualization with Pico GFX-70
Figure 5.40 Message text with default text
Error default: RESTART
Message Text Example Program 5 – Several Message Texts in One Text Element The program consists of three screens that you can select via the up and down cursor buttons. The screen change was defined in the Button editor (see Button Editor on page 5-37). The purpose of this program is to display several messages in one message text element. The Visibility and Display change tabs are also covered. The clock pulse T01 activates counter C01. This counts up to 7 and then resets itself automatically. This therefore produces a continuous loop that activates the individual messages.
Standard path: C:\Program Files\PicoSoft 6 Pro\samples\ Program: Six messages in one Message text module_manual screen change.e60 Screen 1 - The first screen contains a message text element with six message texts. • Status value 1: Message text “These” • Status value 2: Message text “are six” • Status value 3: Message text “message texts” • Status value 4: Message text “in one” • Status value 5: Message text “message text” • Status value 6: Message text “element!!!”. It can be seen that the messages can be moved within the entry field. Screen 2 - Screen 2 is almost the same as screen 1 apart from one addition which enables the message text element to be made invisible via I1 (make contact bit logic). The use of the break contact bit logic would make the element visible. Figure 5.41 Make message text invisible
Publication 1760-UM002B-EN-P - March 2005
I1 not actuated
I1 actuated
Invisible via I1! Message texts
Invisible via I1!
Page 305
Visualization with Pico GFX-70
5-37
Screen 3 - Screen 3 is almost the same as screen 1 apart from one addition, by which the actuation of I1 causes the first message text element to flash and the second message text element to be inverted. Figure 5.42 Making message text flash or inverted Display change via I1! Message texts Message texts
Button Editor
Display change via I1! are six are six
All buttons of the Pico GFX-70 can be assigned in the button editor of the PicoSoft Pro with appropriate functions which overwrite the basic button functions. Carry out the following steps to associate the buttons of the Pico GFX-70: • Select an Operable Screen Element • Display Backlight • Screen Change • Password Logout • Set Variable to Fixed Value • Increment Variable • Decrement Variable • Changeover Relay
Select an Operable Screen Element If a screen with a value entry is present, you can jump to these value entry elements directly. The value entry element is in Entry mode so that you can change the value directly.
Display Backlight The brightness of the display backlight can be adjusted in stages.
Screen Change This function enables the operator to change to other saved screens during operation. If the operator is to be able to move between several screens using a
Publication 1760-UM002B-EN-P - March 2005
Page 306
5-38
Visualization with Pico GFX-70 button function you must assign a screen change button element to an operator button in each of these screens.
Password Logout The Screen overview contains the Passwords tab for defining a logout time. This logout time is skipped with the Password logout function.
Set Variable to Fixed Value This function assigns a fixed value to the selected variable, such as for resetting to a defined value.
Increment Variable The variable value is increased by the set step width.
Decrement Variable The variable value is decreased by the set step width.
Changeover Relay The state of a variable or a function block input is negated.