Page 338
7-10
Pico GFX-70 Settings
3. Select the required function block using the up/down arrow keys. T 03
S
+
>I1 020.030
4. Press the OK button.
>I3 005.000 QV> 012.050
5. Scroll through the constants of the function block inputs. 6. Change the values for a parameter set: – With OK in the Entry mode. – Left/right arrows to change decimal place – Up/down arrows to change the value of a decimal place – OK save constants or – ESC retain previous setting. 7. Press ESC to leave the parameter display.
IMPORTANT
Only constants on the function block inputs can be changed.
Adjustable Parameters for Function Blocks You can modify the function blocks used in the circuit diagram in three different ways: • All circuit diagram parameters can be adjusted in STOP mode via the function block editor. • Set point (constants) can be modified in RUN mode via the function block editor. • Set points (constants) can be modified via the PARAMETERS menu. Adjustable set point values are: • The inputs with all function blocks if constants have been used. • Switch on and off times with time switches. In RUN mode Pico GFX-70 operates with a new set point as soon as it has been modified in the parameter display and saved with OK.
Publication 1760-UM002B-EN-P - March 2005
Page 339
Pico GFX-70 Settings
Setting Date, Time and Daylight Savings Time
7-11
The devices are equipped with a real-time clock with date and time functions. The “time switch” function block can be used to implement time switch applications. If the clock has not yet been set or if Pico GFX-70 is switched on after the buffer time has elapsed, the clock starts with the setting “WE 1:00 01.05.2002”. The Pico GFX-70 clock operates with date and time so the hour, minute, day, month and year must all be set.
IMPORTANT
The time, such as: 1:00, indicates the version of the device operating system.
1. Select SET CLOCK… from the main menu. This will open the menu for setting the time. SET CLOCK DST SETTING
2. Select SET CLOCK. 3. Set the values for day, time, month and year.
HH:MM
00:27
DD.MM
05.05
YEAR :
2002
4. Press the OK button to access the Entry mode. – Use the left/right arrow keys to move between the parameters – Use the up/down arrow keys to change the value. – OK Save day and time – ESC Retain previous setting. 5. Press ESC to leave the time setting display.
Publication 1760-UM002B-EN-P - March 2005
Page 340
7-12
Pico GFX-70 Settings
Changing Between Winter/Summer time (DST)
The devices are fitted with a real-time clock. The clock has various possibilities for changing the DST setting. These are subject to different legal requirements in the EU, GB and USA.
IMPORTANT
The time change algorithm only applies to the northern hemisphere.
• NONE: no daylight saving time setting • MANUAL: a user-defined date for the DST change • EU: date defined by the European Union; Commences: last Sunday in March; Ends: last Sunday in October • GB: date defined in Great Britain; Commences: last Sunday in March; Ends: fourth Sunday in October • US: date defined in the United States of America: Commences: first Sunday in April; Ends: last Sunday in October The following applies to all DST variants: • Winter time h Summer time: On the day of conversion, the clock moves forward one hour at 2:00 to 3:00 • Summer time h Winter time: On the day of conversion, the clock moves back one hour at 3:00 to 2:00. 1. Select SET CLOCK… from the main menu. This will open the menu for setting the time. SET CLOCK DST SETTING
Publication 1760-UM002B-EN-P - March 2005
2. Select the DST SETTING menu option.
Page 341
Pico GFX-70 Settings
7-13
Selecting DST Pico GFX-70 shows you the options for the DST change. The standard setting is NONE for automatic DST changeover (Tick at NONE). NONE
✓ ▲
1. Select the required variant. 2. Press the OK button.
MANUAL EU GB
▼
US
Manual selection SUMMERTIME START DD.MM 00.00
You want to enter your own date.
SUMMERTIME END DD.MM: 00:00
IMPORTANT
The following applies to Pico GFX-70 devices: The time change algorithm always calculates the date from the year 2000. Enter the time change for the year 2000.
1. Proceed to the MANUAL menu and press 2 x OK. – Left and right arrow keys to move between the parameters – Up and down arrow keys to change the value. – OK Save day and time – ESC Retain previous setting. 2. Press ESC to leave the display. 3. Select the day and time at which summer time is to commence. 4. Select the day and time at which summer time is to end.
IMPORTANT
The same time for conversion applies as for the legally determined variants (EU, GB, US).
Publication 1760-UM002B-EN-P - March 2005
Page 342
7-14
Pico GFX-70 Settings
Activating Input Delay (debounce)
Input signals can be evaluated by Pico GFX-70 with a debounce delay. This enables, for example, the trouble-free evaluation of switches and push button actuators subject to contact bounce. In many applications, however, very short input signals have to be monitored. In this case, the debounce function can be switched off. 1. Press DEL and ALT to call up the System menu. 2. Select the SYSTEM menu.
IMPORTANT
DEBOUNCE ✓
▲
If Pico GFX-70 is password-protected you cannot open the System menu until you have “unlocked” it.
The input delay (debounce) is set with the DEBOUNCE menu item.
P BUTTONS RUN MODE CARD MODE
▼
DEBOUNCE ✓
▲
P BUTTONS
Activating Debounce If a tick ✓ is set beside DEBOUNCE, the input delay is set.
RUN MODE CARD MODE
▼
If this is not so, proceed as follows: 1. Select DEBOUNCE and press OK. Debounce mode will be activated and the display will show DEBOUNCE ✓. 2. Press ESC to return to the Status display.
Deactivating Debounce (input delay) If Pico GFX-70 is showing DEBOUNCE in the display, this means that Debounce mode has already been deactivated. 1. Otherwise select DEBOUNCE ✓. 2. Press OK. Debounce mode will be deactivated and the display will show DEBOUNCE.
Publication 1760-UM002B-EN-P - March 2005
Page 343
Pico GFX-70 Settings
IMPORTANT
7-15
How Pico GFX-70 input and output signals are processed internally is explained in Delay Times for Inputs and Outputs on page 8-5.
Activating and Deactivating Even though the cursor buttons (P buttons) have been set as push button actuator inputs in the circuit diagram, this function is not activated the P Buttons automatically. This prevents any unauthorized use of the cursor buttons. The P buttons can be activated in the System menu.
IMPORTANT
If Pico GFX-70 is password-protected you cannot open the System menu until you have “unlocked” it.
The P buttons are activated and deactivated via the P BUTTONS menu. DEBOUNCE ✓
▲
1. Press DEL and ALT to call up the System menu. 2. Select the SYSTEM menu.
P BUTTONS RUN MODE CARD MODE
▼
DEBOUNCE ✓
▲
3. Move to the cursor to the P BUTTONS menu.
P BUTTONS RUN MODE ▼
CARD MODE
Activating the P Buttons If Pico GFX-70 is displaying P BUTTONS active.
✓, this means that the P buttons are
1. Otherwise select P BUTTONS and press OK. Pico GFX-70 changes the display to P BUTTONS are activated.
DEBOUNCE ✓ P BUTTONS
▲ ✓
✓ and the P buttons
2. Press ESC to return to the Status display. The P buttons are only active in the Status display. In this display you can use the P buttons to activate inputs in your circuit diagram.
RUN MODE CARD MODE
▼
Publication 1760-UM002B-EN-P - March 2005
Page 344
7-16
Pico GFX-70 Settings
Deactivating the P Buttons 1. Select P BUTTONS
✓.
2. Press OK. Pico GFX-70 changes the display to P BUTTONS and the P buttons are deactivated.
IMPORTANT
Startup Behavior
The P buttons are automatically deactivated when loading a circuit diagram from the memory module or via PicoSoft Pro to Pico GFX-70, or when deleting a circuit diagram in Pico GFX-70.
The startup behavior is an important aid during the commissioning phase. The circuit diagram which Pico GFX-70 contains is not as yet fully wired up or the system or machine is in a state which Pico GFX-70 is not permitted to control. The outputs should not be controlled when Pico GFX-70 is switched on.
Setting the Startup Behavior
IMPORTANT
The GFX models without a display can only be started in RUN mode.
Requirement: Pico GFX-70 must contain a valid circuit diagram. 1. Switch to the System menu.
IMPORTANT
If Pico GFX-70 is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on page 7-5).
2. Specify the operating mode which Pico GFX-70 must use when the supply voltage is applied.
Publication 1760-UM002B-EN-P - March 2005
Page 345
Pico GFX-70 Settings
7-17
Activating RUN Mode If Pico GFX-70 displays RUN MODE ✓, this means that Pico GFX-70 will start in Run mode when the supply voltage is applied. DEBOUNCE
✓
▲
RUN mode is activated.
P BUTTONS RUN MODE
✓ ▼
CARD MODE
DEBOUNCE
✓
1. Otherwise select RUN MODE and press OK.
2. Press ESC to return to the Status display.
▲
P BUTTONS
Deactivating RUN Mode
RUN MODE CARD MODE
▼
1. Select RUN MODE
✓.
2. Press OK. The RUN mode function is deactivated. The default setting for Pico GFX-70 is for RUN MODE to be displayed. In other words, Pico GFX-70 starts in RUN MODE ✓ when the power is switched on. Startup behavior
Menu display
Status of Pico GFX-70 after startup
Pico GFX-70 starts in STOP mode
RUN MODE
Pico GFX-70 is in STOP mode
Pico GFX-70 starts in RUN mode
RUN MODE ✓
Pico GFX-70 is in RUN mode
Behavior When the Circuit Diagram is Deleted The setting for the startup behavior is a Pico GFX-70 device function. When the circuit diagram is deleted, this does not result in the loss of the setting selected.
Behavior During Upload/Download to Module or PC When a valid circuit diagram is transferred from Pico GFX-70 to a memory module or the PC or vice versa, the setting is still retained. IMPORTANT
The GFX models without a display can only be started in RUN mode.
Publication 1760-UM002B-EN-P - March 2005
Page 346
7-18
Pico GFX-70 Settings
Possible Faults Pico GFX-70 will not start in RUN mode: • a program is not available in Pico GFX-70. • you have selected Pico GFX-70 startup in STOP MODE (RUN MODE menu).
Card Startup Behavior The startup behavior with memory module is for applications where unskilled personnel change the memory module under no-voltage conditions. Pico GFX-70 only starts in the Run mode if a memory module with a valid program is inserted. If the program on the memory module is different to the program in Pico GFX-70, the program from the card is loaded into the processor and the processor starts in the RUN mode. Switch to the System menu.
IMPORTANT
If Pico GFX-70 is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on page 7-5).
Activation of Card Mode Requirement: RUN MODE is active. If Pico GFX-70 displays CARD MODE ✓, this means that when the power supply is switched on, Pico GFX-70 will only start in RUN mode if a memory module with a valid program has been inserted. DEBOUNCE
✓
▲
Pico GFX-70 will start up with the program on the card.
P BUTTONS RUN MODE
✓
CARD MODE
✓
1. Otherwise select CARD MODE and press OK.
▼
Publication 1760-UM002B-EN-P - March 2005
2. Press ESC to return to the Status display.